Mist Eliminator Filter in Intake Hood (10HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
6000 737 794 851 908 961 1012 1061
6400 786
839 893 947 998 1047 1094
6800 836
886 937 987 1036 1083 1129
7200 885
931 979 1027 1074 1119 1163
7600 934
978 1024 1069 1114 1159 1200
8000 983 1025 1068 1111
1154 1196 1237
Barometric Hood, 2" Pleated Filters (7.5HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
6000 599 660 716 769 818 866 911
6400 639
695 748 798 846 892 935
6800 679
733 783 831 877 921 963
7200 719
769 817 863 907 949 990
7600 759
808 854 897 940 980 1020
8000 799
845 889 931 972 1011 1049
SUPPLY
EXHAUST
RPM Range
Low Standard Unit
Medium Optional Kit
High Optional Kit
Mist Eliminator Filter in Intake Hood (15HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
8000 427 470 512 552 591 630 667
8800 469
509 547 584 621 656 691
9600 512
548 583 618 651 684 717
10400 555
589 621 653 684 715 746
11200 597
629 659 689 718 747 776
12000 640 670 698 726 754 781 808
Barometric Hood, 2" Pleated Filters (15HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
8000 437 480 521 551 600 639 676
8800 481
520 558 595 631 665 701
9600 525
561 596 630 663 696 728
10400 569
602 634 665 657 727 758
11200 612
643 674 703 732 761 789
12000 656
685 713 741 768 795 822
SUPPLY
EXHAUST
RPM Range
Low Standard Unit
Medium Optional Kit
High Optional Kit
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
Blower RPM for DH
Blower RPM for DJ