Tranquility® High Efficiency (TR) Series Submittal Data Models TRH/V 006 - 060 60Hz - HFC-410A English Language/I-P Units Submittal Data - I-P Units Unit Designation: Job Name: Architect: Engineer: Contractor: Performance Data Cooling Capacity: Btuh EER: Heating Capacity: Btuh COP: Revised: 18 July, 2013 Ambient Air Temp: °F Entering Water Temp (Clg): °F Entering Air Temp (Clg): °F Entering Water Temp (Htg): °F Entering Air Temp (Htg): °F Airflow: CFM Fan Speed or Motor/RPM/Turns: Operat
Tranquility® High Efficiency (TR) Series Submittal Data Models TRH/V 006 - 060 60Hz - HFC-410A English Language/S-I Units Submittal Data - S-I Units Unit Designation: Job Name: Architect: Engineer: Contractor: Performance Data Cooling Capacity: kW EER: Heating Capacity: kW COP: Revised: 18 July, 2013 Ambient Air Temp: °C Entering Water Temp (Clg): °C Entering Air Temp (Clg): °C Entering Water Temp (Htg): °C Entering Air Temp (Htg): °C Airflow: l/s Fan Speed or Motor/RPM/Turns: Operating
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Table of Contents *Page Number Unit Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 TR Series Nomenclature. . . . . . . . . . .
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Unit Features THE Tranquility® TR SERIES UNIT FEATURES The award winning Tranquility Series raises the bar for water-source heat pump efficiencies, features and application flexibility. Not only does the Tranquility® TR exceed ASHRAE 90.1 efficiencies, but it also uses EarthPure® HFC-410A zero ozone depletion refrigerant, making it an extremely environmentally-friendly option.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Selection Procedure Reference Calculations Heating Cooling HE LWT = EWT GPM x 500 HC CFM x1.08 LAT = EAT + LWT = EWT + HR GPM x 500 LAT (DB) = EAT (DB) - LC = TC - SC SC CFM x1.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Selection Procedure Step 1 Determine the actual heating and cooling loads at the desired dry bulb and wet bulb conditions. Step 2 Obtain the following design parameters: Entering water temperature, water flow rate in GPM, air flow in CFM, water flow pressure drop and design wet and dry bulb temperatures. Air flow CFM should be between 300 and 450 CFM per ton.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P TR Series Nomenclature 1 MODEL TYPE 2 TR 3 H 4 5 6 7 036 A 8 G 9 C 10 3 11 0 12 C 13 L 14 15 B S TR = TRANQUILITY HIGH EFFICIENCY 410A ® SUPPLY AIR OPTIONS CONFIGURATION H = HORIZONTAL V = VERTICAL S = STANDARD B = BACK DISCHARGE, HORIZONTAL ONLY Y = BACK DISCHARGE, HIGH STATIC HORIZONTAL 015-060 COMMERCIAL ONLY T = TOP DISCHARGE, VERTICAL ONLY V = TOP DISCHARGE, HIGH STATIC VERTICAL 015-060 COMMERCIAL ONLY S = STRAIGHT DISCHA
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – AHRI/ASHRAE/ISO 13256-1 ASHRAE/AHRI/ISO 13256-1. English (I-P) Units Water Loop Heat Pump Model Cooling 86°F Ground Water Heat Pump Heating 68°F Cooling 59°F Capacity EER Capacity Capacity COP Btuh Btuh/W Btuh Btuh Ground Loop Heat Pump Heating 50°F EER Btuh/W Capacity Btuh Cooling 77°F COP Capacity Btuh EER Btuh/W Heating 32°F Capacity COP Btuh TR-006 5,800 13.2 7,500 4.7 6,900 21.1 6,200 4.0 6,200 15.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – Selection Notes For operation in the shaded area when water is used in lieu of an antifreeze solution, the LWT (Leaving Water Temperature) WPD Cooling EAT such 80/67°F must be calculated. Flow must be maintained to a-level EWT that theGPM LWT is maintained above 40°F [4.4°C] when the Sens/ Airflow °F Tot PSI clipped FT (see TC below).
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TR H/V 006 220 CFM Nominal (Rated) Airflow EWT GPM °F 20 30 40 50 60 70 80 85 90 100 110 120 1.5 1.5 0.8 0.8 1.1 1.1 1.5 1.5 0.8 0.8 1.1 1.1 1.5 1.5 0.8 0.8 1.1 1.1 1.5 1.5 0.8 0.8 1.1 1.1 1.5 1.5 0.8 0.8 1.1 1.1 1.5 1.5 0.8 0.8 1.1 1.1 1.5 1.5 0.8 0.8 1.1 1.1 1.5 1.5 0.8 0.8 1.1 1.1 1.5 1.5 0.8 0.8 1.1 1.1 1.5 1.5 0.8 0.8 1.1 1.1 1.5 1.5 0.8 0.8 1.1 1.1 1.5 1.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TR H/V 009 325 CFM Nominal (Rated) Airflow EWT GPM °F 20 30 40 50 60 70 80 85 90 100 110 120 2.3 2.3 1.1 1.1 1.7 1.7 2.3 2.3 1.1 1.1 1.7 1.7 2.3 2.3 1.1 1.1 1.7 1.7 2.3 2.3 1.1 1.1 1.7 1.7 2.3 2.3 1.1 1.1 1.7 1.7 2.3 2.3 1.1 1.1 1.7 1.7 2.3 2.3 1.1 1.1 1.7 1.7 2.3 2.3 1.1 1.1 1.7 1.7 2.3 2.3 1.1 1.1 1.7 1.7 2.3 2.3 1.1 1.1 1.7 1.7 2.3 2.3 1.1 1.1 1.7 1.7 2.3 2.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TR H/V 012 400 CFM Nominal (Rated) Airflow EWT GPM °F 20 30 40 50 60 70 80 85 90 100 110 120 3.0 3.0 1.5 1.5 2.3 2.3 3.0 3.0 1.5 1.5 2.3 2.3 3.0 3.0 1.5 1.5 2.3 2.3 3.0 3.0 1.5 1.5 2.3 2.3 3.0 3.0 1.5 1.5 2.3 2.3 3.0 3.0 1.5 1.5 2.3 2.3 3.0 3.0 1.5 1.5 2.3 2.3 3.0 3.0 1.5 1.5 2.3 2.3 3.0 3.0 1.5 1.5 2.3 2.3 3.0 3.0 1.5 1.5 2.3 2.3 3.0 3.0 1.5 1.5 2.3 2.3 3.0 3.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TR H/V 015 525 CFM Nominal (Rated) Airflow EWT GPM °F 20 30 40 50 60 70 80 85 90 100 110 120 3.8 3.8 1.9 1.9 2.8 2.8 3.8 3.8 1.9 1.9 2.8 2.8 3.8 3.8 1.9 1.9 2.8 2.8 3.8 3.8 1.9 1.9 2.8 2.8 3.8 3.8 1.9 1.9 2.8 2.8 3.8 3.8 1.9 1.9 2.8 2.8 3.8 3.8 1.9 1.9 2.8 2.8 3.8 3.8 1.9 1.9 2.8 2.8 3.8 3.8 1.9 1.9 2.8 2.8 3.8 3.8 1.9 1.9 2.8 2.8 3.8 3.8 1.9 1.9 2.8 2.8 3.8 3.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TR H/V 018 600 CFM Nominal (Rated) Airflow EWT GPM °F 20 30 40 50 60 70 80 85 90 100 110 120 4.5 4.5 2.3 2.3 3.4 3.4 4.5 4.5 2.3 2.3 3.4 3.4 4.5 4.5 2.3 2.3 3.4 3.4 4.5 4.5 2.3 2.3 3.4 3.4 4.5 4.5 2.3 2.3 3.4 3.4 4.5 4.5 2.3 2.3 3.4 3.4 4.5 4.5 2.3 2.3 3.4 3.4 4.5 4.5 2.3 2.3 3.4 3.4 4.5 4.5 2.3 2.3 3.4 3.4 4.5 4.5 2.3 2.3 3.4 3.4 4.5 4.5 2.3 2.3 3.4 3.4 4.5 4.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TR H/V 024 800 CFM Nominal (Rated) Airflow EWT GPM °F 20 30 40 50 60 70 80 85 90 100 110 120 6.0 6.0 3.0 3.0 4.5 4.5 6.0 6.0 3.0 3.0 4.5 4.5 6.0 6.0 3.0 3.0 4.5 4.5 6.0 6.0 3.0 3.0 4.5 4.5 6.0 6.0 3.0 3.0 4.5 4.5 6.0 6.0 3.0 3.0 4.5 4.5 6.0 6.0 3.0 3.0 4.5 4.5 6.0 6.0 3.0 3.0 4.5 4.5 6.0 6.0 3.0 3.0 4.5 4.5 6.0 6.0 3.0 3.0 4.5 4.5 6.0 6.0 3.0 3.0 4.5 4.5 6.0 6.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TR H/V 030 1,000 CFM Nominal (Rated) Airflow EWT GPM °F 20 30 40 50 60 70 80 85 90 100 110 120 7.5 7.5 3.8 3.8 5.6 5.6 7.5 7.5 3.8 3.8 5.6 5.6 7.5 7.5 3.8 3.8 5.6 5.6 7.5 7.5 3.8 3.8 5.6 5.6 7.5 7.5 3.8 3.8 5.6 5.6 7.5 7.5 3.8 3.8 5.6 5.6 7.5 7.5 3.8 3.8 5.6 5.6 7.5 7.5 3.8 3.8 5.6 5.6 7.5 7.5 3.8 3.8 5.6 5.6 7.5 7.5 3.8 3.8 5.6 5.6 7.5 7.5 3.8 3.8 5.6 5.6 7.5 7.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TR H/V 036 1,200 CFM Nominal (Rated) Airflow EWT ºF 20 30 40 50 60 70 80 85 90 100 110 120 Performance capacities shown in thousands of Btuh WPD GPM 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.0 4.5 4.5 6.8 6.8 9.0 9.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TR H/V 042 1,350 CFM Nominal (Rated) Airflow EWT GPM °F 20 30 40 50 60 70 80 85 90 100 110 120 10.5 10.5 5.3 5.3 7.9 7.9 10.5 10.5 5.3 5.3 7.9 7.9 10.5 10.5 5.3 5.3 7.9 7.9 10.5 10.5 5.3 5.3 7.9 7.9 10.5 10.5 5.3 5.3 7.9 7.9 10.5 10.5 5.3 5.3 7.9 7.9 10.5 10.5 5.3 5.3 7.9 7.9 10.5 10.5 5.3 5.3 7.9 7.9 10.5 10.5 5.3 5.3 7.9 7.9 10.5 10.5 5.3 5.3 7.9 7.9 10.5 10.5 5.3 5.3 7.9 7.9 10.5 10.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TR H/V 048 1,600 CFM Nominal (Rated) Airflow EWT GPM °F 20 30 40 50 60 70 80 85 90 100 110 120 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.0 6.0 6.0 9.0 9.0 12.0 12.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TR H/V 060 2,000 CFM Nominal (Rated) Airflow EWT GPM °F 20 30 40 50 60 70 80 85 90 100 110 120 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.0 7.5 7.5 11.3 11.3 15.0 15.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Correction Tables – Entering Air Temperature Cooling Corrections Sens Clg Cap Multipliers - Entering DBº F Ent Air WBº F Total Clg Capacity 65 50 0.7800 55 0.8327 60 0.8954 Power Heat of Rejection * 0.9972 0.8243 * 0.9980 0.8667 * * 0.9988 0.9169 70 75 80 80.6 85 90 95 0.9778 * * * * * * 0.8966 1.0556 * * * * * 0.7505 0.9184 1.1056 * * * 65 0.9681 0.6778 0.8992 1.1213 1.1480 1.3439 * * 0.9996 0.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Correction Tables – Antifreeze and Water Pressure Drop Adder for Options Cooling Heating EWT 90°F EWT 30°F WPD Corr. Fct. EWT 30°F Antifreeze Type Antifreeze % Total Cap Sens Cap Power Htg Cap Power Water 0 1.000 1.000 1.000 1.000 1.000 1.000 5 0.995 0.995 1.003 0.989 0.997 1.070 15 0.986 0.986 1.009 0.968 0.990 1.210 25 0.978 0.978 1.014 0.947 0.983 1.360 5 0.997 0.997 1.002 0.989 0.997 1.070 15 0.990 0.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Blower Performance Data – Standard Unit Airflow in CFM with Wet Coil and Clean Air Filter Model Fan Speed MEDIUM TR 009 MEDIUM TR 012 MEDIUM TR 018 TR 024 TR 030 TR 036 TR 042 TR 048 TR 060 Airflow (cfm) at External Static Pressure (in. wg) 0.00 0.05 HIGH TR 006 TR 015 Rated Min Airflow CFM 220 150 LOW HIGH 325 225 LOW HIGH 400 300 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Blower Performance Data – High Static Model Fan Speed Rated Airflow Min CFM Airflow (cfm) at External Static Pressure (in. wg) 0.00 0.05 0.10 HS HI HS MED TR 015 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 774 764 755 745 735 715 696 676 637 519 480 0.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Blower Performance Data with ClimaDry® Fan Speed Model MEDIUM TR 030 MEDIUM 800 600 0.00 Airflow (cfm) Standard TR w/ ClimaDry® (in. wg) 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Blower Performance Data – High Static with ClimaDry® Model Fan Speed Rated Airflow Min CFM Airflow (cfm) at External Static Pressure w/ ClimaDry® (in. wg) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P ClimaDry® II Option – Benefits and Application ClimaDry® II Modulating Reheat Option ClimateMaster’s patented ClimaDry® II Dehumidification option is an innovative means of providing modulating reheat without the complication of refrigeration controls. ClimaDry® II is hot gas generated reheat, which utilizes one of the biggest advantages of a Water-Source Heat Pump (WSHP), the transfer of energy through the water piping system.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P ClimaDry® II Option – Benefits and Application Most ClimateMaster heat pumps have a sensible-to-total (S/T) ratio of 0.72 to 0.82. Therefore, approximately, 25% of the cooling capacity is dedicated to latent cooling capacity (moisture removal). When selecting a unit with ClimaDry® II, the space sensible and latent loads should be calculated.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P ClimaDry® II Option – Sequence of Operation ClimaDry® II Sequence of Operation - A heat pump equipped with ClimaDry® II can operate in three modes; cooling, cooling with reheat (dehumidification), and heating. The cooling/heating modes are like any other ClimateMaster WSHP. The reversing valve (“O” signal) is energized in cooling, along with the compressor contactor(s) and blower relay. In the heating mode the reversing valve is de-energized.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P ClimaDry® II Option – Sequence of Operation • 1st Stage Heating: A simultaneous call from (G) and (Y1) to the (G) and (Y1) terminals of the DXM control board will bring the unit on in 1st Stage Heating. of operation. The proportional controller signals the motorized valve based on the supply air temperature of the supply air sensor.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Physical Data TR Series 006 009 17 18.5 012 Compressor (1 each) Factory Charge HFC-410A - (oz.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P TR - Horizontal – Dimensional Data Electrical Knockouts Overall Cabinet Horizontal Model A Width B Length C Height Horizontal Model H 1/2” J 1/2” K 3/4” Low Voltage Low Voltage Power Supply 006 - 012 in cm 22.5 57.2 40.3 102.4 11.5 29.2 015 - 018 in cm 22.4 56.9 48.3 122.7 17.5 44.5 006 - 012 in cm 2.9 7.4 5.9 15.0 8.9 22.6 024 - 030 in cm 22.4 56.9 48.3 122.7 18.3 46.5 015 - 060 in cm 4.0 10.2 7.0 18.8 10.0 25.
TR Series 60Hz - HFC-410A Submittal Data TR TR TR - Horizontal – Dimensional Data LEFT RETURN 2' [61cm] Service Access RIGHT RETURN CSP Front Front EE Left Return Right Return 5 AA 3.3" [83.8mm] 4 Straight Discharge 3 Blower Outlet 1.1” A Front-View D 0.7" [17.8mm] E Condensate 3 / 4" FPT C V Model 006-012 015-030 036-042 048-060 U 40.3 [102.4] 48.4 [122.9] 53.3 [135.4] 68.0 [172.7] V 24.6 [62.5] 24.6 [62.5] 24.6 [62.5] 27.6 [70.1] W 20.3 [51.6] 20.3 [51.6] 20.3 [51.6] 23.3 [59.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P TR - Vertical Upflow – Dimensional Data Overall Cabinet Vertical Upflow Model A Width B Depth C Height 006 - 012 in cm 22.5 57.2 21.3 54.1 22.5 57.2 015 - 030 in cm 22.4 56.9 22.4 56.9 40.5 102.9 036 - 042 in cm 22.4 56.9 25.4 64.5 46.5 118.1 048 - 060 in cm 25.4 64.5 29.1 73.9 50.5 128.3 Electrical Knockouts Vertical Model J 1/2” K 1/2” L 3/4” Low Voltage Low Voltage Power Supply 006 - 012 in cm 2.9 7.4 5.9 15.0 8.1 20.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P TR - Vertical Upflow – Dimensional Data Field Installed Discharge Flange Access Panels Standard Filter Bracket N P Front O N BSP ASP Front P Air Coil B Q Air Coil Side Air Coil Side Top View-Right Return Top View-Left Return S R S U A CSP CAP (Right Rtn Opposite Side) M R Isometric View 2' [61cm] Service U Air Coil Opptional 2' [61cm] Service Access Left Rtn O Air Coil T T C C CSP Front CSP Back Right Return Right Vie
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Corner Weights for TRH Series Units Total Left-Front* Right-Front* Left-Back* Right-Back* 110 40 20 25 25 kg 50 18 9 11 11 Lbs 112 41 21 25 25 Model TRH006 TRH009 TRH012 TRH015 TRH018 TRH024 TRH030 TRH036 TRH042 TRH048 TRH060 Lbs kg 51 19 10 11 11 Lbs 121 45 22 27 27 kg 55 20 10 12 12 33 Lbs 163 54 44 33 kg 74 24 20 15 15 Lbs 168 55 45 34 34 kg 76 25 20 15 15 Lbs 184 61 50 37 37 kg 83
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Electrical Data – Standard Unit TR Model 006 009 012 015 018 024 030 036 042 048 060 Voltage Code Rated Voltage Voltage Min/Max G 208-230/60/1 197/254 QTY RLA LRA Fan Motor FLA 1 3.3 17.7 0.40 Compressor Total Unit FLA Min Circuit Amp Max Fuse/ HACR 3.7 4.5 15 E 265/60/1 239/292 1 2.9 13.5 0.40 3.3 4.0 15 G 208-230/60/1 197/254 1 4.5 22.2 0.92 5.4 6.5 15 E 265/60/1 239/292 1 3.8 18.8 0.70 4.5 5.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Electrical Data – High Static Blower TR Model 015 018 024 030 036 042 048 060 QTY RLA LRA Fan Motor FLA 197/254 1 6.0 29.0 1.20 7.2 8.7 15 265/60/1 239/292 1 5.4 28.0 0.86 6.3 7.6 15 G 208-230/60/1 197/254 1 7.2 33.0 1.50 8.7 10.5 15 E 265/60/1 239/292 1 5.9 28.0 1.30 7.2 8.7 15 G 208-230/60/1 197/254 1 12.8 58.3 1.50 14.3 17.5 30 E 265/60/1 239/292 1 9.6 54.0 1.30 10.9 13.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Electrical Data – Internal Secondary Pump TR Model 006 009 012 015 018 024 030 036 042 048 060 Voltage Min/Max Compressor Fan Motor FLA Total Unit FLA Max Fuse/ HACR Rated Voltage G 208-230/60/1 197/254 1 3.3 17.7 0.40 4.1 0.4 4.9 15 E 265/60/1 239/292 1 2.9 13.5 0.40 4.0 0.7 4.7 15 G 208-230/60/1 197/254 1 4.5 22.2 0.92 5.8 0.4 7.0 15 E 265/60/1 239/292 1 3.8 18.8 0.70 5.2 0.7 6.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Electrical Data – High Static with Internal Secondary Pump TR Model 015 018 024 030 036 042 048 060 Fan Motor FLA Total Unit FLA Pump FLA Min Circuit Amp Max Fuse/ HACR 29.0 1.20 7.6 0.4 8.9 15 Compressor Voltage Min/Max QTY RLA LRA Voltage Code Rated Voltage G 208-230/60/1 197/254 1 6.0 E 265/60/1 239/292 1 5.4 28.0 0.86 7.0 0.7 8.3 15 G 208-230/60/1 197/254 1 7.2 33.0 1.50 9.5 0.8 11.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Electrical Data with ClimaDry® TR Model 024 030 036 042 048 060 Compressor Voltage Min/Max QTY RLA LRA Fan Motor FLA Total Unit FLA 58.3 1.50 15.1 0.8 18.3 30 9.6 54.0 1.30 11.6 0.7 14.0 20 Voltage Code Rated Voltage G 208-230/60/1 197/254 1 12.8 E 265/60/1 239/292 1 Min Pump Circuit FLA Amp Max Fuse/ HACR H 208-230/60/3 197/254 1 7.7 55.4 1.50 10.0 0.8 11.9 15 *F *460/60/3 414/506 1 3.6 28.0 0.76 5.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Electrical Data – ClimaDry® & High Static Fan TR Model 024 030 036 042 048 060 Voltage Code Rated Voltage G 208-230/60/1 Voltage Min/Max Compressor LRA Fan Motor FLA Total Unit FLA Pump FLA Min Circuit Amp Max Fuse/ HACR QTY RLA 197/254 1 12.8 58.3 1.50 15.1 0.8 18.3 30 239/292 1 9.6 54.0 1.30 11.6 0.7 14.0 20 E 265/60/1 H 208-230/60/3 197/254 1 7.7 55.4 1.50 10.0 0.8 11.9 15 *F *460/60/3 414/506 1 3.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P TR Series Wiring Diagram Matrix Model Wiring Diagram Part Number Electrical Control 96B0006N01 CXM 96B0006N09 96B0006N02 96B0006N04 208-230/60/1, 265/60/1 DXM 96B0104N05 CXM DXM - 96B0008N03 96B0008N04 96B0008N09 LON MPC 96B0008N01 96B0008N02 ETL - 96B0007N07 96B0008N08 LON MPC 208-230/60/3 96B0007N04 TR Series Three Phase (460V Style) ® - 96B0007N01 96B0007N02 LON MPC ClimaDry 96B0007N03 96B0007N06 LON MPC 96B0006N10 TR Ser
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Single Phase TR with ClimaDry® ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
6+6.' . %KTEWKV $TGCMGT 4GNC[ EQPVCEVU Ä 0 % 4GNC[ EQPVCEVU Ä 0 1 01 4GNC[ EQPVCEVU Ä 0 1 5QNGPQKF %QKN 5YKVEJÄ .155 1( %*#4)' 5YKVEJÄ *KIJ RTGUUWTG $.7 1RVKQP ,WORGT Ä HKGNF ENKRRGF 126+10#. 6GUV 2KPU $.7 ;'. ) ; $4 5'' 016' )4; % 4 ; %1/ $4 $4) $40 1HH 1P $40 %%) ;'. %% 5VCVWU .'& ;'. $.- %QORTGUUQT 4GNC[ %% ) 725 &+5#$.'& '0#$.'& 56#)' 016 75'& &&% 176276 &&% /14/#. HCWNV &KR 5YKVEJ ,9 (2 .QY 6GOR ,9 (2 .
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Single Phase TR Units with DXM Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 208/230V TR Units with CXM Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 208/230V TR Units with DXM Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 460/575V TR Units with CXM Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 460/575V TR Units with DXM Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 460/575V TR Units with CXM And LON Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 460/575V TR Units with DXM & LON Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 460/575V TR Units with CXM & MPC Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 460/575V TR Units with DXM & MPC Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® (TR) Series 60Hz Engineering Specifications – Page 1 General: Furnish and install ClimateMaster Tranquility® “TR” Water-Source Heat Pumps, as indicated on the plans. Equipment shall be completely assembled, piped and internally wired. Capacities and characteristics as listed in the schedule and the specifications that follow.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® (TR) Series 60Hz Engineering Specifications – Page 2 Cabinets shall have separate holes and knockouts for entrance of line voltage and low voltage control wiring. All factory-installed wiring passing through factory knockouts and openings shall be protected from sheet metal edges at openings by plastic ferrules. Supply and return water connections shall be copper FPT fittings.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® (TR) Series 60Hz Engineering Specifications – Page 3 Option: The unit will be supplied with internally mounted secondary pump for primary/secondary applications, including one-pipe systems. Option: The unit will be supplied with cupro-nickel coaxial water to refrigerant heat exchanger. Option: The refrigerant to air heat exchanger shall be coated. Option: Unit shall include ClimaDry® II reheat option.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® (TR) Series 60Hz Engineering Specifications – Page 4 g. Condensate overflow electronic protection. h. Option to reset unit at thermostat or disconnect. i. Automatic intelligent reset. Unit shall automatically reset the unit 5 minutes after trip if the fault has cleared. If a fault occurs 3 times sequentially without thermostat meeting temperature, then lockout requiring manual reset will occur. j. Ability to defeat time delays for servicing. k.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® (TR) Series 60Hz Engineering Specifications – Page 5 Remote Service Sentinel (CXM/DXM): Solid state control system shall communicate with thermostat to display (at the thermostat) the unit status, fault status, and specific fault condition, as well as retrieve previously stored fault that caused unit shutdown. The Remote Service Sentinel allows building maintenance personnel or service personnel to diagnose unit from the wall thermostat.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® (TR) Series 60Hz Engineering Specifications – Page 6 o. p. q. r. Heating command. Fan “ON/AUTO” command. Fault reset command. Itemized fault code revealing reason for specific shutdown fault (any one of 7). This option also provides the upgraded 75VA control transformer with load side short circuit and overload protection via a built in circuit breaker.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® (TR) Series 60Hz Engineering Specifications – Page 7 d. Multistage Digital Automatic Changeover (ATA22U01) Thermostat shall be multi-stage (2H/2C), manual or automatic changeover with HEAT-OFF-COOL-AUTO-EM HEAT system settings and fan ON-AUTO settings. Thermostat shall have an LCD display with temperature, setpoint(s), mode, and status indication. The temperature indication shall be selectable for ºF or ºC.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Notes: ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Notes: ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TR Series 60Hz - HFC-410A Submittal Data Eng/I-P Revision History Date: Item: Action: EAT Minimum Limit ClimaDry® Updated 02/05/13 Electrical Data Tables Miscellaneous Edits 09/27/12 EAT Limits Recommended Minimum Installation Clearances for Vertical Units * Updates to Text - ClimaDry® Option Added 07/18/13 08/23/12 Unit Hanger Detail Updated 05/22/12 ClimaDry WPD Table Size 015, 018 w/ClimaDry Updated, Removed 02/20/12 Engineering Specifications Updated 02/02/12 ClimaDry II Option I