Electrical - HWG Wiring
Low Voltage Field Wiring
ELECTRICAL - LOW VOLTAGE WIRING
Figure 24: 50YGS Low Voltage Field Wiring Figure 25: 50YGP Low Voltage Field Wiring
The primary low voltage wiring from the GT-PCS is to the Air
Handler.
HWG Module Wiring - For “Outdoor” Compressor Section
The HWG module should be wired to a 115 or 240 vac power
supply as shown in the wire diagrams. A safety disconnect
should be installed at the HWG module as required by code
to allow servicing of the module. DO NOT energize the pump
until all HWG piping is completed and air is purged from the
water piping to avoid running the pump “dry”.
Remote HWG Kit Wiring Installation
1. Disconnect power to outdoor unit and HWG kit module.
2. Open access panel to locate factory-installed terminal
block inside the HWG module.
3. Connect four T-stat eld-supplied wires on the opposite
side of terminal block where thermistors are connected.
Next, route T-stat wires thru HWG module kit cabinet to
the outdoor unit.
4. Remove outdoor unit side panel to access control box
5. Install factory-supplied terminal block as shown in Fig.
23a.
6. Locate violet jumper that is installed in “T5” terminal on
DXM2.
Fig. 23a: HWG Kit Wiring Diagram
7. Cut the jumper and connect one end of the factory
supplied blue color wires to the cut jumper using wire
nuts and connect the other side of the blue wires to the
terminal block in outdoor unit.
8. Connect factory-supplied brown wire from “C” on DXM2
to terminal block. Connect factory-supplied red wire
from “R” on DXM2 to “COM” on K2 relay on DXM2 and
connect the other red wire from “NC” to terminal block
(refer to Fig. 23a).
9. Verify proper wiring connections before turning on power.
YGP