Specifications
39
GT-PCS Split Units - 60Hz Puron
®
Created: 29 Aug., 2013
DXM2 Layout and Connections
Figure 30: DXM2 Layout and Connections
Low Water Temperature Cutout Selection
The DXM2 control allows the fi eld selection of low water
(or water-antifreeze solution) temperature limit by clipping
jumper JW3, which changes the fault cutout temperature
associated with thermistor LT1. Note that the LT1 thermistor
is located on the refrigerant line between the coaxial heat
exchanger and expansion device (TXV). Therefore, LT1 is
sensing refrigerant temperature, not water temperature,
which is a better indication of how water fl ow rate/
temperature is affecting the refrigeration circuit.
The factory setting for LT1 is for systems using water (30°F
[-1.1°C] refrigerant temperature cutout or fallout). In low water
temperature (extended range) applications with antifreeze
(most ground loops), jumper JW3 should be clipped as
shown in Figure 30 to change the setting to 10°F [-12.2°C]
refrigerant cutout or fallout temperature, a more suitable
temperature when using an antifreeze solution. All residential
units include water/refrigerant circuit insulation to prevent
internal condensation, which is required when operating with
entering water temperatures below 59°F [15°C].
P1
Alarm
Relay
Comp
Relay
O
Y1
Y2
W
G
C
R
AL1
24Vdc
EH1
EH2
P6
R
C
Off On
JW3
A
OVR
ESD
C
R
NSB
AL2
JW1
Acc1
Relay
Acc2
Relay
H
COM1
NC1
NO1
COM2
NC2
NO2
P3
CO
RV
RV
LT1
LT1
LT2
LT2
LP
LP
HP
HP
P7
Status
Fault
R
R
CC
CCG
CO
S1
S2
1
12
1
4
e
sU yr
ot
c
aF
(240Vac)
Com
N.O.
Fan Enable
Micro
U1
Off On
P2
COH
COM
AO2
P11
Gnd
T1
P10
T2 T2 T3 T3 T4 T4
T5
P9
T5
T6 T6
A0-1 A0-2
Off On
S3
RV
Relay
CCH
Relay
Test
P5
B-
Gnd
P4
A+ 24V
(240Vac)
Fan Speed
N.O.
N.C.
12V
OUT
Gnd
P8
IN
NC
P12
1 2 3 4
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Service tool
connection
Communicating
stat connection
Conventional
stat connection
Cabinet
temperature
sensor
(with variable
speed pump)
24V to compressor
second-stage solenoid
for Y2/full
load capacity
Use 4 mounting screws
#6 sheet metal screw
1” long
Configure
modulating valve
or variable
speed pump
Variable
speed pump
Entering
water temp
Leaving
water temp
Leaving
air temp
Electric heat
connection
Factory low
voltage molex
connection for
unit harness
Entering Hot water
Temperature
Compressor Discharge
temperature
ECM Motor
Connection
Test Button
to Speed up
Time Delays
Communications
and HWG
Settings
Water Coil
Low Temp
Limit Setting.
JWT-LT1 jumper
should be clipped
for low temp
(antifreeze)
operation
Accessory
relays refer
to DXM2 AOM
for configuration
ECM Motor Connection
(Not applicable to split
systems)