Table 18b: Performance Data — 50YGS/50YGP Model 038 Full Load
1250 CFM Nominal (Rated) Airfl ow Cooling, 1250 CFM Nominal (Rated) Airfl ow Heating
EWT
°F
Cooling - EAT 80/67°F Heating - EAT 70°F
GPM
WPD
TC SC kW HR EER LWT
YGS
HWC
YGP
HWC
GPM
WPD
HC kW HE COP LAT LWT
YGS
HWC
YGP
HWC
PSI FT PSI FT
20
2.1 1.5 3.4 45.7 31.2 1.88 52.2 24.4 70.0 1.9 1.8 9.0 8.3 19.2 24.7 1.98 17.9 3.5 86.2 16.0 2.1 2.0
30
2.6 1.2 2.8 45.7 31.2 1.88 52.2 24.4 70.0 1.9 1.8 4.5 2.6 6.0 27.3 2.02 20.4 3.6 88.1 20.9 2.4 2.3
2.6 1.2 2.8 45.7 31.2 1.88 52.2 24.4 70.0 1.9 1.8 6.8 4.6 10.6 28.6 2.05 21.6 3.6 89.2 23.6 2.6 2.5
2.6 1.2 2.8 45.7 31.2 1.88 52.2 24.4 70.0 1.9 1.8 9.0 6.9 16.0 29.4 2.06 22.3 3.6 89.7 25.0 2.6 2.5
40
3.5 1.4 3.2 45.7 31.2 1.88 52.2 24.4 70.0 1.9 1.8 4.5 2.0 4.7 31.5 2.10 24.3 4.1 91.3 29.2 2.9 2.8
3.5 1.4 3.2 45.7 31.2 1.88 52.2 24.4 70.0 1.9 1.8 6.8 3.8 8.8 33.1 2.13 25.8 4.1 92.5 32.3 3.1 2.9
3.5 1.4 3.2 45.7 31.2 1.88 52.2 24.4 70.0 1.9 1.8 9.0 5.9 13.6 34.0 2.15 26.7 3.9 93.1 34.1 3.2 3.0
50
4.5 1.7 3.9 45.5 31.1 1.93 52.1 23.5 73.1 1.9 1.8 4.5 1.7 3.9 35.7 2.18 28.3 4.3 94.4 37.4 3.4 3.2
5.2 2.1 4.9 45.7 31.2 1.88 52.2 24.4 70.0 1.9 1.8 6.8 3.3 7.6 37.6 2.22 30.0 4.4 95.8 41.1 3.6 3.4
5.2 2.1 4.9 45.7 31.2 1.88 52.2 24.4 70.0 1.9 1.8 9.0 5.2 11.9 38.6 2.24 31.0 4.5 96.6 43.1 3.7 3.5
60
4.5 1.5 3.5 44.0 30.6 2.12 51.2 20.7 82.8 2.6 2.5 4.5 1.5 3.5 40.0 2.27 32.2 4.6 97.5 45.7 3.9 3.7
6.8 2.9 6.8 45.2 31.0 1.97 51.9 22.9 75.4 2.1 2.0 6.8 2.9 6.8 42.2 2.32 34.2 4.7 99.2 49.9 4.1 3.9
9.0 4.7 10.8 45.6 31.1 1.90 52.1 24.0 71.6 1.9 1.8 9.0 4.7 10.8 43.4 2.35 35.4 4.7 100.0 52.1 4.2 4.0
70
4.5 1.5 3.4 41.8 29.8 2.34 49.8 17.9 92.1 3.4 3.2 4.5 1.5 3.4 44.3 2.37 36.2 4.8 100.7 53.9 4.4 4.2
6.8 2.8 6.4 43.5 30.4 2.17 50.9 20.0 85.1 2.8 2.7 6.8 2.8 6.4 46.8 2.42 38.5 4.9 102.6 58.6 4.6 4.4
9.0 4.4 10.1 44.2 30.7 2.09 51.4 21.1 81.4 2.5 2.4 9.0 4.4 10.1 48.2 2.46 39.8 5.0 103.6 61.1 4.7 4.5
80
4.5 1.5 3.4 39.2 28.7 2.61 48.1 15.0 101.4 4.3 4.1 4.5 1.5 3.4 48.7 2.47 40.3 5.0 104.0 62.1 4.8 4.6
6.8 2.7 6.2 41.1 29.5 2.41 49.4 17.1 94.6 3.7 3.5 5.6 2.0 4.7 50.4 2.51 41.8 5.9 105.2 65.0 4.9 4.7
9.0 4.2 9.7 42.1 29.9 2.31 50.0 18.2 91.1 3.3 3.1 5.6 2.0 4.7 50.4 2.51 41.8 5.9 105.2 65.0 4.9 4.7
90
4.5 1.5 3.5 36.4 27.5 2.93 46.4 12.4 110.6 5.4 5.1 3.3 1.0 2.4 50.4 2.51 41.8 5.9 105.2 65.0 4.9 4.7
6.8 2.7 6.2 38.4 28.4 2.70 47.6 14.2 104.1 4.7 4.5 3.3 1.0 2.4 50.4 2.51 41.8 5.9 105.2 65.0 4.9 4.7
9.0 4.1 9.5 39.4 28.8 2.59 48.2 15.2 100.7 4.3 4.1 3.3 1.0 2.4 50.4 2.51 41.8 5.9 105.2 65.0 4.9 4.7
100
4.5 1.5 3.5 33.5 26.1 3.32 44.9 10.1 119.9 6.6 6.3 2.4 0.7 1.7 50.4 2.51 41.8 5.9 105.2 65.0 4.9 4.7
6.8 2.7 6.1 35.5 27.0 3.05 45.9 11.6 113.6 5.8 5.5 2.4 0.7 1.7 50.4 2.51 41.8 5.9 105.2 65.0 4.9 4.7
9.0 4.1 9.4 36.5 27.5 2.92 46.4 12.5 110.3 5.4 5.1 2.4 0.7 1.7 50.4 2.51 41.8 5.9 105.2 65.0 4.9 4.7
110
4.5 1.4 3.2 30.9 24.8 3.81 43.9 8.1 129.5 8.1 7.7 1.9 0.4 1.0 50.4 2.51 41.8 5.9 105.2 65.0 4.9 4.7
6.8 2.6 6.0 32.6 25.6 3.48 44.5 9.4 123.2 7.1 6.7 1.9 0.4 1.0 50.4 2.51 41.8 5.9 105.2 65.0 4.9 4.7
9.0 4.0 9.2 33.5 26.1 3.32 44.9 10.1 120.0 6.7 6.4 1.9 0.4 1.0 50.4 2.51 41.8 5.9 105.2 65.0 4.9 4.7
120
4.5 1.1 2.6
Operation Not Recommended
1.5 0.1 0.1 50.4 2.51 41.8 5.9 105.2 65.0 4.9 4.7
6.8 2.4 5.5 1.5 0.1 0.1 50.4 2.51 41.8 5.9 105.2 65.0 4.9 4.7
9.0 3.9 8.9 30.8 24.7 3.82 43.9 8.1 129.7 8.1 7.7 1.5 0.1 0.1 50.4 2.51 41.8 5.9 105.2 65.0 4.9 4.7
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% antifreeze solution.
See performance correction tables for operating conditions other than those listed above.
See Performance Data Selection Notes for operation within the shaded areas.