System information
48
Geothermal Applications
Carrier: Turn to the Experts.
Table 9: GT-PG (50YE) Series PSC Blower Performance Data
(Without Whole House Dehumidifi cation)
Model
Fan
Speed
Rated
Airfl ow
Min
CFM
Airfl ow (cfm) at External Static Pressure (in. wg)
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
018
HI
600 450
704 711 693 690 675 640 598 515
MED 602 599 581 585 573 547 492
LO 531 527 517 506 495 462
024
HI
950 655
1111 1105 1066 1006 934 854 765 662 635
MED 890 879 854 818 770 708 686 623
LO 759 745 730 704 662 627
030
HI
1000 685
1374 1351 1296 1228 1159 1090 1016 919 775
MED 1146 1151 1128 1091 1047 997 934 844 705
LO 1011 1015 999 945 911 863 785
036
HI
1200 825
1375 1387 1377 1350 1307 1251 1182 1099 1003 890
MED 992 1013 1013 1002 986 967 941 900 832 719
LO 887 900 897 886 872 853 826 785
042
HI
1400 960
1808 1759 1723 1680 1617 1524 1399 1247 1075
MED 1537 1518 1494 1459 1408 1338 1247 1134 1001
LO 1323 1309 1284 1246 1192 1122 1036 936 824
048
HI
1600 1100
1805 1791 1760 1720 1674 1620 1552 1457 1318 1116
MED 1296 1297 1299 1299 1293 1276 1240 1176 1072 915
LO
060
HI
1950 1500
2311 2300 2279 2257 2209 2140 2088 1990 1901 1856 1752
MED 2058 2039 2016 1983 1949 1920 1874 1807 1750 1670 1582
LO 1868 1858 1858 1838 1806 1792 1749 1699 1636 1570
Black areas denote ESP where operation is not recommended.
Units factory shipped on medium speed. Other speeds require fi eld selection.
All airfl ow is rated and shown above at the lower voltage if unit is dual voltage rated, e.g. 208V for 208-230V units.
Whole House Dehumidification