User manual
ATC32U02 Communicating, Programmable Thermostat - User Manual
Rev.: 24 Feb., 2014
10
Geothermal Heat Pump Systems
• Backlight On Time (default 30 seconds): After
a button press, the backlight stays on for the
selected amount of time - options: 30 to 120
seconds, ON (in 30 second increments)
• Date Display (default MM/DD/YY): adjusts the
date format
5.6.2 OFFSETS
Not recommended for user access. Contact your
dealer for changes.
5.6.2.1 TEMPERATURE OFFSET
If you fi nd that the temperature displayed on the
thermostat does not accurately represent the room
temperature where the thermostat is located, this
offset function compensates for the difference.
The thermostat will apply an offset between what
temperature the thermostat is measuring versus the
temperature that is displayed.
TEMPERATURE OFFSET
The Temperature Offset function allows for
calibration of the temperature sensor.
Adjust the Temperature Offset settings using the
up/down arrow buttons. Press the center button to
save changes.
• Indoor Temperature (default 0°F): options:
-5°F to +5°F (in 1°F increments)
• Remote Temperature (default 0°F): options:
-5°F to +5°F (in 1°F increments)
• Outdoor Temperature (default 0°F): options:
-5°F to +5°F (in 1°F increments)
5.6.2.2 HUMIDITY OFFSET
If you fi nd that the Humidity level displayed on
the thermostat does not accurately represent the
Humidity level of the room in which the thermostat is
located, use the Humidity Offset function to calibrate
the humidity sensor.
Adjust the Humidity Offset setting using the up/
down arrow buttons. Press the center button to
save changes.
• Indoor Humidity (default 0%): options:
-10% to +10% (in 1% increments)
5.6.3 AUTO CHANGEOVER TIME
Not recommended for user access. Contact your
dealer for changes.
5.6.4 PROGRAM SETTINGS
Set additional system parameters related to program
scheduling and system operation.
5.6.4.1 PROGRAMMING OPTION
Adjust the Programming options using the up/down
arrow buttons. Press the center button to save
changes.
• Programmable (default) – enables 7-day
programming
• Non-Programmable – disables 7-day programming
• Night Setback – enables night setback
programming
NOTE: When the thermostat is confi gured for non-
programmable mode, the Display Date and Time
setting defaults to NO.
PROGRAM SETTINGS
SMART RECOVERY
PREVIOUS
SELECT OPTION
EVENTS PER DAY
PROGRAMMING OPTION
DEMAND REDUCTION
5.6.4.2 SMART RECOVERY
Smart recovery is a feature designed to save
energy by gradually adjusting temperatures. When
it is time for a program schedule temperature
change, smart recovery begins working in
advance, turning the system on and off as needed
to slowly adjust the indoor temperature so that
it reaches the program temperature setpoints at
the time you set. Rather than waiting to start the
equipment until the program time has occurred.
Adjust the Smart Recovery setting using the up/
down arrow buttons. Press the center button to
save changes.
• Events Per Day (default On): options: ON,
OFF
NOTE 1: The thermostat must be confi gured for
programmable mode by installer to access the
Smart Recovery setting.
NOTE 2: Auxiliary heat will not be used during
Smart Recovery.
5.6.4.3 EVENTS PER DAY
NOTE: The thermostat must be confi gured for
programmable mode by installer to access the
Events per Day setting.
Events Per Day sets the number of program
schedule events for each day. An event is a period
of time scheduled with a certain heat setpoint, cool
setpoint, and fan mode.