THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D TRANQUILITY VERTICAL STACK (TRM) SERIES WITH EARTHPURE® REFRIGERANT The Tranquility Vertical Stack (TRM) series offers an innovative, labor-saving solution for spaces where individual, quiet control of the heating and cooling system is important. TRM units’ pre-piped risers and pre-wired cabinets are especially ideal for multi-story buildings.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Selection Procedure Reference Calculations Heating HE LWT = EWT GPM x 500 LAT = EAT + HC CFM x1.08 Cooling HR LWT = EWT + GPM x 500 LAT (DB) = EAT (DB) - LC = TC - SC SC CFM x1.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Selection Procedure Step 1 Determine the actual heating and cooling loads at the desired dry bulb and wet bulb conditions. Step 2 Obtain the following design parameters: Entering water temperature, water flow rate in GPM, air flow in CFM, water flow pressure drop and design wet and dry bulb temperatures. Air flow CFM should be between 300 and 450 CFM per ton.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D TRM Series Nomenclature Hose Kit 1 2 3 4 5 6 7 8 AH H 0 5 0 2 B Group Revision Level AHH = Accessory Hose Kit Hi-Rise B = Current Revision Hose Size Length 050 = 1/2” Nominal 075 = 3/4” Nominal 100 = 1” Nominal 2 = Length in Feet 3 = Length in Feet Rev.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Performance Data ARI/ASHRAE/ISO 13256-1 ASHRAE/ARI/ISO 13256-1.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Performance Data Selection Notes For operation in the shaded area when water is used in lieu of an anti-freeze solution, the LWT (Leaving Water Temperature) must be calculated. Flow must be maintained to a level such that the LWT is maintained above 42°F [5.6°C] when the JW3 jumper is not clipped (see example below).
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Performance Data TRM09 405 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TRM09 (Cv = 4.9, MOPD = 125 psi) EWT °F 20 WPD Adder GPM PSI FT 1.10 0.25 0.58 1.70 0.64 1.48 2.25 1.27 2.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Performance Data TRM12 445 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TRM12 (Cv = 4.9, MOPD = 125 psi) GPM 20 GPM PSI FT 1.5 0.46 1.06 2.3 1.17 2.70 3.0 2.16 4.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Performance Data TRM15 595 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TRM15 (Cv = 4.9, MOPD = 125 psi) GPM 20 GPM PSI FT 1.9 0.74 1.71 2.8 1.74 4.02 3.8 2.16 4.99 WPD* EWT °F WPD Adder 30 40 50 60 70 80 85 90 100 110 120 Performance capacities shown in thousands of Btuh Cooling - EAT 80/67°F Sens/Tot Ratio EER HC 9.3 0.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Performance Data TRM18 685 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TRM18 (Cv = 10.3, MOPD = 125 psi) GPM 20 GPM PSI FT 2.3 0.24 0.55 3.4 0.58 1.34 4.5 1.10 2.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Performance Data TRM24 850 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TRM24 (Cv = 10.3, MOPD = 125 psi) GPM 20 GPM PSI FT 3.0 0.42 0.97 4.5 1.02 2.36 6.0 1.96 4.53 WPD* EWT °F WPD Adder 30 40 50 60 70 80 85 90 100 110 120 Performance capacities shown in thousands of Btuh Cooling - EAT 80/67°F TC SC Sens/Tot Ratio PSI FT 6.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Performance Data TRM30 1140 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TRM30 (Cv = 10.3, MOPD = 125 psi) GPM 20 GPM PSI FT 3.8 0.67 1.55 5.6 1.58 3.65 7.5 3.06 7.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Performance Data TRM36 1260 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TRM36 (Cv = 10.3, MOPD = 125 psi) GPM 20 GPM PSI FT 4.5 0.93 2.15 6.8 2.32 5.36 9.0 4.40 10.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Performance Data Correction Tables Air Flow Correction Table Airflow Cooling Heating % of Rated Total Capacity Sensible Capacity Power Heat of Rejection Heating Capacity Power Heat of Extraction 70% 0.921 0.800 0.969 0.943 0.942 1.077 0.934 75% 0.934 0.833 0.974 0.952 0.952 1.062 0.947 80% 0.946 0.866 0.979 0.961 0.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Antifreeze Correction Table Antifreeze Type Water Propylene Glycol Methanol Ethanol Ethylene Glycol Antifreeze % Cooling Heating EWT 90°F EWT 30°F WPD Corr. Fct. EWT 30°F Total Cap Sens Cap Power Htg Cap Power 0 1.000 1.000 1.000 1.000 1.000 1.000 5 0.995 0.995 1.003 0.989 0.997 1.070 15 0.986 0.986 1.009 0.968 0.990 1.210 25 0.978 0.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Blower Performance Data Airflow in CFM with wet coil and clean air flilter. Model TRM09 TRM12 Fan Speed HI LOW HI LOW Rated Airflow 405 Min CFM 284 445 312 595 416 HI TRM15 MED LOW HI TRM18 MED 685 480 LOW HI TRM24 MED 850 596 LOW HI TRM30 TRM36 MED 1140 798 Airflow (cfm) at External Static Pressure (in. wg) 0.00 0.01 0.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Physical Data Model 09 12 Compressor (1 Each) Factory Charge R410A (oz) [kg] 15 18 24 Rotary 33.5 [0.95] 35 [0.99] 30 36 Scroll 43 [1.22] 48.5 [1.38] 71 [2.01] 75 [2.13] 75 [2.13] PSC Fan Motor & Blower (2 Speeds) Fan Motor (hp) [W] 1/30 [25] 1/15 [50] 1/6 [124] 1/6 [124] 1/5 [149] 1/2 [373] 1/2 [373] 6.75 x 7.25 [174 x 184] 6.75 x 7.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Electrical Data Model TRM 22 Voltage Code Min/Max Voltage Voltage Compressor RLA LRA Fan Motor FLA Units with Secondary Loop Pump Standard Units Total Unit FLA Min Circuit Amps Max Fuse/ HACR Total Unit FLA Min Circuit Amps Max Fuse/ HACR TRM09 G 208-230/60/1 197/254 4.5 23.0 0.31 4.8 5.9 15 5.2 6.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Typical Wiring Diagram Single Phase TRM Units With CXM Controller w w w. c l i m a t e m a s t e r.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D AHH Series Stainless Steel Braided Hose Kit Specifications: • Designed for water source heat pump applications. • Kevlar® reinforced EPDM core with ANSI 302/304 stainless steel outer braid. • Fire rated materials per ASTM E 84-00 (NFPA 255, ANSI/UL 723 & UBC 8-1).
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Hinged "G" Style Return Air Panel 0.625" (16) A Mounting bracket 59" (1499) Filt er Inner panel is hinged for filter access. 1.81" (46) D Mounting bracket slots Side view Bottom of return air panel is 4-1/2" (114.3) from floor surface. Unit Size A 09 - 12 18-1/2” [470] 15 - 18 21-1/2” [546] 24 - 36 25-1/2” [648] 1.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Hinged "G" Style Return Air Panel With Keyed Locks w w w. c l i m a t e m a s t e r.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Hinged "H" Style Return Air Panel Holes to secure frame to studs (typical) NOTICE: Seal between the frame and cabinet with weather seal material to avoid air being pulled in from the wall cavity. DO NOT attach frame to cabinet.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Hinged "H" Style Return Air Panel NOM. 2” X 4” (51 x 102) STUD AND 5/8" (16) DRYWALL Note: H style return air panel is wider than TRM cabinet.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D TRM Unit Dimensions Single Unit, Furred In Cabinet (88 in.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D TRM Unit Dimensions Master Unit, Furred In Cabinet (88 in.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D TRM Unit Dimensions Slave Unit, Furred In Cabinet (88 in.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Air Flow vs. Grille Selection * Grilles are shipped loose for field installation after drywall has been applied to cabinets that are furred in. ** Grilles are brushed aluminum or painted (polar ice). Single Deflection- Adjustable vertical blades for controlling horizontal path of discharge air.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Riser Definitions Riser Tailpiece (length of riser that extends down from cabinet bottom) Dimension F on submittal drawing- Riser tailpiece sized for 2" (51) insertion into 3" (76) expanded section at top of cabinet. Actual job fit may be 1" (25) to 3" (76) insertion (built-in +1" (25) floor to floor tolerance).
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Riser Arrangements Top Floor Units 1. All Risers Capped At Cabinet Run-Outs • System piping is bottom supply & return Standard for bottom supply & return unless otherwise specified. 2.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Riser Arrangements Bottom Floor Units 1. All Riser Through Slab At Bottom • Bottom supply & return • Top supply & return feeding other equipment below Standard for bottom supply & return unless otherwise specified. 2.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Riser Extension Sizing Joint Overlap “B” 2" (51) Riser Tail Piece: Length of riser extending down from the cabinet. Riser tail piece must extend a minimum of 5" (127) below slab. Room Riser Height (RRH): Cabinet height + 3" (76). Standard Cabinet is 88" (2235) + 3" (76) = 91" (2311).
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Riser Length Sizing Unit "A" To determine the riser tail piece length of a unit (unit "A"). Top Floor Riser Tail Piece ( of unit A)= FF - RRH + 2" (51). RRH: Room riser height is cabinet height + 3" (76). Standard cabinet height is 88" (2235). Tail Piece FF RRH Unit "B" RRH= 88" (2235) + 3" (76) = 91" (2311).
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Cabinet Height & Slab Slot Size To determine the slab slot size required for the risers and to determine if clear height is OK for unit installation, use the cabinet height and slab slot charts on the next page. To use the charts you will need the clear height in the room the unit is in, size of unit, number of risers, riser dimensions and type of installation.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Shipping Units Are Shipped FOB Factory ClimateMaster Hi-Rise Cabinets are normally shipped to the jobsite on dedicated open flatbeds trailers, palletized for maximum shipping density, grouped together by building, size and floor where possible, wrapped and covered with tarp for protection (Figure 1).
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Riser GPM Sizing Riser GPM requirements and individual Unit GPM requirements are necessary to select the proper Riser Piping diameters. Refer to this page to determine GPM requirement, then refer to Riser Diameter Sizing Table to determine Riser Piping diameters. Example is for bottom supply - bottom return system feed loop.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Riser Diameter Sizing Refer to Riser GPM Sizing for the prefix to this example. Each TRM Vertical Stack unit has three riser pipes. The following example will be for one riser pipe (from the top floor to the bottom floor), and will be representative of the remaining two riser pipes.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Riser Slot Arrangements 27.50” (80” [203 cm] cabinet) [69.5 cm] 11.50” [29.2 cm] (88” [224 cm] cabinet) 35.50 [90.2 cm] 52.50” [133.4cm] 3.50” (all sizes) [8.9 cm] Always figure riser extension from the bottom of the cabinet, total extension length is effective length plus 2" [5.1 cm] Standard riser arrangement is 3" [7.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Tranquility Modular - TRM Series Engineering Specifications Rev.: 04/02/07 General: Furnish and install ClimateMaster Water Source Heat Pumps, as indicated on the plans with capacities and characteristics as listed in the schedule and the specifications that follow. Vertical Stack Water Source Heat Pumps: Units shall be low range, 20° to 120°F (-6.7° to 48.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Chassis: The chassis, which incorporates the air coil, water coil, drain pan, and compressor, shall be easily installed for quick jobsite installation and future servicing purposes. The slide in chassis shall have an insulated panel separating the fan compartment from the compressor compartment. Compressors are not in the air stream.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Cabinet Drain Pan: The drain pan shall be constructed of galvanized steel and have a powder coat paint application to further inhibit corrosion. This corrosion protection system shall meet the stringent 1000 hour salt spray test per ASTM B117.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D a. b. c. d. e. f. g. h. i. j. k. l. m. n. o. Removable thermostat connector. Night setback control. Random start on return from night setback. Minimized reversing valve operation (Unit control logic shall only switch the reversing valve when cooling is demanded for the first time.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D a. b. c. d. e. f. g. h. i. j. k. l. m. n. o. p. q. r.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D c. d. e. f. g. h. i. TRM 54 shall provide permanent memory of set-point(s) without batteries. A fault LED shall be provided to display specific fault condition. Thermostat shall come standard with remote temperature sensor, but may be operated with internal sensor if desired via installation of a jumper.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D buttons (up/down/right/left/select) with menu-driven selections for ease of use and programming. DDC Sensors: ClimateMaster wall mounted DDC sensor to monitor room temperature and interfaces with optional interface system described above. Several types as described below: a. Sensor only with no display (LON and MPC). b. Sensor with override (LON only). c.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v. : 0 5 / 2 3 / 0 7 D Notes: w w w. c l i m a t e m a s t e r.
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S Tr a n q u i l i t y Ve r t i c a l S t a c k ( T R M ) S e r i e s R e v.