Tranquility® Modular (TRM) Vertical Stack Series Table of Contents TRM Model Nomenclature 3 TRM Model Nomenclature - Chassis 4 Accessory Nomenclature 5 General Information 6 Riser & Cabinet Installation 8 Cabinet Installation 11 Piping Installation 14 Water-Loop Heat Pump Applications 15 Ground-Loop Heat Pump Applications 16 Ground-Water Heat Pump Applications 17 Water Quality Standards 19 Electrical Wiring - Line Voltage 20 Electrical Wiring - Low Voltage 21 Blower Performance Dat
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 TRM Model Nomenclature - Chassis Chassis 1 2 3 4 5 TRM 6 7 8 9 10 11 12 09 G S S S C S A Series Revision Level TRM = Tranquility® High Rise Chassis A = 24, 30, 36 B = 09, 12, 15, 18 Unit Size Standard 09, 12, 15, 18, 24, 30, 36 S = Standard Voltage Heat Exchanger Options G = 208-230/60/1 E = 265/60/1 Standard Extended Range Options* A S.S.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 General Information Safety Warnings, cautions, and notices appear throughout this manual. Read these items carefully before attempting any installation, service, or troubleshooting of the equipment. CAUTION: Indicates a potentially hazardous situation or an unsafe practice, which if not avoided could result in minor or moderate injury or product or property damage.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Inspection - Upon receipt of the equipment, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the packaging of each unit, and inspect each unit for damage. Ensure that the carrier makes proper notation of any shortages or damage on all copies of the freight bill and completes a common carrier inspection report.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Riser & Cabinet Installation Figure 1: Vertical Stack Unit Components WARNING! 1 Supply, Return, and Condensate Risers 2 Cabinet 3 Optional Frame CAUTION! 4 Chassis 5 Return Air Panel CAUTION! To ensure correct riser positioning and to compensate for variations in floor-to-floor dimensions, do not allow the unit to unit riser joint to bottom out.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 2. Move cabinet into position. CAUTION: Keep risers off the floor while moving cabinet. Look into risers and remove any debris. From the bottom of the riser, measure up 2” and mark. See 6B. 3. Raise the cabinet upright, align it and fit 3 risers into the risers below. The top of each riser is equipped with a 3" swagged section. Insertion must be 1” minimum to 2” maximum. Modify risers or use extensions if needed. 4.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Wallboard Installation - NOTICE! If you have the surface mounted thermostat option, make sure before you install the wallboard that the 2x4 tile ring is in the correct orientation. Turn if needed. Check your thermostat. Install studs and wallboard using conventional construction methods. Secure drywall to studs with low profile, pan-head sheet metal screws.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Cabinet Installation Figure 2: Cabinet Conduit For Electrical 3” Swage Sight and Riser runouts must be Sound Baffle centered in slot. They may have moved durring shipping. Control Box Loosen clamps and readjust if needed. Then re-tighten clamps.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 NOTICE - Drywall openings shown below are for specific cabinets. Cut openings for your cabinet.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Field Supplied Grille with Insect Screen Outside Wall Insulation Drywall Field Supplied Insulated Ductwork Field Supply Flex Duct Collar or Fabricate Extension. Seal to Cabinet and Wall. Cut Hole in Stud and Seal. See IOM with Kit for Location and Size. Supply Air Grille Opening G or H Panel Frame Motorized Air Damper Assembled to Frame. Connect Molex Wire Harness to Chassis Control Box.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Piping Installation Installation of Supply and Return Piping Follow these piping guidelines. 1. Install a drain valve at the base of each supply and return riser to facilitate system flushing. 2. Factory standard cabinets have shut-off valves and hoses have swivel-joint fittings to permit chassis removal for servicing. 3. Place strainers at the inlet of each system circulating pump. 4.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Water-Loop Heat Pump Applications Commercial Water Loop Applications - Commercial systems typically include a number of units connected to a common piping system. Any unit plumbing maintenance work can introduce air into the piping system; therefore air elimination equipment is a major portion of the mechanical room plumbing.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Ground-Loop Heat Pump Applications Flushing the Earth Loop - Upon completion of system installation and testing, flush the system to remove all foreign objects and purge to remove all air. Antifreeze - In areas where minimum entering loop temperatures drop below 40°F [5°C] or where piping will be routed through areas subject to freezing, antifreeze is required.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Ground-Water Heat Pump Applications Open Loop - Ground Water Systems - Shut off valves should be included for ease of servicing. Boiler drains or other valves should be “tee’d” into the lines to allow acid flushing of the heat exchanger. Shut off valves should be positioned to allow flow through the coax via the boiler drains without allowing flow into the piping system.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Flow Regulation - Flow regulation can be accomplished by two methods. One method of flow regulation involves simply adjusting the ball valve or water control valve on the discharge line. Measure the pressure drop through the unit heat exchanger, and determine flow rate from. Since the pressure is constantly varying, two pressure gauges may be needed. Adjust the valve until the desired flow of 1.5 to 2 gpm per ton [2.0 to 2.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Water Quality Standards Table 4: Water Quality Standards Water Quality Parameter HX Material Closed Recirculating Open Loop and Recirculating Well Scaling Potential - Primary Measurement Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below pH/Calcium Hardness Method All - pH < 7.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Electrical Wiring - Line Voltage WARNING! WARNING! To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation. CAUTION! CAUTION! Use only copper conductors for field installed electrical wiring. Unit terminals are not designed to accept other types of conductors.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Electrical Wiring - Low Voltage Thermostat Connections - The thermostat should be wired directly to the CXM or DXM board. See “Electrical – Thermostat” for specific terminal connections. Review the appropriate AOM (Application, Operation and Maintenance) manual for units with DDC controls.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Blower Performance Data Table 5: TRM with ECM-X Motor Model TRM15 TRM18 TRM24 TRM30 TRM36 Motor TAP HI MED HI MED MED LOW* LOW HI MED HI MED* MED LOW LOW HI MED HI MED MED LOW* LOW HI MED HI MED* MED LOW LOW HI MED HI* MED MED LOW LOW Rated Airflow Min CFM 600 650 900 0.0 0.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Thermostat Installation Installation of Optional Wall-Mounted Thermostat The unit can be furnished with a 24-volt surface mounted ACO or MCO control circuit or a remote 24-volt ACO or MCO thermostat. A typical field connection diagram is shown in Figure 6. Refer to instructions provided with remote thermostat for wiring instructions. WARNING! Zone integrity must be maintained to efficiently control units or groups of units.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Chassis Pre-Installation 1. Check chassis data plate. Verify chassis is correct for cabinet. 2. Check for any shipping or handling damage. Make repairs or adjustments. 3. Verify refrigerant tubing is free of kinks or dents and that it does not touch other unit components. 4. Inspect all electrical connections. Connections must be clean and tight at the terminals. 5. Replace any panels or covers removed for steps 2-4. 6.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Start-Up Preparation System Cleaning and Flushing - Cleaning and flushing the unit is the single most important step to ensure proper start-up and continued efficient operation of the system. Follow the instructions below to properly clean and flush the system: Do not flush through chassis koax.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Hose Kit & Chassis Installation Hose Kit Installation - After cabinets are installed, remove the upper and lower panels. SAVE THESE FOR RE-INSTALLATION AFTER THE CHASSIS IS INSTALLED! The cabinet has one or two shipping braces across the front (Figure 15) remove and discard both braces.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Figure 18 WARNING! WARNING! Do Not Remove Valve without first draining the risers below cabinet level. Step 2: Attach Flex Hoses. Let the universal ends of the hoses hang inside the cabinet for now. (Figure 22). Note: Be sure the valve handles are in a position that enables them to be opened and closed. Check the swivel ends of the hoses (Figure 21). Gaskets must be in the hose for proper seal.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Step 3: Attach to the Chassis. Slide the chassis part way into the cabinet. Match the WATER IN hose to the WATER IN tube on the chassis and the WATER OUT hose to the WATER OUT tube. Tighten the swivel connection keeping the copper tube parallel to the sides of the chassis, then tighten the hose to the copper making sure the hose hangs straight without twisting or turning (Figure 23).
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 7. Before installing the return air/access panel, perform the following checks: a. Ensure that fan wheel rotates freely and does not rub against housing. If rough handling during shipping has caused fan wheel to shift, adjust as necessary. b. Verify that water piping connections to the chassis are complete and that unit service valves which were closed during flushing have been opened. c.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 TRM Series Wiring Diagram Matrix Only CXM and DXM diagrams for ACO/MCO Controls are presented in this IOM. Other diagrams can be located online at climatemaster.com. Click ‘Commercial’ (go to ‘Quick Links’ in the upper right) using the part numbers presented below.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Typical Wiring Diagram Single Phase TRM Units with CXM Controller c l i m a t e m a s t e r.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 CXM Controls CXM Control - For detailed control information, see CXM or DXM Application, Operation and Maintenance (AOM) manual (part # 97B0003N12 or part #97B0003N13). Field Selectable Inputs - Test mode: Test mode allows the service technician to check the operation of the control in a timely manner.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 DXM Controls DXM Control - For detailed control information, see CXM AOM (part #97B0003N12), DXM AOM (part #97B0003N13), Lon controller AOM (part #97B0013N01) or MPC AOM (part # 97B0031N01). Water coil low temperature limit setting: Jumper 3 (JW3-FP1 Low Temp) provides field selection of temperature limit setting for FP1 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature). Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 1.3 - Thermostat type (heat pump or heat/cool): DIP 1.3 provides selection of thermostat type. Heat pump or heat/cool thermostats can be selected. When in heat/ cool mode, Y1 is the input call for cooling stage 1; Y2 is the input call for cooling stage 2; W1 is the input call for heating stage 1; and O/W2 is the input call for heating stage 2.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Safety Features - CXM/DXM Controls Safety Features – CXM/DXM Control The safety features below are provided to protect the compressor, heat exchangers, wiring and other components from damage caused by operation outside of design conditions. Anti-short cycle protection: The control features a 5 minute anti-short cycle protection for the compressor. Note: The 5 minute anti-short cycle also occurs at power up.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 UPS warning code = 8 Swapped FP1/FP2 thermistors: During test mode, the control monitors to see if the FP1 and FP2 thermistors are in the appropriate places. If the control is in test mode, the control will lockout with code 9 after 30 seconds if: a. The compressor is on in the cooling mode and the FP1 sensor is colder than the FP2 sensor, or: b.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Table 8: Building Commissioning Limits BUILDING COMMISSIONING ALL TRM MODELS AMBIENT MIN - MAX DB Cooling °F [°C] Heating °F [°C] 45-110 [7-43] 40-85 [4.5-29] RETURN AIR MIN DB/WB 60/45 [16/7] 40 [4.5] RETURN AIR MAX DB/WB 100-83 [38-28] 80 [27] STANDARD UNIT ENTERING WATER MIN* - MAX 40-120 [4.5-49] 60-90 [16-43] EXTENDED RANGE UNIT** ENTERING WATER MIN* - MAX 30-120 [-1-49] 20-90 [-6.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Unit and System Checkout WARNING! WARNING! Polyolester Oil, commonly known as POE oil, is a synthetic oil used in many refrigeration systems including those with HFC-410A refrigerant. POE oil, if it ever comes in contact with PVC or CPVS piping, may cause failure of the PVC/CPVC.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Unit Start-Up Procedures Unit Start-up Procedure 1. Turn the thermostat fan position to “ON”. Blower should start. 2. Balance air flow at registers. 3. Adjust all valves to their full open positions. Turn on the line power to all heat pumps. 4. Room temperature should be within the minimummaximum ranges of Table 8. During start-up checks, loop water temperature entering the heat pump should be between 60°F [16°C] and 95°F [35°C].
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Unit Operating Conditions Note: Table 10 includes the following notes: • Airflow is at nominal (rated) conditions; • Entering air is based upon 70°F [21°C] DB in heating and 80/67°F [27/19°C] in cooling; • Subcooling is based upon head pressure at compressor service port; • Cooling air and water values can vary greatly with changes in humidity level.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Table 10: TRM Series Typical Operating Pressures and Temperatures (60 Hz I-P Units) TRM18 Full Load Cooling TRM18 Full Load Heating Suction Pressure PSIG Discharge Pressure PSIG Superheat Subcooling Water Temp Drop °F Air Temp Rise °F DB 1.5 2.25 3 75-85 78-88 81-91 272-292 274-294 276-296 13-18 13-18 13-18 4-9 4-9 4-9 5.9-7.9 4.3-6.3 2.7-4.7 16-22 16-22 17-23 50 1.5 2.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Start-Up Log Sheet Installer: Complete unit and system checkout and follow unit start-up procedures in the IOM. Use this form to record unit information, temperatures and pressures during start-up. Keep this form for future reference.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Preventive Maintenance Water Coil Maintenance (Direct ground water applications only) If the system is installed in an area with a known high mineral content (125 P.P.M. or greater) in the water, it is best to establish a periodic maintenance schedule with the owner so the coil can be checked regularly. Consult the well water applications section of this manual for a more detailed water coil material selection.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Functional Troubleshooting Fault Main power problems HP Fault Code 2 Htg Clg Possible Cause Solution Air temperature out of range in heating Overcharged with refrigerant Bad HP Switch Insufficient charge Check line voltage circuit breaker and disconnect. Check for line voltage between L1 and L2 on the contactor. Check for 24VAC between R and C on CXM/DXM' Check primary/secondary voltage on transformer.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Performance Troubleshooting Performance Troubleshooting Htg Clg Possible Cause X X Dirty filter Solution Replace or clean. Check for dirty air filter and clean or replace. X Reduced or no air flow in heating Check fan motor operation and airflow restrictions. Too high of external static. Check static vs. blower table. Check for dirty air filter and clean or replace.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v.
c l i m a t e m a s t e r. c o m Rev.: 11/09 Please refer to the CM Installation, Operation and Maintenance Manual for operating and maintenance instructions. LC083 *LC083* NOTE: Some states or Canadian provinces do not allow limitations on how long an implied warranty lasts, or the limitation or exclusions of consequential or incidental damages, so the foregoing exclusions and limitations may not apply to you.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v.
THE SMART SOLUTION FOR ENERGY EFFICIENCY Vertical Stack R e v. : 1 1 / 0 9 / 1 2 Notes: c l i m a t e m a s t e r.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS Vertical Stack R e v.