T H E SM ART S OLUTION FOR E N E RGY E FFICIEN CY E N G I N E E R I N G D E S I G N GUI D E : T R A NQ UI L I T Y M O D UL AR (T R M ) SE RI E S 0 .
The Smart Choice for Energy Efficiency TABLE OF CONTENTS Commercial HVAC ..................................................................................................................................................................2 System Comparisons ..............................................................................................................................................................3 Water-Source & Geothermal Heat Pumps...........................................................
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s COMMERCIAL HVAC ENERGY EFFICIENCY The ever-changing environment of commercial construction offers exciting breakthroughs in technology and materials, but it is not without some heartburn. Today, owners, architects, and contractors face many challenges in the design and construction of their projects.
The Smart Choice for Energy Efficiency ROOFTOP Rooftop systems are similar to VAV systems in that they use a central ductwork system to distribute conditioned air into the building space. However, instead of one central unit, the system is comprised of multiple units which can be tasked for different conditioning requirements. Rooftop systems usually require additional structural reenforcement as well as cranes or other lifting equipment to place the units.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s WATER-SOURCE HEAT PUMPS to maintain a constant temperature of 60 to 70°F in the water loop during high heating demand months. Within this temperature range, the units can operate in either heating or cooling mode. As the most energy efficient HVAC systems on the market, Water-Source Heat Pumps are uniquely simple in design.
The Smart Choice for Energy Efficiency GEOTHERMAL SYSTEMS These “Boilerless/Towerless” Heat Pump systems use the natural thermal properties of the Earth to dissipate or capture heat for the water loop. Geothermal Heat Pumps operate in an identical fashion to Water-Source Heat Pump units. However, without the need for a boiler or cooling tower, they save substantial energy costs and space. The water loop system is underground and the units are inside the building.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s A WATER-SOURCE EXAMPLE A mixture of units in heating mode and units in cooling mode create a constant temperature in the water loop. In Balanced Mode, there is no need for heat injection or rejection via the boiler or cooling tower. The heat is simply moved from one zone to another.
The Smart Choice for Energy Efficiency A GEOTHERMAL EXAMPLE Using the same building model, the cooling tower and boiler are replaced with a geothermal vertical loop field. Identical in overall zone operation, the building benefits by having less overall equipment and reduced operation costs. Building aesthetics are also improved by eliminating outdoor equipment and additional space is gained by eliminating the boiler and additional support equipment.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s THE CLIMATEMASTER ADVANTAGE pilot runs are completed, unit literature is finalized and the product is released to the marketplace. Every unit we produce follows this strict and sequenced path insuring no stone is left unturned, and no detail is missed.
The Smart Choice for Energy Efficiency COMPONENT PARTS allowed us to maintain a high degree of competence in our industry. Our test cells and test equipment are calibrated and certified periodically, per recognized industry standards, to insure the data is accurate and repeatable. In addition to testing new concept units, the lab continually audits production units throughout the year to insure quality performance and reliability. To produce a quality unit, you have to start with quality components.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s ENGINEERING DESIGN SPECIFICATIONS CXM Advanced units need advanced specifications. ClimateMaster’s new Engineering Design specifications provide the most detailed information for your next project.
The Smart Choice for Energy Efficiency E-COATED AIR COILS performance, configuration, and cost options as the ClimateMaster family of products offers. From our smallest horizontal unit in the GCH006, to our largest vertical in the GLV300, to our Rooftop series with available 100% make-up air (when mated with the Rx ERV), to the console, water-to-water, and two-stage Tranquility 27™, we have a unit to fit your application.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s TRANQUILITY VERTICAL STACK (TRM) SERIES WITH EARTHPURE® REFRIGERANT UNIT FEATURES • Sizes 09 (3/4 ton, 2.6 kW) through 36 (3 ton, 10.6 kW) • Environmentally-friendly EarthPure® (HFC-410A) zero ozone depletion refrigerant • High efficiency rotary and scroll compressors • Exceeds ASHRAE 90.
The Smart Choice for Energy Efficiency Torsion-flex blower motors Stainless steel braided flexible hoses allow quick connection from the piping (risers) to the chassis and allow easy removal of the chassis Removable chassis allows staged installation and ease of maintenance/service once installation is complete Advanced digital controls with Remote Service Sentinel Enhanced controls shown with optional DDC Controllers (MPC) Exclusive dual-level compressor isolation lowers vibration and reduces noise fo
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s About ARI/ISO/ASHRAE 13256-1 The performance standard ARI/ASHRAE/ISO 13256-1 became effective January 1, 2000 and replaces ARI Standards 320, 325, and 330. This new standard has three major categories: Water Loop (comparable to ARI 320), Ground Water (ARI 325), and Ground Loop (ARI 330).
The Smart Choice for Energy Efficiency ARI/ISO/ASHRAE 13256-1 Data ASHRAE/ARI/ISO 13256-1. English (IP) Units Water Loop Heat Pump Model Cooling 86°F Capacity Btuh EER Btuh/W Ground Water Heat Pump Heating 68°F Capacity Btuh COP Cooling 59°F Capacity Btuh EER Btuh/W Ground Loop Heat Pump Heating 50°F Capacity Btuh COP Cooling 77°F Capacity Btuh EER Btuh/W Heating 32°F Capacity Btuh COP TRM09 8,800 13.0 12,500 4.6 10,100 19.5 9,800 3.8 9,300 14.7 7,200 3.1 TRM12 11,600 13.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Model Nomenclature 1 2 3 4 6 5 8 7 9 10 11 12 13 14 15 09 P G O N P A 1A A O O O A Unit Size Revision Level 09, 12, 15, 18, 24, 30, 36 A = CURRENT R410A UNITS Cabinet Style P = STANDARD Q = MASTER R = SLAVE S = STANDARD T = MASTER U = SLAVE Standard O = STANDARD .625 Flange “H” PANEL 1 Right Left 1.
The Smart Choice for Energy Efficiency Reference Calculations Heating Cooling HE LWT = EWT GPM x 500 LAT = EAT + HC CFM x1.08 HR LWT = EWT + GPM x 500 LAT (DB) = EAT (DB) - LC = TC - SC SC CFM x1.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Correction Tables Airflow Cooling Heating % of Rated Total Capacity Sensible Capacity Power Heat of Rejection Heating Capacity Power Heat of Extraction 70% 0.921 0.800 0.969 0.943 0.942 1.077 0.934 75% 0.934 0.833 0.974 0.952 0.952 1.062 0.947 80% 0.946 0.866 0.979 0.961 0.961 1.048 0.958 85% 0.958 0.899 0.985 0.
The Smart Choice for Energy Efficiency Unit Model Number Designation TRM = Vertical Stack Hi-Rise Heat Pump flow and air temperature would have on the corrected capacities. If the desired capacity cannot be achieved, select the next larger or smaller unit and repeat the procedure. Remember, when in doubt, undersize slightly for best performance. Capacity Table Index TRM-09 - TRM-36 - See Page 20-27. Glossary of Terms See Page 17.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Performance Data Selection Notes For operation in the shaded area when water is used in lieu of an anti-freeze solution, the LWT (Leaving Water Temperature) must be calculated. Flow must be maintained to a level such that the LWT is maintained above 42°F [5.6°C] when the JW3 jumper is not clipped (see example below).
The Smart Choice for Energy Efficiency Performance Data TRM-09 405 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TRM09 (Cv = 4.9, MOPD = 125 psi) GPM 20 GPM 1.10 1.70 2.25 PSI FT 0.25 0.58 0.64 1.27 WPD* EWT °F WPD Adder 30 1.48 2.93 40 50 60 70 80 85 90 100 110 120 Performance capacities shown in thousands of Btuh Cooling - EAT 80/67°F Sens/Tot Ratio EER HC 5.6 0.65 3.4 82.9 2.53 12.6 25.8 6.5 0.67 4.2 84.8 2.83 0.41 12.6 27.6 6.8 0.68 4.5 85.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Performance Data TRM-12 445 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TRM12 (Cv = 4.9, MOPD = 125 psi) EWT °F GPM 20 WPD Adder GPM 1.5 PSI FT 0.46 1.06 2.3 1.17 2.70 3.0 2.16 4.
The Smart Choice for Energy Efficiency Performance Data TRM-15 595 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TRM15 (Cv = 4.9, MOPD = 125 psi) 1.9 0.74 1.71 2.8 1.74 4.02 3.8 2.16 4.99 Cooling - EAT 80/67°F GPM PSI FT 20 3.8 2.1 4.8 1.9 0.3 0.8 19.0 12.1 0.64 0.64 21.2 2.8 0.6 1.4 19.5 12.1 0.62 0.60 21.5 3.8 1.8 4.2 19.7 12.0 0.61 0.58 21.6 1.9 0.3 0.7 18.2 11.9 0.65 0.72 20.6 2.8 0.5 1.2 18.8 12.1 0.64 0.66 3.8 1.6 3.8 19.1 12.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Performance Data TRM-18 685 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TRM18 (Cv = 10.3, MOPD = 125 psi) EWT °F GPM 20 WPD Adder GPM 2.3 PSI FT 0.24 0.55 3.4 0.58 1.34 4.5 1.10 2.
The Smart Choice for Energy Efficiency Performance Data TRM-24 850 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TRM24 (Cv = 10.3, MOPD = 125 psi) EWT °F GPM 20 WPD Adder GPM 3.0 PSI FT 0.42 0.97 4.5 1.02 2.36 6.0 1.96 4.53 30 40 50 60 70 80 85 90 100 110 120 Performance capacities shown in thousands of Btuh WPD* Cooling - EAT 80/67°F Sens/Tot Ratio EER HC 14.1 1.58 8.8 85.3 2.61 26.7 15.9 1.59 10.6 87.3 2.93 11.2 88.1 3.04 11.6 88.5 3.11 13.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Performance Data TRM-30 1140 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TRM30 (Cv = 10.3, MOPD = 125 psi) EWT °F GPM 20 WPD Adder GPM PSI FT 3.8 0.67 1.55 5.6 1.58 3.65 7.5 3.06 7.
The Smart Choice for Energy Efficiency Performance Data TRM-36 1260 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TRM36 (Cv = 10.3, MOPD = 125 psi) 4.5 0.93 2.15 6.8 2.32 5.36 9.0 4.40 10.20 Heating - EAT 70°F GPM PSI FT 20 9.0 9.8 22.7 4.5 2.5 5.8 39.9 25.1 0.63 1.56 45.1 25.5 23.0 2.20 15.6 86.9 3.06 6.8 5.2 11.9 39.7 24.2 0.61 1.48 44.6 26.8 23.9 2.21 16.5 87.6 3.16 9.0 8.6 19.9 39.4 23.5 0.60 1.44 44.1 27.3 24.4 2.22 17.0 87.9 3.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Physical Data Model 09 12 33.5 [0.95] 35 [0.99] Compressor (1 Each) Factory Charge R410A (oz) [kg] 15 18 24 30 43 [1.22] 48.5 [1.38] 71 [2.01] 75 [2.13] Rotary 36 Scroll 75 [2.13] PSC Fan Motor & Blower (2 Speeds) Fan Motor (hp) [W] 1/30 [25] 1/15 [50] 1/6 [124] 1/6 [124] 1/5 [149] 1/2 [373] 1/2 [373] 6.75 x 7.25 [174 x 184] 6.
The Smart Choice for Energy Efficiency Hinged Return Air Panel - “G” Style 0.625" (16) A Mounting bracket 59" (1499) Filt er Inner panel is hinged for filter access. 1.81" (46) Mounting bracket slots D Side view Bottom of return air panel is 4-1/2" (114.3) from floor surface. Unit Size A 09 - 12 17-1/2” [445] 15 - 18 20-1/2” [521] 24 - 36 24-1/2” [622] Notes: 1. Panel Fits over mounting bracket for self alignment, then 4 bolts driven through panels slots into nuts on chassis. 2.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Hinged Return Air Panel - “G” With Keyed Locks 0.625" (16) A Mounting bracket 59" (1499) Filt er Inner panel is hinged for filter access. 1.81" (46) Mounting bracket slots D Side view Bottom of return air panel is 4-1/2" (114.3) from floor surface.
The Smart Choice for Energy Efficiency Hinged Return Air Panel - “G” Style Installation 1-1/4" (32) TOP VIEW G STYLE RETURN AIR PANEL 2" MINIMUM (51) CABINET RISER CHASE (optional) DRYWALL 5/8" (16) 2 LAYERS OF 5/8" (16) DRYWALL ON FRONT SURFACE FOR CORRECT FIT OF “G” PANEL Drywall can be applied directly to unit surfaces, however, for best sound attenuation, a furred in stud wall installation is recommended. Note: All measurements are in inches, millimeters are in parenthesis.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Return Air Panel - “H” Style Holes to secure frame to studs (typical) NOTICE: Seal between the frame and cabinet with weather seal material to avoid air being pulled in from the wall cavity. DO NOT attach frame to cabinet.
The Smart Choice for Energy Efficiency Return Air Panel - “H” Style Installation NOM. 2” X 4” (51 x 102) STUD AND 5/8" (16) DRYWALL Note: H style return air panel is wider than TRM cabinet.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 .
The Smart Choice for Energy Efficiency Master Unit Furred In Cabinet Dimensions Optional Top Duct Connection 1/2" (13) Collar Optional Remote T/Stat Conduit B Supply Riser 5-3/4"(146) 5-3/4"(146) Power Conduit 3" (76) Return Riser B A A 33-1/2"* C Thin wall Conduit 3/4" (19) Supply Air Opening 1/2" (13) Collar Optional 24V Surface Mount T/Stat 2" (51) Floor to floor + 2” (51) (Max.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 .
The Smart Choice for Energy Efficiency Cabinet Configurations Single Supply - Side Double Supply - Side 1A 1B 1C 2A 2B 2D 1E 1F 1G 2G 2H 2K 1J 1K 1L 2N 2P 2R Triple Supply - Top & Sides Double Supply - Top & Side 2C 2E 2F 3B 3C 3D 2J 2L 2M 3F 3G 3H 2Q 2S 2T 3K 3L 3M Triple Supply - Sides 3A 3E Quadruple Supply - Top & Sides 4A 3J 1H 4C No Supply - For Field Modification Single Supply - Top &Side 1D 4B 1M OA NOTES: 1: The riser compartment is defined as bein
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Air Flow Vs. Grille Selection * Grilles are shipped loose for field installation after drywall has been applied to cabinets that are furred in. ** Grilles are brushed aluminum or painted (polar ice). Single Deflection- Adjustable vertical blades for controlling horizontal path of discharge air.
The Smart Choice for Energy Efficiency Riser Definitions Riser Tailpiece (length of riser that extends down from cabinet bottom) Dimension F on submittal drawing- Riser tailpiece sized for 2" (51) insertion into 3" (76) expanded section at top of cabinet. Actual job fit may be 1" (25) to 3" (76) insertion (built-in +1" (25) floor to floor tolerance). Riser tailpiece should extend beneath bottom of slab a minimum of 5" (127) to facilitate brazing.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Riser Arrangements - Top Floor Units 1. All Risers Capped At Cabinet Run-Outs • System piping is bottom supply & return Standard for bottom supply & return unless otherwise specified. 2.
The Smart Choice for Energy Efficiency Riser Arrangements - Bottom Floor Units 1. All Riser Through Slab At Bottom • Bottom supply & return • Top supply & return feeding other equipment below Standard for bottom supply & return unless otherwise specified. 2. Supply & Return Capped At Cabinet Run-Out, Drain Through Slab • Top supply & return • Supply & return mains above these units on "Between-Floors" main piping Standard for top supply & return unless otherwise specified. 3.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Riser Extension Sizing Joint Overlap “B” Riser Tail Piece: Length of riser extending down from the cabinet. Riser tail piece must extend a minimum of 5" (127) below slab. 2" (51) Room Riser Height (RRH): Cabinet height + 3" (76). Standard Cabinet is 88" (2235) + 3" (76) = 91" (2311).
The Smart Choice for Energy Efficiency Riser Length Sizing Unit "A" To determine the riser tail piece length of a unit (unit "A"). Top Floor Riser Tail Piece ( of unit A)= FF - RRH + 2" (51). RRH: Room riser height is cabinet height + 3" (76). Standard cabinet height is 88" (2235). Tail Piece FF RRH Unit "B" Top Floor RRH= 88" (2235) + 3" (76) = 91" (2311). FF: Floor to Floor height is the dimension from the top of the slab above to the top of the slab below.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Cabinet Heigth and Slab Slot Size To determine the slab slot size required for the risers and to determine if clear height is OK for unit installation, use the cabinet height and slab slot charts on the next page.
The Smart Choice for Energy Efficiency Slab Slot Chart - 3 Pipe Slab Slot Size Type of Installation Type 1 Type 2 Type 3 WxL WxL WxL 09 - 12 96 95 94 93 92 5 7/8" X 15" [149 X 381] 6 1/4" X 15" [159 X 381] 6 5/8" X 15" [168 X 381] 7" X 15" [179 X 381] 7 1/2" X 15" [191 X 381] 5 7/8" X 15" [149 X 381] 5 3/8" X 15" [137 X 381] 5 3/8" X 15" [137 X 381] Not Recommended Not Recommended 5" X 15" [127 X 381] 5" X 15" [127 X 381] 5" X 15" [127 X 381] 5" X 15" [127 X 381] Not Recommended 15 - 18 96 95 9
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Shipping Units Are Shipped FOB Factory ClimateMaster Hi-Rise Cabinets are normally shipped to the jobsite on dedicated open flatbeds trailers, palletized for maximum shipping density, grouped together by building, size and floor where possible, wrapped and covered with tarp for protection (Figure 1).
The Smart Choice for Energy Efficiency Riser GPM Sizing Riser GPM requirements and individual Unit GPM requirements are necessary to select the proper Riser Piping diameters. Refer to this page to determine GPM requirement, then refer to Riser Diameter Sizing Table to determine Riser Piping diameters. Example is for bottom supply - bottom return system feed loop. GPM's are dependent upon unit load and system loop water temperatures. Please refer to Performance Charts for individual Unit GPM requirements.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Riser Diameter Sizing Refer to Riser GPM Sizing for the prefix to this example. Each TRM Vertical Stack unit has three riser pipes. The following example will be for one riser pipe (from the top floor to the bottom floor), and will be representative of the remaining two riser pipes.
The Smart Choice for Energy Efficiency Riser Slot Arrangements 27.50” (80” [203 cm] cabinet) [69.5 cm] 11.50” [29.2 cm] 35.50 (88” [224 cm] cabinet) [90.2 cm] 52.50” [133.4cm] 3.50” (all sizes) [8.9 cm] Always figure riser extension from the bottom of the cabinet, total extension length is effective length plus 2" [5.1 cm] Standard riser arrangement is 3" [7.6 cm] above and 13" [33 cm] below to 24” [61 cm] below (overall riser=115” [292.1 cm] Max.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Blower Performance Data Airflow in CFM with wet coil and clean air flilter. Model TRM09 TRM12 Fan Speed HI LOW HI LOW Rated Airflow Min CFM 405 284 445 312 595 416 HI TRM15 TRM18 TRM24 MED 0.01 0.05 0.10 0.15 0.20 408 403 376 346 319 292 349 343 320 296 445 434 409 378 349 320 345 341 325 0.25 0.30 0.35 0.40 0.
The Smart Choice for Energy Efficiency Unit Electrical Data Model Voltage Code Voltage Min/Max Voltage Compressor RLA LRA Fan Motor FLA Units with Secondary Loop Pump Standard Units Total Unit FLA Min Circuit Amps Max Fuse/ HACR Total Unit FLA Min Circuit Amps Max Fuse/ HACR TRM09 G 208-230/60/1 197/254 4.5 23.0 0.31 4.8 5.9 15 5.2 6.3 15 TRM12 G 208-230/60/1 197/254 5.3 30.0 0.70 6.0 7.4 15 6.4 7.8 15 TRM15 G 208-230/60/1 197/254 5.8 30.0 1.00 6.8 8.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 .
The Smart Choice for Energy Efficiency Typical Wiring Diagram - DXM Controls - Single Phase 53
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s CXM AND DXM SERIES CONTROLLERS DXM Control Board The CXM and DXM Series Controllers are designed to enhance Water-Source Heat Pump unit performance with the ability to coordinate complete systems. CXM Series controllers offer complete stand-alone unit control. DXM Series controls add advanced unit operation and system control features.
The Smart Choice for Energy Efficiency OPEN-PROTOCOL DDC CAPABILITY The CXM and DXM Series can be upgraded with the addition of a separate LonMark or MPC (Multiple ProtoCol -- BACNET, N2, Modbus) DDC module, either as a factory option, or field installed at a later date. LonWorks is an open protocol DDC network, which can be integrated with most third-party building automation systems. In addition, the MPC controller offers the other popular building management system protocols (BACNET, N2, Modbus).
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 .
The Smart Choice for Energy Efficiency TRM Vertical Stack Series 60Hz Engineering Guide Specs. Rev.: 07/07/06 General: Furnish and install ClimateMaster Water Source Heat Pumps, as indicated on the plans with capacities and characteristics as listed in the schedule and the specifications that follow. Vertical Stack Water Source Heat Pumps: Units shall be low range, 20° to 120°F (-6.7° to 48.9°C) entering water temperature for low temperature application.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s shall be 2 speed, permanently lubricated, PSC type with thermal overload protection. The fan motor shall be isolated from the fan housing by a torsionally flexible motor mounting system with rubber type grommets to inhibit vibration induced high noise levels associated with “hard wire belly band” motor mounting.
The Smart Choice for Energy Efficiency Option: The unit will be supplied with internally factory mounted automatic water flow regulators. Option: The unit will be supplied with internally mounted secondary pump for primary/secondary applications. Cabinet Drain Pan: The drain pan shall be constructed of galvanized steel and have a powder coat paint application to further inhibit corrosion. This corrosion protection system shall meet the stringent 1000 hour salt spray test per ASTM B117.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Option: Enhanced solid state control system (DXM) This control system features two stage control of cooling and two stage control of heating modes for exacting temperature and dehumidification purposes.
The Smart Choice for Energy Efficiency j. k. l. m. n. o. p. q. r. Condensate sensor alarm Hi/low voltage alarm Fan “ON/AUTO” position of space thermostat as specified above Unoccupied / occupied command Cooling command Heating command Fan “ON / AUTO” command Fault reset command Itemized fault code revealing reason for specific shutdown fault (any one of 7) This option also provides the upgraded 75VA control transformer with load side short circuit and overload protection via a built in circuit breaker.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 . 7 5 t o 3 To n Ve r t i c a l H i - R i s e U n i t s Option: Extended 4-year compressor warranty covers compressor for a total of 5 years. Option: Extended 4-year refrigeration circuit warranty covers coils, reversing valve, expansion valve and compressor for a total of 5 years. Option: Extended 4-year control board warranty covers the CXM/DXM control board for a total of 5 years.
The Smart Choice for Energy Efficiency h. i. changeover with HEAT-OFF-COOL-AUTO system settings and fan ON-AUTO settings. Thermostat shall have an LCD display with temperature, set-point(s), mode, and status indication. The temperature indication shall be selectable for ºF or ºC. The thermostat shall provide permanent memory of set-point(s) without batteries. Thermostat shall provide convenient override feature to temporarily change set point.
ClimateMaster Water-Source Heat Pumps Tr a n q u i l i t y M o d u l a r ( T R M ) S e r i e s 0 .
7300 S.W. 44th Street Oklahoma City, OK 73179 Phone: 405-745-6000 Fax: 405-745-6058 www.climatemaster.com ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.