Vertical High Rise Stack (VHS) Series Submittal Data Models 816-10 - 36 60Hz - R22 English Language/I-P Units Geothermal Heat Pump Systems SUBMITTAL DATA - I-P UNITS Unit Designation: Job Name: Architect: Engineer: Contractor: PERFORMANCE DATA Cooling Capacity: Btuh EER: Heating Capacity: Btuh COP: Ambient Air Temp: °F Entering Water Temp (Clg): °F Entering Air Temp (Clg): °F Entering Water Temp (Htg): °F Entering Air Temp (Htg): °F Airflow: CFM Fan Speed or Motor/RPM/Turns: Operating Wei
Vertical High Rise Stack (VHS) Series Submittal Data Models 816-10 - 36 60Hz - R22 English Language/S-I Units Geothermal Heat Pump Systems SUBMITTAL DATA - S-I UNITS Unit Designation: Job Name: Architect: Engineer: Contractor: PERFORMANCE DATA Cooling Capacity: kW EER: Heating Capacity: kW COP: Ambient Air Temp: °C Entering Water Temp (Clg): °C Entering Air Temp (Clg): °C Entering Water Temp (Htg): °C Entering Air Temp (Htg): °C Airflow: l/s Fan Speed or Motor/RPM/Turns: Operating Weight:
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Table of Contents *Page Number Unit Features Selection Procedure VHS Series Nomenclature Performance Data - ARI/ASHRAE/ISO 13256-1 Performance Data Selection Notes Performance Data - 816-10 Performance Data - 816-15 Performance Data - 816-20 Performance Data - 816-28 Performance Data - 816-30 Performance Data - 816-36 Performance Data Correction Tables Blower Performance Data Physical Data Electrical Data Wiring Diagram Matrix Typi
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems THE VERTICAL STACK (VHS) SERIES UNIT FEATURES The VHS series offers an innovative, labor-saving solution for spaces where individual, quiet control of the heating and cooling system is important. VHS units’ pre-piped risers and pre-wired cabinets are especially ideal for multistory buildings.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Selection Procedure Reference Calculations Heating HE LWT = EWT GPM x 500 LAT = EAT + HC CFM x1.08 Cooling HR LWT = EWT + GPM x 500 LAT (DB) = EAT (DB) - LC = TC - SC SC CFM x1.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Selection Procedure Step 1 Determine the actual heating and cooling loads at the desired dry bulb and wet bulb conditions. Step 2 Obtain the following design parameters: Entering water temperature, water flow rate in GPM, air flow in CFM, water flow pressure drop and design wet and dry bulb temperatures. Air flow CFM should be between 300 and 450 CFM per ton.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems VHS Series Nomenclature Cabinet 1 2 3 4 10 S 6 5 G O N 7 8 9 10 11 12 13 14 15 A A 1A O O O O Q REVISION LEVEL Q = CURRENT R22 UNITS UNIT SIZE (TRM) SIZE / R410A 10 15 20 28 30 36 STANDARD (TRM) R410A CABINET STYLE A = STANDARD C = MASTER D = SLAVE B = STANDARD E = MASTER F = SLAVE O = STANDARD A, B, C etc.... = SPECIAL 1, 2, 3 etc.... RIGHT .
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems VHS Series Nomenclature Chassis 1 2 3 4 5 6 7 8 9 10 11 12 13 816 10 G S P S S C O Q Model Type Revision Level Q = Current Revision Size 20 - 36 S = Current Revision Size 10 & 15 816 Chassis Unit Size Standard 10, 15, 20, 28, 30, 36 O = Standard Voltage Heat Exchanger Options E = 265/60/1 G = 208-230/60/1 C = Copper Coax w/Coated Air Coil N = Cupro-Nickel Coax w/Coated Air Coil L = Copper Coax w/Non-Coated Air
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems VHS Series Nomenclature Hose Kit 1 2 3 4 5 6 7 8 AH H 0 5 0 2 B Group Revision Level B = Current Revision AHH = Accessory Hose Kit Hi-Rise Hose Size Length 050 = 1/2” Nominal 075 = 3/4” Nominal 100 = 1” Nominal 2 = Length in Feet 3 = Length in Feet Return Air Panel 1 2 3 4 5 6 7 8 9 10 11 AVHSG 1 S F S L S Accessory Return Air Panel Standard AVHSG = G-Panel AVHSH = H-Panel S = Standard Revision Level J =
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data ARI/ASHRAE/ISO 13256-1 ASHRAE/ARI/ISO 13256-1. English (IP) Units Water Loop Heat Pump Model Cooling 86°F Ground Water Heat Pump Heating 68°F Capacity Btuh EER Btuh/W Capacity Btuh COP 816-10 8,500 11.6 11,500 4.2 816-15 12,000 12.3 14,700 4.2 816-20 18,500 12.0 23,600 4.2 816-28 25,200 12.0 32,000 4.2 816-30 28,100 12.5 36,000 4.2 816-36 32,600 12.5 42,500 4.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data Selection Notes For operation in the shaded area when water is used in lieu of an anti-freeze solution, the LWT (Leaving Water Temperature) must be calculated. Flow must be maintained to a level such that the LWT is maintained above 42°F [5.6°C] when the JW3 jumper is not clipped (see example below). This is due to the potential of the refrigerant temperature being as low as 32°F [0°C] with 40°F [4.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data 816-10 320 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, 816-10 (Cv = 4.9, MOPD = 150 psi) GPM EWT °F WPD Adder PSI FT 1.2 0.06 0.14 1.7 0.17 0.40 2.2 0.38 0.87 2.7 0.60 1.38 40 50 60 70 80 85 90 100 110 Performance capacities shown in thousands of Btuh WPD* GPM Cooling - EAT 80/67°F Heating - EAT 70°F PSI FT TC SC Sens/ Tot Ratio kW HR EER 1.2 0.7 1.7 11.0 7.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data 816-15 410 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, 816-15 (Cv = 4.9, MOPD = 150 psi) GPM EWT °F WPD Adder PSI FT 40 Performance capacities shown in thousands of Btuh WPD* GPM Cooling - EAT 80/67°F Heating - EAT 70°F PSI FT TC SC Sens/ Tot Ratio kW HR EER 1.6 1.0 2.4 14.8 10.0 0.67 0.61 16.9 24.4 2.5 2.5 5.7 15.4 10.2 0.66 0.56 17.3 27.6 3.3 4.2 9.7 15.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data 816-20 680 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, 816-20 (Cv = 4.9, MOPD = 150 psi) GPM EWT °F WPD Adder PSI FT 40 Performance capacities shown in thousands of Btuh WPD* GPM Cooling - EAT 80/67°F Heating - EAT 70°F PSI FT TC SC Sens/ Tot Ratio kW HR EER 2.2 1.5 3.5 23.1 15.8 0.69 1.16 27.0 19.9 3.6 3.2 7.5 24.2 16.1 0.67 1.04 27.7 23.3 5.0 5.6 12.9 24.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data 816-28 940 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, 816-28 (Cv = 10.3, MOPD = 150 psi) GPM EWT °F WPD Adder Performance capacities shown in thousands of Btuh WPD* GPM Cooling - EAT 80/67°F Heating - EAT 70°F PSI FT TC SC Sens/ Tot Ratio kW HR EER 3.3 1.6 3.6 31.3 20.0 0.64 1.50 36.4 20.8 5.1 3.5 8.0 32.3 20.3 0.63 1.36 36.9 23.7 6.5 6.3 14.5 32.7 20.3 0.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data 816-30 1000 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, 816-30 (Cv = 10.3, MOPD = 150 psi) GPM EWT °F WPD Adder PSI FT 40 Performance capacities shown in thousands of Btuh WPD* GPM Cooling - EAT 80/67°F Heating - EAT 70°F PSI FT TC SC Sens/ Tot Ratio kW HR EER 3.6 1.7 4.0 34.3 20.7 0.60 1.81 40.5 18.9 5.6 3.8 8.7 35.1 21.0 0.60 1.69 40.8 20.8 7.5 6.6 15.2 35.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data 816-36 1200 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, 816-36 (Cv = 10.3, MOPD = 150 psi) GPM EWT °F WPD Adder PSI FT 4.2 0.53 1.22 6.2 1.30 3.01 8.4 2.68 6.19 10.6 4.73 10.92 40 50 60 70 80 85 90 100 110 Performance capacities shown in thousands of Btuh WPD* GPM Cooling - EAT 80/67°F Heating - EAT 70°F PSI FT TC SC Sens/ Tot Ratio kW HR EER 4.2 1.9 4.5 40.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Performance Data Correction Tables Air Flow Correction Table Airflow Cooling Heating % of Rated Total Capacity Sensible Capacity Power Heat of Rejection Heating Capacity Power Heat of Extraction 67% 0.966 0.927 0.966 0.962 0.966 1.114 0.943 74% 0.969 0.933 0.968 0.965 0.969 1.091 0.947 80% 0.972 0.939 0.970 0.968 0.972 1.068 0.951 87% 0.986 0.969 0.986 0.984 0.986 1.045 0.976 94% 0.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Blower Performance Data Airflow in CFM with wet coil and clean air flilter. Airflow (cfm) at External Static Pressure (in. wg) Model Fan Speed Rated Airflow Min CFM 0.00 0.05 0.10 0.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Physical Data Model 10 Compressor (1 Each) 15 20 30 36 23 [0.65] 29 [0.82] 44 [1.25] 55 [1.56] 50 [1.42] 1/30 [25] 1/6 [124] 1/4 [187] 1/4 [187] 1/4 [187] 1/2 [373] 1/2 [373] 1/2 [373] Rotary Factory Charge R22 (oz) [kg] 16 [0.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Electrical Data All 816 Units Model 816-10 816-10 High Static 816-15 816-15 High Static 816-20 816-20 High Static 816-28 816-28 High Static 816-30 816-30 High Static 816-36 816-36 High Static Standard 816 Unit 816 unit with Secondary Pump QTY RLA LRA Fan Motor FLA 197/254 1 4.5 20.0 0.31 4.8 5.9 15 0.43 5.2 6.4 15 239/292 1 3.3 18.6 0.30 3.6 4.4 15 N/A N/A N/A N/A 197/254 1 4.5 20.0 0.70 5.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems VHS Series Wiring Diagram Matrix Only CXM and DXM diagrams for ACO/MCO Controls are presented in this submittal. Other diagrams can be located online at climatemaster.com using the part numbers presented below.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Typical Wiring Diagram Single Phase VHS Units With CXM Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Typical Wiring Diagram Single Phase VHS Units With DXM Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Typical Wiring Diagram Single Phase VHS Units With DXM Controller with Night Setback, Emergency Shutdown, & Pump Restart Y1 Y2 SHUTDOWN OUTPUT TIME CLOCK CONTACT W O G R C AL1 PUMP RESTART INPUT (PUMP TIME OFF OVERIDE) RCS C S C COM2 COM1 FAN R DXM CONTROLLER FAN SPEED AL2 R NSB C ESD L H A HP LP FP1 FP2 RV CO NSB NO NC COM R ACC#2 COM NO NC COM ACC#1 SHUTDOWN R TEST ACC1.NO EH1 EH2 ACC1.C ACC2.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Typical Unit - Exploded View Single Unit: Furred In & Ducted 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 816/TRM cabinet (furred-in) Slide-in heating and cooling chassis Architectural acoustic R/A panel with hinged center door Factory installed supply, return and condensate risers Factory installed drain pan with P-trap assembly Factory installed supply and return feeders with ball valves Blower and motor assembly Top
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems AHH Series Stainless Steel Braided Hose Kit Specifications: • Designed for VHS water source heat pump applications. • Kevlar® reinforced EPDM core with ANSI 302/304 stainless steel outer braid. • Fire rated materials per ASTM E 84-00 (NFPA 255, ANSI/UL 723 & UBC 8-1).
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Hinged "G" Style Return Air Panel 0.625" (16) A Mounting bracket 59" (1499) Filt er Inner panel is hinged for filter access. 1.81" (46) Mounting bracket slots D Side view Bottom of return air panel is 4-1/2" (114.3) from floor surface. Unit Size A 10 - 15 18-1/2” [470] 20 21-1/2” [546] 28 - 36 25-1/2” [648] Notes: 1.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Hinged "G" Style Return Air Panel With Keyed Locks Standard G Panel With Keyed Locks ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems "G" Style Return Air Panel with Cabinet Flush Mounted 1¼ (32) It is recommended to fill the gap with sound absorbing material Drywall 5/8" (16) X C B A R.O. CABINET X 3 ½ (89) Minimum RISER CHASE (optional) TOP VIEW It is recommended to leave 2” (51) minimum clearance on both sides for removing panel TYPICAL CORNER INSTALLATION 1¼ (32) C Riser Diameters 1”(25.4) to 3”(76) Standard X G Panel Perimeter A R.O.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems "G" Style Return Air Panel with Cabinet Recessed Frame Kit Required X Seal (4) Sides Frame Outside Drywall NOTICE: Seal between the frame and cabinet with weather seal material to avoid air being pulled in from the wall cavity. DO NOT attach frame to cabinet.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Hinged "H" Style Return Air Panel Holes to secure frame to studs (typical) NOTICE: Seal between the frame and cabinet with weather seal material to avoid air being pulled in from the wall cavity. DO NOT attach frame to cabinet.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Hinged "H" Style Return Air Panel Note: H style return air panel is wider than TRM cabinet H STYLE RETURN AIR PANEL 3½ (89) RECOMMENDED 2” MINIMUM (51) CLEARANCE ON BOTH SIDES FOR REMOVING PANEL RISER CHASE (optional) DRYWALL 5/8" (16) TOP VIEW SEAL 4 SIDES FRAME OUTSIDE DRYWALL NOTICE: Seal between the frame and cabinet with weather seal material to avoid air being pulled in from the wall cavity.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Optional Top Duct Connection 1/2" (13) Collar Optional Remote T/Stat Conduit 2.00(51) Condensate Drain Riser (Insulated) Supply Riser 5.75(146) Service B Area 5.75(146) Power Conduit 3" (76) B A Thin wall Conduit 3/4" (19) Supply Air Opening 1/2" (13) Collar Optional 24V Surface Mount T/Stat Note 4 Upper Control Box & Electrical Power Connections Motor-Blower Assembly Upper Block off not shown 2" 4" (102) 33.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems VHS Unit Dimensions Master Unit, Furred In Cabinet (88 in. [2235mm] Height) Optional Top Duct Connection 1/2" (13) Collar Optional Remote T/Stat Conduit Supply Riser 5.75” (146) Service B Area 5.75” (146) Power Conduit 3" (76) 2" 33.50”* 4" (102) (851) 9.88" (251) Return Riser A A (51) Floor to floor + 2” (51) (Max. 115” (2921) 2.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems VHS Unit Dimensions Slave Unit, Furred In Cabinet (88 in. [2235mm] Height) Optional Top Duct Connection 1/2" (13) Collar Optional Remote T/Stat Conduit 2.00(51) Condensate Drain 5.75"(146 ) Service B Area 5.75"(146 ) Power Conduit A A Thin wall Conduit 3/4" (19) Supply Air Opening 1/2" (13) Collar Optional 24V Surface Mount T/Stat 2" (51) 33.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems VHS Master-Slave Cabinet Connected Master Cabinet Slave Cabinet S Chassis R S R R R S S R Chassis S Hoses Hoses Option 1 - Cross field supplied piping between cabinets. Mark shutoffs inside slave cabinet. Run hoses straight across. Master Cabinet Slave Cabinet S Chassis S S R R R S Chassis R Hoses Hoses Option 2 - Field supplied and brazed piping to be straight across. Mark shutoffs inside slave cabinet.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems VHS Cabinet Configurations Single Supply - Side Double Supply - Side 1A 1B 1C 2A 2B 2D 1E 1F 1G 2G 2H 2K 1J 1K 1L 2N 2P 2R Double Supply - Top & Side Triple Supply - Top & Sides 2C 2E 2F 3B 3C 3D 2J 2L 2M 3F 3G 3H 2Q 2S 2T 3K 3L 3M Quadruple Supply - Top & Sides Single Supply - Top 1D 1H 1M 4A OA 3J 3E S U P P L Y LEGEND = RETURN AIR (AIR ENTERING CABINET) = SUPPLY AIR (AIR LEAVING C
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Air Flow vs. Grille Selection * Grilles are shipped loose for field installation after drywall has been applied to cabinets that are furred in. ** Grilles are brushed aluminum or painted (polar ice). Single Deflection- Adjustable vertical blades for controlling horizontal path of discharge air. Double Deflection- Adjustable vertical and horizontal blades for controlling horizontal and vertical path of discharge air.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Riser Definitions Riser Tailpiece (length of riser that extends down from cabinet bottom) Dimension F on submittal drawing- Riser tailpiece sized for 2" (51) insertion into 3" (76) expanded section at top of cabinet. Actual job fit may be 1" (25) to 3" (76) insertion (built-in +1" (25) floor to floor tolerance). Riser tailpiece should extend beneath bottom of slab a minimum of 5" (127) to facilitate brazing.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Riser Definitions Swaged 3” Deep For A Riser From Above A Dia. A Dia. A Dia. A Dia. B Dia. Runout Into Cabinet Runout Into Cabinet Runout Into Cabinet B Dia. C Dia. Runout Into Cabinet Supply and Return Supply and Return Transition Up Straight Supply and Return Transition Down Drain Transition Up Notes 1. You must know water flow direction to determine if cabinet requires transition up or down. 2.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Riser Arrangements Top Floor Units 1. All Risers Capped At Cabinet Run-Outs • System piping is bottom supply & return Standard for bottom supply & return unless otherwise specifed. 2.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Riser Arrangements Bottom Floor Units 1. All Riser Through Slab At Bottom • Bottom supply & return • Top supply & return feeding other equipment below Standard for bottom supply & return unless otherwise specifed. 2.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Riser Extension Sizing Joint Overlap “B” Riser Tail Piece: Length of riser extending down from the cabinet. Riser tail piece must extend a minimum of 5" (127) below slab. 2" (51) Room Riser Height (RRH): Cabinet height + 3" (76). Standard Cabinet is 88" (2235) + 3" (76) = 91" (2311). Above Slab Riser Tailpiece 3"(76) Swage Riser Extension Floor To Floor Height (FF): Distance from top of unit slab to top of above slab.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Riser Length Sizing Unit "A" To determine the riser tail piece length of a unit (unit "A"). Top Floor Riser Tail Piece ( of unit A)= FF - RRH + 2" (51). RRH: Room riser height is cabinet height + 3" (76). Standard cabinet height is 88" (2235). Tail Piece FF Unit "B" RRH= 88" (2235) + 3" (76) = 91" (2311). RRH FF: Floor to Floor height is the dimension from the top of the slab above to the top of the slab below.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Cabinet Height & Slab Slot Size To determine the slab slot size required for the risers and to determine if clear height is OK for unit installation, use the cabinet height and slab slot charts on the next page. To use the charts you will need the clear height in the room the unit is in, size of unit, number of risers, riser dimensions and type of installation.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Slab Slot Chart - 3 Pipe 3 Pipe Standard 88" Cabinet Slab Slot Size Type of Installation Type 1 Type 2 Type 3 WxL WxL WxL 10 - 15 96 95 94 93 92 5 7/8" X 15" [149 X 381] 6 1/4" X 15" [159 X 381] 6 5/8" X 15" [168 X 381] 7" X 15" [179 X 381] 7 1/2" X 15" [191 X 381] 5 7/8" X 15" [149 X 381] 5 3/8" X 15" [137 X 381] 5 3/8" X 15" [137 X 381] Not Recommended Not Recommended 5" X 15" [127 X 381] 5" X 15" [127 X 381] 5" X 15" [
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Riser GPM Sizing Riser GPM requirements and individual Unit GPM requirements are necessary to select the proper Riser Piping diameters. Refer to this page to determine GPM requirement, then refer to Riser Diameter Sizing Table to determine Riser Piping diameters. Example is for bottom supply - bottom return system feed loop. GPM's are dependent upon unit load and system loop water temperatures.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Riser Diameter Sizing Refer to Riser GPM Sizing for the prefix to this example. Each TRM Vertical Stack unit has three riser pipes. The following example will be for one riser pipe (from the top floor to the bottom floor), and will be representative of the remaining two riser pipes. From Table 1 (below) determine the proper riser diameter needed to satisfy the required GPM's at each unit. Refer to Table 2 (below) for a summary.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Riser Slot Arrangements 27.50” for 80” (2032) cabinet [695] 11.50” [292] 35.50 for 88” (2235) cabinet [902] 5.25” (133) 2.50” (64) 52.50” [1334] 2.25” (57) 3.00” (76) Center line of cabinet 3.50” (all sizes) [89] Slots allow for riser stack expansion and contraction. Riser stub should be centered in slot. Dimensions are inches [mm]. ClimateMaster works continually to improve its products.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Shipping Units Are Shipped FOB Factory ClimateMaster Hi-Rise Cabinets are normally shipped to the jobsite on dedicated open flatbeds trailers, palletized for maximum shipping density, grouped together by building, size and floor where possible, wrapped and covered with tarp for protection (Figure 1). The size of each pallet depends upon the cabinet size and number of cabinets (Figure 2).
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Vertical High Rise - VHS Series Engineering Specifications Rev.: 05/29/09 Page 1 General: Furnish and install ClimateMaster Water Source Heat Pumps, as indicated on the plans with capacities and characteristics as listed in the schedule and the specifications that follow. Vertical Stack Water Source Heat Pumps: Units shall be low range, 40° to 110°F (4.4° to 43.3°C) entering water temperature for low temperature application.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Vertical High Rise - VHS Series Engineering Specifications Rev.: 05/29/09 Page 2 Option: High static motors. Chassis: The chassis, which incorporates the air coil, water coil, drain pan, and compressor, shall be easily installed for quick jobsite installation and future servicing purposes. The slide in chassis shall have an insulated panel separating the fan compartment from the compressor compartment.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Vertical High Rise - VHS Series Engineering Specifications Rev.: 05/29/09 Page 3 Option: The unit will be supplied with internally factory mounted automatic water flow regulators. Option: The unit will be supplied with internally mounted secondary pump for primary/secondary applications. Cabinet Drain Pan: The drain pan shall be constructed of galvanized steel and have a powder coat paint application to further inhibit corrosion.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Vertical High Rise - VHS Series Engineering Specifications Rev.: 05/29/09 Page 4 This control system coupled with a multi-stage thermostat will better dehumidify room air by automatically running the heat pump’s fan at lower speed on the first stage of cooling thereby implementing low sensible heat ratio cooling.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Vertical High Rise - VHS Series Engineering Specifications Rev.: 05/29/09 Page 5 q. r. Fault reset command Itemized fault code revealing reason for specific shutdown fault (any one of 7) This option also provides the upgraded 75VA control transformer with load side short circuit and overload protection via a built in circuit breaker.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Vertical High Rise - VHS Series Engineering Specifications Rev.: 05/29/09 Page 6 FIELD INSTALLED OPTIONS Hose Kits - AHH Series (required for field water connections): Water connections between chassis and the cabinet shall be accomplished via a hose kit consisting of Kevlar-reinforced EPDM core hose surrounded by a stainless-steel braid. Hose kit shall have brass fittings with stainless-steel ferrules.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Vertical High Rise - VHS Series Engineering Specifications Rev.: 05/29/09 Page 7 h. five buttons (up/down/right/left/select) with menu-driven selections for ease of use and programming.
VHS Series 60Hz - R22 Submittal Data Eng/I-P Geothermal Heat Pump Systems Revision History Date: Item: Action: 29 May, 2009 Stand-Alone and Big Book Submittals Consolidated 29 May, 2009 Engineering Specifications Verbiage Updated 27 Oct, 2008 Blower Performance Data Notes Updated 26 Aug, 2008 Physical Data Table Max Working Pressure Table Added 30 May, 2008 MWV Pressure Drop Data Updated 19 April, 2007 Table of Contents Added Table of Contents 19 April, 2007 Specifications Updated