Specifications

ClimateMaster works continually to improve its products. As a result, the design and speci cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for speci c information on the current design and speci cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
Page ______ of ______Rev.: 29 May, 2009BLC105 - 13
VHS Series 60Hz - R22 Submittal Data Eng/I-P
Geothermal Heat Pump Systems
Performance Data
816-15
EWT
°F
GPM
WPD* Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT TC SC
Sens/
Tot
Ratio
kW HR EER HC kW HE LAT COP
40
1.6 1.0 2.4 14.8 10.0 0.67 0.61 16.9 24.4
Operation Not Recommended
2.5 2.5 5.7 15.4 10.2 0.66 0.56 17.3 27.6
3.3 4.2 9.7 15.6 10.3 0.66 0.54 17.5 29.1
4.1 6.7 15.4 15.8 10.3 0.65 0.52 17.6 30.1 10.8 0.91 7.7 94.4 3.50
50
1.6 1.0 2.4 14.1 9.6 0.69 0.68 16.4 20.7 11.5 0.92 8.3 96.0 3.65
2.5 2.4 5.6 14.6 9.9 0.68 0.62 16.8 23.4 12.1 0.94 8.9 97.4 3.79
3.3 4.2 9.6 14.9 10.0 0.67 0.60 16.9 24.7 12.4 0.95 9.2 98.1 3.85
4.1 6.6 15.2 15.0 10.0 0.67 0.59 17.0 25.6 12.6 0.95 9.4 98.5 3.89
60
1.6 1.0 2.3 13.3 9.3 0.70 0.76 15.9 17.5 13.1 0.96 9.8 99.5 3.98
2.5 2.4 5.5 13.9 9.6 0.69 0.70 16.3 19.8 13.8 0.98 10.5 101.2 4.12
3.3 4.1 9.5 14.1 9.7 0.69 0.68 16.4 20.9 14.1 0.99 10.8 101.9 4.19
4.1 6.5 15.0 14.3 9.7 0.68 0.66 16.5 21.6 14.3 0.99 10.9 102.4 4.23
70
1.6 1.0 2.3 12.6 8.9 0.71 0.86 15.5 14.7 14.6 1.00 11.2 102.9 4.27
2.5 2.3 5.4 13.1 9.2 0.70 0.79 15.8 16.6 15.3 1.02 11.9 104.7 4.41
3.3 4.1 9.4 13.3 9.3 0.70 0.76 15.9 17.5 15.7 1.03 12.2 105.4 4.47
4.1 6.4 14.8 13.5 9.4 0.70 0.74 16.0 18.1 15.9 1.03 12.4 105.9 4.51
80
1.6 1.0 2.2 11.8 8.5 0.72 0.96 15.1 12.5 16.0 1.04 12.5 106.1 4.52
2.5 2.3 5.4 12.4 8.8 0.71 0.89 15.4 14.1 16.8 1.06 13.2 107.9 4.66
3.3 4.0 9.3 12.6 8.9 0.71 0.86 15.5 14.9 17.1 1.07 13.5 108.7 4.72
4.1 6.3 14.6 12.7 9.0 0.71 0.84 15.6 15.4 17.4 1.07 13.7 109.2 4.75
85
1.6 1.0 2.2 11.5 8.3 0.73 1.01 14.9 11.3 16.7 1.05 13.1 107.6 4.64
2.5 2.3 5.3 12.0 8.6 0.72 0.94 15.2 12.8 17.5 1.07 13.8 109.4 4.77
3.3 4.0 9.2 12.2 8.7 0.72 0.91 15.3 13.4 17.8 1.08 14.1 110.3 4.83
4.1 6.2 14.4 12.3 8.8 0.71 0.89 15.4 13.9 18.1 1.09 14.3 110.8 4.86
90
1.6 0.9 2.1 11.1 8.1 0.73 1.07 14.7 10.4 17.3 1.07 13.7 109.1 4.74
2.5 2.3 5.3 11.6 8.4 0.72 0.99 15.0 11.7 18.1 1.09 14.4 110.9 4.87
3.3 3.9 9.1 11.8 8.5 0.72 0.96 15.1 12.3 18.5 1.10 14.7 111.7 4.93
4.1 6.1 14.2 12.0 8.6 0.72 0.94 15.2 12.7 18.7 1.10 14.9 112.2 4.96
100
1.6 0.9 2.1 10.3 7.6 0.74 1.19 14.4 8.7
Operation Not Recommended
2.5 2.3 5.2 10.8 7.9 0.73 1.11 14.6 9.7
3.3 3.9 9.0 11.0 8.1 0.73 1.08 14.7 10.3
4.1 6.1 14.0 11.2 8.2 0.73 1.06 14.8 10.6
110
3.3 3.9 8.9 10.3 7.6 0.74 1.20 14.4 8.5
4.1 6.0 13.8 10.4 7.7 0.74 1.18 14.4 8.8
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
ARI/ISO certi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not re ect fan or pump power corrections for ARI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
* Pressure drop with valve = PSI + (GPM/3.5)
2
(Valve has a CV of 3.5 & MOPD of 30psi)
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
See Performance Data Selection Notes for operation in the shaded areas.
Performance capacities shown in thousands of Btuh410 CFM Nominal (Rated) Air ow
*WPD Adder for
Motorized Valve,
816-15
(Cv = 4.9,
MOPD = 150 psi)
GPM
WPD Adder
PSI FT
1.6 0.11 0.25
2.5 0.37 0.86
3.3 0.85 1.95
4.1 1.61 3.72