Service manual
23
climatemaster.com
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tranquility
®
Compact (TC) Series
Rev.: 02/06/15
Electrical Data – ECM
TC
Model
Voltage
Code
Rated
Voltage
Voltage
Min/Max
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
RLA LRA QTY
015
G 208/230/60/1 197/254 6.0 29.0 1 2.70 8.7 10.2 15
E 265/60/1 239/292 5.4 28.0 1 2.10 7.5 8.9 15
018
G 208/230/60/1 197/254 7.2 33.0 1 2.70 9.9 11.7 15
E 265/60/1 239/292 5.9 28.0 1 2.10 8.0 9.5 15
024
G 208/230/60/1 197/254 12.8 58.3 1 3.90 16.7 19.9 30
E 265/60/1 239/292 9.6 54.0 1 3.20 12.8 15.2 20
H 208/230/60/3 197/254 7.7 55.4 1 3.90 11.6 13.5 20
*F *460/60/3 414/506 3.6 28.0 1 3.20 6.8 7.7 15
030
G 208/230/60/1 197/254 14.1 73.0 1 3.90 18.0 21.5 35
E 265/60/1 239/292 11.2 60.0 1 3.20 14.4 17.2 25
H 208/230/60/3 197/254 8.9 58.0 1 3.90 12.8 15.0 20
*F *460/60/3 414/506 4.2 28.0 1 3.20 7.4 8.5 15
036
G 208/230/60/1 197/254 16.7 79.0 1 5.20 21.9 26.1 40
E 265/60/1 239/292 13.5 72.0 1 4.70 18.2 21.6 35
H 208/230/60/3 197/254 10.4 73.0 1 5.20 15.6 18.2 25
*F *460/60/3 414/506 5.8 38.0 1 4.70 10.5 12.0 15
042
G 208/230/60/1 197/254 17.9 112.0 1 5.20 23.1 27.6 45
H 208/230/60/3 197/254 13.5 88.0 1 5.20 18.7 22.1 35
*F *460/60/3 414/506 6.0 44.0 1 4.70 10.7 12.2 15
048
G 208/230/60/1 197/254 21.8 117.0 1 6.90 28.7 34.2 50
H 208/230/60/3 197/254 13.7 83.1 1 6.90 20.6 24.0 35
*F *460/60/3 414/506 6.2 41.0 1 6.00 12.2 13.8 20
060
G 208/230/60/1 197/254 26.3 134.0 1 6.90 33.2 39.8 60
H 208/230/60/3 197/254 15.6 110.0 1 6.90 22.5 26.4 40
*F *460/60/3 414/506 7.8 52.0 1 6.00 13.8 15.8 20
* 460 volt units require a neutral connection. All “F” voltage units with ECM require a four wire power supply with neutral.
Motors are 265 volt and are wired between one hot leg and neutral.
All fuses Class RK-5