Service manual

29
climatemaster.com
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tranquility
®
Compact (TC) Series
Rev.: 02/06/15
Blower Performance Data (ECM Motor)
Operation not recommended
Model
Max
ESP
(in. wg)
Fan
Motor
(hp)
Tap
Setting
Cooling Mode Dehumid Mode Heating Mode
Stg 1 Stg 2 Fan Stg 1 Stg 2 Fan Stg 1 Stg 2 Fan
TC
015
0.50
1/3
4 470 550 275 376 440 275 470 550 275
0.50 3 425 500 250 340 400 250 425 500 250
0.50 2 380 450 225 304 360 225 380 450 225
0.50 1 340 400 200 272 320 200 340 400 200
TC
018
0.50
1/3
4 550 650 325 440 520 325 550 650 325
0.50 3 510 600 300 408 480 300 510 600 300
0.50 2 465 550 275 372 440 275 465 550 275
0.50 1 425 500 250 340 400 250 425 500 250
TC
024
0.50
1/2
4 745 875 438 596 700 438 745 875 438
0.50 3 680 800 400 544 640 400 680 800 400
0.50 2 615 725 363 492 580 363 615 725 363
0.50 1 550 650 325 440 520 325 550 650 325
TC
030
0.50
1/2
4 890 1050 525 712 840 525 890 1050 525
0.50 3 810 950 475 648 760 475 810 950 475
0.50 2 745 875 438 596 700 438 745 875 438
0.50 1 680 800 400 544 640 400 680 800 400
T C
036
0.50
3/4
4 1085 1275 638 868 1020 638 1085 1275 638
0.50 3 1020 1200 600 816 960 600 1020 1200 600
0.50 2 955 1125 563 764 900 563 955 1125 563
0.50 1 850 1000 500 680 800 500 850 1000 500
TC
042
0.50
3/4
4 1255 1475 738 1004 1180 738 1255 1475 738
0.50 3 1120 1320 660 896 1056 660 1120 1320 660
0.50 2 1020 1200 600 816 960 600 1020 1200 600
0.50 1 935 1100 550 748 880 550 935 1100 550
TC
048
0.75
1
4 1445 1700 850 1156 1360 850 1445 1700 850
0.75 3 1275 1500 750 1020 1200 750 1275 1500 750
0.75 2 1190 1400 700 952 1120 700 1190 1400 700
0.75 1 1105 1300 650 884 1040 650 1105 1300 650
TC
060
0.75
1
4 1740 2050 1025 1392 1640 1025 1740 2050 1025
0.75 3 1615 1900 950 1292 1520 950 1615 1900 950
0.75 2 1490 1750 875 1192 1400 875 1490 1750 875
0.75 1 1360 1600 800 1088 1280 800 1360 1600 800
See ECM control section for details on setting taps.
Air ow is controlled within 5% up to the Max ESP shown with wet coil.
Do not select Dehumidi cation mode if HP CFM is on setting 1.
Air ow in CFM with wet coil and clean air lter