Service manual

41
climatemaster.com
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tranquility
®
Compact (TC) Series
Rev.: 02/06/15
Piping System Cleaning and Flushing - Cleaning and
ushing the WLHP piping system is the single most
important step to ensure proper start-up and continued
effi cient operation of the system.
Follow the instructions below to properly clean and
ush the system:
1. Ensure that electrical power to the unit is
disconnected.
2. Install the system with the supply hose connected
directly to the return riser valve. Use a single length
of fl exible hose.
3. Open all air vents. Fill the system with water. DO
NOT allow system to overfl ow. Bleed all air from the
system. Pressurize and check the system for leaks
and repair as appropriate.
4. Verify that all strainers are in place (ClimateMaster
recommends a strainer with a #20 stainless steel
wire mesh). Start the pumps, and systematically
check each vent to ensure that all air is bled from
the system.
5. Verify that make-up water is available. Adjust make-
up water as required to replace the air which was
bled from the system. Check and adjust the water/air
level in the expansion tank.
6. Set the boiler to raise the loop temperature to
approximately 85°F [29°C]. Open a drain at the
lowest point in the system. Adjust the make-up water
replacement rate to equal the rate of bleed.
7. Refi ll the system and add trisodium phosphate
in a proportion of approximately one pound per
150 gallons (.8 kg per 1000 l ) of water (or other
equivalent approved cleaning agent). Reset the
boiler to raise the loop temperature to 100°F [38°C].
Circulate the solution for a minimum of 8 to 24 hours.
At the end of this period, shut off the circulating
pump and drain the solution. Repeat system
cleaning if desired.
8. When the cleaning process is complete, remove the
short-circuited hoses. Reconnect the hoses to the
proper supply, and return the connections to each of
the units. Refi ll the system and bleed off all air.
9. Test the system pH with litmus paper. The system
water should be in the range of pH 6.0 - 8.5 (see
table 3). Add chemicals, as appropriate to maintain
neutral pH levels.
10. When the system is successfully cleaned, fl ushed,
refi lled and bled, check the main system panels,
safety cutouts and alarms. Set the controls to
properly maintain loop temperatures.
Note: The manufacturer strongly recommends all piping
connections, both internal and external to the unit, be
pressure tested by an appropriate method prior to any
nishing of the interior space or before access to all
connections is limited. Test pressure may not exceed
the maximum allowable pressure for the unit and all
components within the water system. The manufacturer
will not be responsible or liable for damages from water
leaks due to inadequate or lack of a pressurized leak
test, or damages caused by exceeding the maximum
pressure rating during installation.
Piping System Cleaning and Flushing
CAUTION!
CAUTION! DO NOT use “Stop Leak” or similar chemical
agent in this system. Addition of chemicals of this type to
the loop water will foul the heat exchanger and inhibit unit
operation.