ADVANCED SETTINGS - HUMIDITY SETTINGS
39INSTRUCTION MANUAL
>:: HUM FAN: ON - fan runs when there is an independent demand to humidify.
OFF: fan only runs when there is a demand to humidify while heating or cooling.
:: DH FAN: ON - fan runs when there is an independent demand to dehumidify.
OFF: fan only runs when there is a demand to dehumidify while cooling.
:: DH REVERSE: ON - DH relay is normally closed when relative humidity is above
DH set point. OFF: DH relay is normally open when relative humidity is above DH
set point.
:: DH CONTROL COMPRESSOR: ON - Thermostat will turn off the air conditioning if
either the dehumidify set point or the temperature set point is reached, whichever
comes first, both DH relay and compressor will turn off. OFF: DH relay is inde-
pendent of compressor activity (DH becomes a spare relay and can be used for a
variable speed fan or separate dehumidifier or air exchanger)
ADVANCED SETTINGS - HEAT PUMP
38 Climatouch
™
CT0-7TC-32H
:: HP ON when Furnace On: Heat Pump and Furnace can operate together when
2nd stage furnace is required. HP “OFF” when Furnace On: turns off the Heat
Pump when the furnace is On (required on some gas or oil furnaces).