The following figure, instead, gives an example of the integral contribution of the adjustment method.
Set point
Set point
+
P. band
Tin
Pass
[KW]
Max
Min
0 %
Start
compressor
(P09.43)
100 %
Integral
+ limit
(P39.07)
- limit
(P39.07)
Integral
time
Integral
time
Integral
time
Integral
time
Integral
time
Example
1-compressor unit
Band: 6°C
Integral limit: 20%
Integral time: 90 s
Set point
Set point
+
P. band
Tout
Figure 1.14: Adjustment for a single-compressor unit: integral contribution