System information

C0240111-06-07-GB
25
ALARM DESCRIPTION details RESET
522
Exp 2 Probe 2 error slave “analogue, as above” A
523
Exp 2 Probe 3 error slave “analogue, as above” A
524
Exp 2 Probe 4 error slave “analogue, as above” A
525
Exp 2 Probe 5 error slave “analogue, as above” A
526
Exp 2 Probe 6 error slave “analogue, as above” A
527
Exp 2 Probe 7 error slave “analogue, as above” A
528
Exp 2 Probe 8 error slave “analogue, as above” A
531
Exp 3 Probe 1 error slave “analogue, as above” A
532
Exp 3 Probe 2 error slave “analogue, as above” A
533
Exp 3 Probe 3 error slave “analogue, as above” A
534
Exp 3 Probe 4 error slave “analogue, as above” A
551
Exp 5 Probe 1 error slave “analogue, as above” A
552
Exp 5 Probe 2 error slave “analogue, as above” A
553
Exp 5 Probe 3 error slave “analogue, as above” A
554
Exp 5 Probe 4 error slave “analogue, as above” A
611
Antifreeze pre
-alarm evaporator 1
Low water temperature at evaporator outlet pre-
alarm. Also specifies which evaporator (if more
than one) is involved in the alarm condition
S
612
Antifreeze pre
-alarm evaporator 2 “as above, for circuit 2” S
613
Antifreeze pre
-alarm evaporator 3 “as above, for circuit 3” S
614
Antifreeze pre
-alarm evaporator 4 “as above, for circuit 4” S
631
Low pressure in circuit 1 pre-alarm
Low pressure acquired from circuit 1 transducer
pre
-alarm
S
632
Low pressure in circuit 2 pre-alarm “as above, for circuit 2” S
633
Low pressure in circuit 3 pre-alarm “as above, for circuit 3” S
634
Low pressure in circuit 4 pre-alarm “as above, for circuit 4” S
641
High pressure in circuit 1 pre-alarm
High pressure acquired from circuit 1 transducer
pre
-alarm
S
642
High pressure in circuit 2 pre-alarm “as above, for circuit 2” S
643
High pressure in circuit 3 pre-alarm “as above, for circuit 3” S
644
High pressure in circuit 4 pre-alarm “as above, for circuit 4” S
Key to “RESET” column:
M = Manual reset alarm (if the condition that generated the alarm is eliminated, the alarm must be
reset from the keypad); sets “cumulative alarms”
A = Automatic reset alarm (if the condition that generated the alarm is eliminated, the alarm is reset
automatically); sets “cumulative alarms”
A/M = Automatic reset alarm for the first “n” cut-ins, after which manual; sets “cumulative alarms”
S = Signal on display (does not set “cumulative alarms”)
S-A = Automatic reset signal (that does not stop the machine) or alarm. The mode is selected from a
parameter
M - A/M = Manual reset alarm (in hermetic, alternative and screw compressors),
automatic for the first “n” cut-ins, after which manual (in centrifuge compressors)
B =Block that cannot be reset from the display; sets “cumulative alarms”. To eliminate the alarm,
switch the relative compressor off and then back on again.