System information

C0240111-06-07-GB
27
Mask Description Para n°
Refrigerant:
Type : R407c
Sets the type of refrigerant used. 01.13
Recovery:
Enabled: N
Enables recovery.
Recovery is enabled automatically in the polyvalent units.
01.14
Freecooling:
Enabled: N
Enables freecooling control. 01.15
Enable probes:
External temp. N
Optional temp. N
Probe enable mask for enabling the external air temperature probe or optional temperature
probe (only visible in water-air units)
01.17
01.24
Enable probes:
Cond. in. temp. N
Cond. out. temp. N
Probe enable mask for enabling the condenser inlet probe or the condenser outlet probe
(only visible in water-water chiller and heat pump units with just one condenser; two
condenser outlet probes are enabled in the units with two condensers)
01.16
01.25
Enable probes:
Pressure N
Low Pressure N
Maschera di abilizzazione sonde per l'abilitazione dei trasduttori di alta pressione e di bassa
pressione.
01.18
01.19
High pressure
transducers
Start Scale 00.0bar
End Scale 30.0bar
Mask for configuring the high pressure transducers. 01.20
01.21
High pressure
transducers
Start Scale 00.0bar
End Scale 30.0bar
Mask for configuring the low pressure transducers. 01.22
01.23
Global.
Access mask to user global parameters submenu.
Press "Up" or "Down" to scroll the other
masks and "Esc" to return to the submenu.
Enter another
manufacturer
password
0000000000
Sets a new password.
ATTENTION: THE PASSWORD ENTERED IN THIS FIELD IS THE ONLY ONE THAT
ALLOWS ACCESS TO THE MANUFACTURER MENU!!
Display
passwords
service 0000
user 0000
Displays the passwords governing access to the service and user menus
W 3000
Code CA 15.00 GB 
Man. C0240011-06-07
This mask contains the reference information of the software [Code] and of the reference
technical manual [Man.].
The closed padlock symbol shows that the board is provided with its propriety software; two
padlocks appear on units with 3 or 4 circuits
Functions
Access mask to functions submenu.
Press "Up" or "Down" to scroll the other masks and
"Esc" to return to the submenu.
Setpoint
Limitation
Winter N
Enables setpoint limitation in summer and winter modes. 05.02
Ext. air winter set
point limit. -05.0°C
Delta 05.0°C
Max var. set 05.0°C
(only with winter setpoint limitation) Enables setting of the external air temperature setpoint
below which setpoint limitation begins in the heat pump or recovery only modes and defining
the temperature delta at which the maximum setpoint (lowering) variation (negative) takes
place.
05.07
05.08
05.09
Max setpoint
limit
winter
45.0°C
(only with winter setpoint limitation) maximum winter setpoint limit 05.10
Coil
fractioning N
Enables coil fractioning. 05.11
Upper set 10.0 bar
Upper diff. 05.0 bar
Lower set 12.0 bar
Lower diff. 00.5 bar
(only with coil fractioning) Sets the upper setpoint and differential and the lower setpoint and
differential for controlling coil fractioning.
05.12
05.13
05.14
05.15
Subcooling
modulating
adjustment
Enable N
Enables subcooling modulating adjustment (only for units with centrifuge compressors) 05.30