System information

C0240111-06-07-GB
30
Mask Description Para n°
Status Code Description
S0 off Off, circuit off
S1 chiller on Chiller on
S2 ch+rec on Chiller plus recovery on
S3 chiller pd Chiller in pumpdown
S4 chiller off Chiller off
S5 rec on Recovery on
S6 defrost Defrost
S7 rec pd Recovery in pumpdown
S8 rec off Recovery off
S9 heatpump on Heat pump on
S10 ch+rec pd Chiller plus recovery in pumpdown
S11 heatpump pd Heat pump in pumpdown
S12 heatpump off Heat pump off
13.01
13.02
13.03
13.04
13.05
13.06
13.07
13.08
13.09
13.10
13.11
13.12
13.13
Valve release
time: V1: 000 s
V2: 000 s V3: 000 s
V4: 000 s V5: 000 s
Sets the valve release time. 13.14
13.15
13.16
13.17
13.18
Valve release
time : V6: 000 s
V7: 000 s V8: 000 s
V9: 000 s V10:000 s
Sets the valve release time. 13.19
13.20
13.21
13.22
13.23
C1: off
valve:CCCCCCCCCC
C2: off
valve:CCCCCCCCCC
Displays the status of the circuits and circuit valves.
C3: off
valve:CCCCCCCCCC
C4: off
valve:CCCCCCCCCC
Displays the status of the circuits and circuit valves.
Defrost
Access mask to defrost submenu.
Press "Up" or "Down" to scroll the other masks and "Esc"
to return to the submenu.
Defrost config.
Timer + Auto Tuning
Sets 3 defrost types:
Traditional, defrosting at fixed intervals,
Timer Tuning, defrosting at dynamic intervals,
Timer Tuning + Auto Tuning, defrosting at dynamic intervals, also analysing evaporation
pressure values.
21.01
Defrost parameters:
Start 03.0 bar
Stop 14.0 bar
Defines the pressure setpoints for start and stop defrost. 21.02
21.03
Defrost parameters:
Delay 01800 s
Max. time 00300 s
Drip time 120 s
Sets defrost time parameters.
Delay: cumulative time measured before the defrost procedure starts.
Max. time: maximum duration of defrost procedure.
Drip time: duration of coil dripping
21.04
21.05
21.06
Timer tuning defrost
Ref. time 120 s
Ref. T. -10°C 180 s
Ref. T. +10°C 060 s
Sets certain timer tuning defrost parameters.
Nominal defrost reference time (display only).
Reference time at -10°C used to calculate the nominal reference time.
Reference time at +10°C used to calculate the nominal reference time.
21.08
21.07
Timer tuning
maximum delay
variation perc.
20 %
Sets the maximum current defrost delay variation percentage. 21.09
Maximum defrosts
per hour 3
Sets the maximum number of defrosts in an hour. If this value is exceeded, the finned coil
alarm appears.
21.10
Ext t.-Evap. t.
calc. interval 300 s
t.ext-t.evap. var.
speed threshold 3.0°C
(only for auto tuning)
Maximum rate of change in the difference between external temperature and evaporation
temperature. If exceeded, it force activates the defrost procedure after the bypass time. The
calculation is updated every "calculation interval"
21.11
21.12
Ext t.-evap. t.
difference threshold
for changing defrost
delay 15.0°C
(only for auto tuning)
Initial threshold for the difference between external temperature and evaporation temperature
for changing the defrost start delay.
21.13
Threshold offset
Start var. 2.0°C
Variation factor
1 %
(only for auto tuning)
Offset used to calculate the threshold for changing the defrost start delay.
Defrost start delay change factor provided by Auto Tuning Defrost.
21.14
21.15