System information

C0240111-06-07-GB
36
Mask Description Para n°
High pressure
pre-alarm
Offset -03.5 bar
Diff. 05.0 bar
Mask for setting the offset (with respect to the high pressure alarm from transducer) and
differential of the high pressure pre-alarm (only visible if pre-alarm management and high
pressure transducers are enabled). The anti-freeze alarm setpoint and offset define signal
activation (negative offset), the differential defines deactivation (downwards with positive
value).
35.48
35.49
W 3000
Cod. CA 15.00 GB 
Man. C0240011-06-07
This mask contains the reference information of the software [Code] and of the reference
technical manual [Man.].
The closed padlock symbol shows that the board is provided with its propriety software; two
padlocks appear on units with 3 or 4 circuits.
Enter new
service
password
0000
Sets a new password.
ATTENTION: THE PASSWORD ENTERED IN THIS FIELD IS THE ONLY ONE THAT
ALLOWS ACCESS TO THE SERVICE MENU!!
Ventil.
Access mask to fan submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to
return to the submenu.
Condensation contr.
Enable precond.
Y
Precond. time 10 s
Precond. perc. 066 %
Enables pre-condensation (pre-
ventilation), sets the duration and defines a value at which the
fans (or condensation valve) run during this phase.
51.01
51.02
51.03
Condensation contr.
Chiller step1
Setpoint 15.0 bar
Diff. 3.0 bar
Sets step 1 in the chiller mode (only displayed if step condensation is set). 51.04
51.05
Condensation contr.
Chiller step2
Setpoint 16.5 bar
Diff. 3.0 bar
Sets step 2 in the chiller mode (only displayed if step condensation is set). 51.06
51.07
Condensation contr.
Chiller step3
Setpoint 18.0 bar
Diff. 3.0 bar
Sets step 3 in the chiller mode (only displayed if step condensation is set). 51.08
51.09
Condensation contr.
Chiller step4
Setpoint 19.0 bar
Diff. 2.0 bar
Sets step 4 in the chiller mode (only displayed if step condensation is set). 51.10
51.11
Evaporation contr.
HeatPump step1
Setpoint 08.0 bar
Diff. 1.0 bar
Sets step 1 in the heat pump mode (only displayed if step condensation is set). 51.12
51.13
Evaporation contr.
HeatPump step2
Setpoint 05.0 bar
Diff. 1.4 bar
Sets step 2 in the heat pump mode (only displayed if step condensation is set). 51.14
51.15
Evaporation contr.
HeatPump step3
Setpoint 02.2 bar
Diff. 0.8 bar
Sets step 3 in the heat pump mode (only displayed if step condensation is set). 51.16
51.17
Evaporation contr.
HeatPump step4
Setpoint 01.0 bar
Diff. 0.5 bar
Sets step 4 in the heat pump mode (only displayed if step condensation is set). 51.18
51.19
Circuits on with
fan overheating
N
Enables the circuits even if the fan overheating alarm has tripped. 51.20
Calibration
Access mask to calibration submenu.
Press "Up" or "Down" to scroll the other masks and
"Esc" to return to the submenu.
Master calibration
offset Value
B1: 0.0bar 07.3bar
B2: 0.0°C 12.3°C
Modifies the probe offsets. (Only present if required by the type of machine configured).
The word "master" only appears on units with more than 2 circuits.
27.01
27.02
Master calibration
offset Value
B3: 0.0°C 12.3°C
B4: 0.0°C 12.3°C
Modifies the probe offsets. (Only present if required by the type of machine configured)
The word "master" only appears on units with more than 2 circuits.
27.03
27.04
Master calibration
offset Value
B5: 0.0°C 12.3°C
B6: 0.0°C 07.3bar
Modifies the probe offsets. (Only present if required by the type of machine configured)
The word "master" only appears on units with more than 2 circuits.
27.05
27.06
Master calibration
offset Value
B7: 0.0°C 05.3°C
B8: - -
Modifies the probe offsets. (Only present if required by the type of machine configured)
The word "master" only appears on units with more than 2 circuits.
27.07
27.08