System information
C0240111-06-07-GB
36
Mask Description Para n°
High pressure
pre-alarm
Offset -03.5 bar
Diff. 05.0 bar
Mask for setting the offset (with respect to the high pressure alarm from transducer) and
differential of the high pressure pre-alarm (only visible if pre-alarm management and high
pressure transducers are enabled). The anti-freeze alarm setpoint and offset define signal
activation (negative offset), the differential defines deactivation (downwards with positive
value).
35.48
35.49
W 3000
Cod. CA 15.00 GB
Man. C0240011-06-07
This mask contains the reference information of the software [Code] and of the reference
technical manual [Man.].
The closed padlock symbol shows that the board is provided with its propriety software; two
padlocks appear on units with 3 or 4 circuits.
Enter new
service
password
0000
Sets a new password.
ATTENTION: THE PASSWORD ENTERED IN THIS FIELD IS THE ONLY ONE THAT
ALLOWS ACCESS TO THE SERVICE MENU!!
Ventil.
← ↓
Access mask to fan submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to
return to the submenu.
Condensation contr.
Enable precond.
Y
Precond. time 10 s
Precond. perc. 066 %
Enables pre-condensation (pre-
ventilation), sets the duration and defines a value at which the
fans (or condensation valve) run during this phase.
51.01
51.02
51.03
Condensation contr.
Chiller step1
Setpoint 15.0 bar
Diff. 3.0 bar
Sets step 1 in the chiller mode (only displayed if step condensation is set). 51.04
51.05
Condensation contr.
Chiller step2
Setpoint 16.5 bar
Diff. 3.0 bar
Sets step 2 in the chiller mode (only displayed if step condensation is set). 51.06
51.07
Condensation contr.
Chiller step3
Setpoint 18.0 bar
Diff. 3.0 bar
Sets step 3 in the chiller mode (only displayed if step condensation is set). 51.08
51.09
Condensation contr.
Chiller step4
Setpoint 19.0 bar
Diff. 2.0 bar
Sets step 4 in the chiller mode (only displayed if step condensation is set). 51.10
51.11
Evaporation contr.
HeatPump step1
Setpoint 08.0 bar
Diff. 1.0 bar
Sets step 1 in the heat pump mode (only displayed if step condensation is set). 51.12
51.13
Evaporation contr.
HeatPump step2
Setpoint 05.0 bar
Diff. 1.4 bar
Sets step 2 in the heat pump mode (only displayed if step condensation is set). 51.14
51.15
Evaporation contr.
HeatPump step3
Setpoint 02.2 bar
Diff. 0.8 bar
Sets step 3 in the heat pump mode (only displayed if step condensation is set). 51.16
51.17
Evaporation contr.
HeatPump step4
Setpoint 01.0 bar
Diff. 0.5 bar
Sets step 4 in the heat pump mode (only displayed if step condensation is set). 51.18
51.19
Circuits on with
fan overheating
N
Enables the circuits even if the fan overheating alarm has tripped. 51.20
Calibration
← ↓
Access mask to calibration submenu.
Press "Up" or "Down" to scroll the other masks and
"Esc" to return to the submenu.
Master calibration
offset Value
B1: 0.0bar 07.3bar
B2: 0.0°C 12.3°C
Modifies the probe offsets. (Only present if required by the type of machine configured).
The word "master" only appears on units with more than 2 circuits.
27.01
27.02
Master calibration
offset Value
B3: 0.0°C 12.3°C
B4: 0.0°C 12.3°C
Modifies the probe offsets. (Only present if required by the type of machine configured)
The word "master" only appears on units with more than 2 circuits.
27.03
27.04
Master calibration
offset Value
B5: 0.0°C 12.3°C
B6: 0.0°C 07.3bar
Modifies the probe offsets. (Only present if required by the type of machine configured)
The word "master" only appears on units with more than 2 circuits.
27.05
27.06
Master calibration
offset Value
B7: 0.0°C 05.3°C
B8: - -
Modifies the probe offsets. (Only present if required by the type of machine configured)
The word "master" only appears on units with more than 2 circuits.
27.07
27.08