System information

C0240111-06-07-GB
55
Para n°
Description of parameter Default U.M. Min. Max.
13.12 Valve configuration in status 11 - heatpump pd - 0 - 0 99
13.13 Valve configuration in status 12 - heatpump off - 0 - 0 99
13.14 Valve 1 release time 0 s 0 999
13.15 Valve 2 release time 0 s 0 999
13.16 Valve 3 release time 0 s 0 999
13.17 Valve 4 release time 0 s 0 999
13.18 Valve 5 release time 0 s 0 999
13.19 Valve 6 release time 0 s 0 999
13.20 Valve 7 release time 0 s 0 999
13.21 Valve 8 release time 0 s 0 999
13.22 Valve 9 release time 0 s 0 999
13.23 Valve 10 release time 0 s 0 999
15.03 Pressure setpoint for forcing chiller status from recovery 23.5 bar 10.0 P 01.21
15.04 Pressure differential for forcing chiller status from recovery 5.0 bar 0.1 9.9
15.05 Enables cyclical forcing from chiller plus heat recovery mode to chiller mode
0 -
15.06
Maximum time in chiller plus heat recovery mode before forcing to chiller
mode
60 min 1 999
15.07
Minimum time in chiller mode before forcing to chiller plus heat recovery
mode
120 s 40 500
17.01 Enable condensation control (0:No - 1:Yes) 1 -
17.02 Type of condensation adjustment (0:Step. Cont - 1:Step - 2:Continuous) 2 - 0 2
17.03 condensation steps 3 - 1 P 99.23
17.04 Type of condensation control (0:Separate - 1:Individual - 2:Dual) 0 - 0 P 99.26
17.05
Linear operation model (0:Standard - 1:0-10V - 2:PWM - 3:FAE - 4:0-10V
C5110973)
2 - 0 4
17.06 Condensation valve logic (0:direct - 1:reverse) 0 -
17.10 Enable maximum condensation override in the chiller mode (0:No - 1:Yes) 0 -
17.11 Maximum condensation override setpoint in the chiller mode 23.0 bar 10.0 P 01.21
17.12 Maximum condensation override differential in the chiller mode 3.0 bar 0.1 5.0
17.13
Enable minimum evaporation override in the heat pump mode (0:No -
1:Yes)
0 -
17.14 Minimum evaporation override setpoint in the heat pump mode 1.0 bar 0.5 15.0
17.15 Minimum evaporation override differential in the heat pump mode 0.5 bar 0.1 5.0
17.32 Continuous adjustment setpoint in the chiller mode 14.0 bar 5.0 P 01.21
17.33 Continuous adjustment differential in the chiller mode 5.0 bar 0.1 15.0
17.34 Continuous adjustment setpoint in the heat pump mode 6.0 bar 0.5 15.0
17.35 Continuous adjustment differential in the heat pump mode 1.0 bar 0.1 15.0
17.36 Maximum condensation limit in continuous adjustment 100 % P 17.37 100
17.37 Minimum condensation limit in continuous adjustment 30 % 0 P 17.36
17.38
Adjustment under the minimum condensation limit (0:adjustment always
-
1:adjustment Off)
1 -
17.39 Condensation adjustment off differential 1.0 bar 0.0 5.0
17.40 Water modulating valve control (0:disabled - 1:enabled) 0 -
17.41 Opening time 0-100% water modulating valve 70 s 0 999
19.01 Temperature difference for activating freecooling 1.0 °C 1.0 5.0
19.02 Temperature offset for deactivating freecooling -4.0 °C -10.0 P 99.21
19.03 Temperature delta for deactivating freecooling 1.0 °C 0.1 3.0
19.04 Type of freecooling valve control (0:direct - 1:reverse) 0 -
19.05 Hysteresis temperature of individual fans 0.3 °C 0.0 1.0
19.06 Start/stop delay for each fan 20 s 1 500
21.01 Defrost type (0:standard - 1:Timer Tuning - 2:Timer Tuning + Auto Tuning) 2 - 0 2
21.02 Start defrost setpoint 3.0 bar 0.0 P 21.03
21.03 Stop defrost setpoint 14.0 bar P 21.02 P 25.07
21.04 Defrost delay 1800 s 60 3600
21.05 Maximum defrost time 300 s 10 500
21.06 Drip time 120 s 0 500
21.07 Reference time at +10°C for calculating reference time. 60 s 30 P 21.08
21.08 Reference time at -10°C for calculating reference time. 180 s P 21.07 P 99.28
21.09 Defrost start delay variation percentage 20 s 0 100
21.10 Maximum number of defrosts per hour 3 - 1 9
21.11
Calculation interval of the rate of change in the difference between external
temperature and evaporation temperature
300 s 10 600
21.12
Maximum rate of change in the difference between external temperature
and evaporation temperature.
3.0 °C 0.1 9.9
21.13
Initial threshold of difference between external temperature and evaporation
temperature for changing the defrost delay.
15.0 °C 2.0 20.0
21.14 Offset for calculating the threshold for changing the defrost delay. 2.0 °C 0.5 9.9
21.15 Defrost delay variation factor 1 % 0 99
21.16 Circuit start-up bypass delay for override in the defrost mode 120 s 0 999
21.17
Delay in the defrost delay change with temperature difference higher than
the calculated threshold
600 s 0 999
21.18 Maximum derived evaporation pressure -0.1 bar/m -10.0 10.0