System information

C0240111-06-07-GB
56
Para n°
Description of parameter Default U.M. Min. Max.
21.19 Forced defrosting with low pressure (0:disabled - 1:enabled) 1 -
21.20 Forced defrosting pressure threshold 1.7 bar P 23.05 9.9
21.21 Circuit separation pressure with hermetic compressors 1.7 bar P 23.05 9.9
21.22 Restore pressure for separating the circuits with hermetic compressors 2.1 bar P 21.21 9.9
21.23 Free defrost enable (0:disabled - 1:enabled) 1 -
21.24 Minimum external temperature for free defrost operation 4.0 °C -10.0 10.0
21.25 Drip mode enable with compressors on (0:disabled - 1:enabled) 0 -
23.01 High pressure from transducers alarm 28.0 bar 0.0 P 25.07
23.02 High pressure from transducers alarm differential 7.0 bar 0.0 30.0
23.03 of low pressure alarm automatic resets 3 - 0 5
23.04 Duration of low pressure alarm 120 s 0 500
23.05 Low pressure alarm setpoint 1.6 bar 0.1 9.9
23.06 Low pressure alarm differential 0.9 bar 0.1 4.0
23.07 Enable low pressure control with low external air temperature (0:No - 1:Yes)
0 -
23.08 Start-up time for low pressure control with low external air temperature 120 s 10 P 23.04
23.09 Low pressure setpoint with low external air temperature 0.1 bar 0.1 P 23.05
23.10 Low pressure differential with low external air temperature 0.5 bar 0.1 4.0
23.11 of centrifugal compressor alarm automatic resets 3 - 0 5
23.12 Bypass time of compressor thermal protection alarm 10 s 0 360
23.13 Setpoint for activating the high compressor discharge temperature alarm 125.0 °C 70.0 125.0
23.14
Differential for deactivating the high compressor discharge temperature
alarm
10.0 °C 2.0 25.0
23.15 Compressor oil alarm delay after starting 90 s 1 120
23.16 Compressor oil alarm delay during running 90 s 1 120
23.25 of flow switch alarm automatic resets 3 - 0 9
23.26 Evaporator flow switch start-up delay 10 s 1 120
23.27 Evaporator flow switch running delay 1 s 1 20
23.28 Recuperator flow switch start-up delay 10 s 1 120
23.29 Recuperator flow meter running delay 1 s 1 20
23.30 Condenser flow meter start-up delay 10 s 1 120
23.31 Condenser flow meter running delay 1 s 1 20
23.34
Maximum delay for automatic reset of flow switch alarms and pump
operation in alarm conditions
15 s 15 999
27.01 Probe 1 calibration 0.0 °C/bar -9.9 9.9
27.02 Probe 2 calibration 0.0 °C/bar -9.9 9.9
27.03 Probe 3 calibration 0.0 °C/bar -9.9 9.9
27.04 Probe 4 calibration 0.0 °C/bar -9.9 9.9
27.05 Probe 5 calibration 0.0 °C/bar -9.9 9.9
27.06 Probe 6 calibration 0.0 °C/bar -9.9 9.9
27.07 Probe 7 calibration 0.0 °C/bar -9.9 9.9
27.08 Probe 8 calibration 0.0 °C/bar -9.9 9.9
27.09 Probe 9 calibration 0.0 °C/bar -9.9 9.9
27.10 Probe 10 calibration 0.0 °C/bar -9.9 9.9
27.11 Expansion 1 Probe 1 calibration 0.0 °C/bar -9.9 9.9
27.12 Expansion 1 Probe 2 calibration 0.0 °C/bar -9.9 9.9
27.13 Expansion 1 Probe 3 calibration 0.0 °C/bar -9.9 9.9
27.14 Expansion 1 Probe 4 calibration 0.0 °C/bar -9.9 9.9
27.21 Expansion 2 Probe 1 calibration 0.0 °C/bar -9.9 9.9
27.22 Expansion 2 Probe 2 calibration 0.0 °C/bar -9.9 9.9
27.23 Expansion 2 Probe 3 calibration 0.0 °C/bar -9.9 9.9
27.24 Expansion 2 Probe 4 calibration 0.0 °C/bar -9.9 9.9
27.25 Expansion 2 Probe 5 calibration 0.0 °C/bar -9.9 9.9
27.26 Expansion 2 Probe 6 calibration 0.0 °C/bar -9.9 9.9
27.27 Expansion 2 Probe 7 calibration 0.0 °C/bar -9.9 9.9
27.28 Expansion 2 Probe 8 calibration 0.0 °C/bar -9.9 9.9
27.31 Expansion 3 Probe 1 calibration 0.0 °C/bar -9.9 9.9
27.32 Expansion 3 Probe 2 calibration 0.0 °C/bar -9.9 9.9
27.33 Expansion 3 Probe 3 calibration 0.0 °C/bar -9.9 9.9
27.34 Expansion 3 Probe 4 calibration 0.0 °C/bar -9.9 9.9
27.51 Expansion 5 Probe 1 calibration 0.0 °C/bar -9.9 9.9
27.52 Expansion 5 Probe 2 calibration 0.0 °C/bar -9.9 9.9
27.53 Expansion 5 Probe 3 calibration 0.0 °C/bar -9.9 9.9
27.54 Expansion 5 Probe 4 calibration 0.0 °C/bar -9.9 9.9
31.01 Slave Probe 1 calibration 0.0 °C/bar -9.9 9.9
31.02 Slave Probe 2 calibration 0.0 °C/bar -9.9 9.9
31.03 Slave Probe 3 calibration 0.0 °C/bar -9.9 9.9
31.04 Slave Probe 4 calibration 0.0 °C/bar -9.9 9.9
31.05 Slave Probe 5 calibration 0.0 °C/bar -9.9 9.9
31.06 Slave Probe 6 calibration 0.0 °C/bar -9.9 9.9
31.07 Slave Probe 7 calibration 0.0 °C/bar -9.9 9.9
31.08 Slave Probe 8 calibration 0.0 °C/bar -9.9 9.9