Para n°
Description of parameter
99.23
Maximum number of available ventilation steps (depends on the type of board used and the configured type of
compressors):
- hardware XL (4:maximum four ventilation steps)
- unit with centrifuge compressors (4:maximum four steps)
- other cases (3:maximum three ventilation steps)
99.24 Maximum number of pumps available from board (2: maximum two pumps)
99.25 Minimum settable limit for choosing the compressor type (depends on the type of board installed):
- with hardware B (1:hermetic)
- with hardware L (0:centrifuge or hermetic)
- with hardware XL (2:alternative or screw)
99.26 Possible ventilation type, depends on the number of cooling circuits:
- unit with 4 circuits (2: separate, single or dual ventilation)
- unit with 3 circuits (0: separate ventilation)
- unit with 1 or 2 circuits (1: separate or single ventilation)
99.28 Maximum upper Timer-Tuning-Defrost band limit. This is the result of (maximum defrost time)-
(reference time calculated by
the system according to weather conditions and the unit operating mode) (P21.05 - P21.07 o P21.05 - P21.08)
99.29 Maximum settable chiller setpoint limit with inlet adjustment of:
High inlet temperature alarm setpoint-7°C (P35.41 - 7°C)
99.30 Maximum settable chiller setpoint limit with outlet adjustment of:
High inlet temperature alarm setpoint-12°C (P35.41 - 12°C)
99.31 maximum limit for the configurable type of evaporators (1:no evaporation or water evaporation)
99.32 maximum limit for setting the screw compressor oil management algorithms (depends on the set type of adjustment):
- with modulating adjustment (1: none or direct)
- with step adjustment (3: none, direct, indirect or direct+indirect)