6.2 Condensation
Condensation adjustment depends on how the fans are turned on.
Various condensation adjustment types in the “chiller” operating mode are shown below.
The fans may be turned on using the on/off system ( “step”) in which the fans are turned on
progressively one after the other (figure 6.3a) or mutually excluded (figure 6.3b). Fans switched on in
parallel but that increase fan speed (depending on pressure) are illustrated in figure 6.3c).
Pressure
Set Point
Set Point -
differential
Set Point
Set Point -
differential
Set Point
Set Point -
differential
Active
steps
1
2
3
Step1 on
Step2 on
Step3 on
Continual step speed adjustment
Set Point
Set Point -
differential
Step4 on
Figure 6.3a: “continuous step” condensation adjustment
Pressure
Set Point
Set Point -
differential
1
Set Point
Set Point -
differential
Step1 on Step3 on
Active
steps
Set Point
Set Point -
differential
Step2 on
step speed adjustment
Set Point
Set Point -
differential
Step4 on
Figure 6.3b: “step” condensation adjustment
Condensation
Pressure
Set Point
Set point +
differential
Continual adjustment
100%
max sp. %
min sp. %
Set Point -
diff. Off
Condensation without
Adjustment off
Condensation with
Adjustment off
Figure 6.3c: “step” condensation adjustment