C0240111-06-07-GB
7
In the W3000 base
the following procedure is used: press [MENU] / select the “User” menu using
the [UP] or [DOWN] keys / press [ENTER] to access the menu / press enter to type in the
password / press [UP] or [DOWN] to choose the password and [ENTER] to confirm / use the [UP]
or [DOWN] keys to choose the “dI 0” (Enable from digital input) mask / press [ENTER] to view
the current setting of the parameter (“Y” or “N”) / press [ENTER] to modify the parameter (the
display flashes) / press [UP] or [DOWN] to select one of the two alternatives.
Press the “digital input” button on the panel to switch the unit on and off.
using time bands:
For W3000 and W3000 compact (if the clock board is fitted)
Make sure that the “Clock board not installed” is not displayed in the “clock menu”.
Check that the “Time bands enabled” parameter in the “user menu” is set to “Yes”.
SWITCHING ON: set the required switching on time in the “clock menu”. The unit switches on
when the set time is reached. The “On from time bands” message appears in the main mask
to show that the unit has been switched on. N.B.: The unit does not switch on if it is set to
“Off from keypad” or “Off from digital input”.
SWITCHING OFF: set the required switching off time in the “clock menu”. The unit switches
off when the set time is reached. The “Off from time bands” message appears in the main
mask to show that the unit has been switched off.
using the supervision protocol:
Only if the serial board is fitted.
Check that the “Supervisor enable” and “On/Off enable from supervisor” parameters in the “user
menu” are set to “Yes”.
Proceed as follows:
SWITCHING ON: Send the switching on command from the protocol. The “On from
supervisor” message appears in the main mask to show that the unit has been switched on.
N.B.: The unit does not switch on if it is set to “Off from keypad” or “Off from digital input”.
SWITCHING OFF: Send the switching off command from the protocol. The “Off from
supervisor” message appears in the main mask to show that the unit has been switched off.
In the W3000 base the following procedure is used: press [MENU] / select the User menu using
the [UP] or [DOWN] keys / press [ENTER] to access the menu / press enter to type in the
password / press [UP] or [DOWN] to choose the password and [ENTER] to confirm / use the [UP]
or [DOWN] keys to choose the “SPr” (Enable from supervisor) mask / press [ENTER] to view the
current setting / press [ENTER] to see the display flashing / press [UP] or [DOWN] to modify the
setting and press [ENTER] to confirm.