System information

C0240111-06-07-GB
70
ā€œLā€ WATER-WATER UNIT ā€œLā€
Digital inputs
ID1
Circuit 1 low pressure switch
ID2
Compressor 1 thermal protection
ID3
Compressor 2 thermal protection
ID4
Circuit 2 low pressure switch
ID5
Compressor 3 thermal protection
ID6
Compressor 4 thermal protection
ID7
Condenser flow switch (units with freon-side
reversal only)
ID8
ID9
Evaporator flow switch
ID10
Remote on/off
ID11
Pump 1 thermal switch
ID12
Pump 2 thermal switch
ID13
Circuit 1 high pressure switch
ID14
Circuit 2 high pressure switch
ID15
Phase sequence
ID16
System pressure control
ID17
Demand limit
ID18
Chiller/Heat pump from external contact
Analogue inputs
B1
Circuit 1 high pressure transducer
B2
Evap. outlet water temperature (blend)
B3
Evaporator inlet water temperature
B4
Evap. outlet water temperature 1
B5
Evap. outlet water temperature 2
B6
Circuit 2 high pressure transducer
B7
Outlet 2 water temp. / cond. inlet
B8
Setpoint var. from ext. signal (4-20mA.0-10V)
B9
Condenser outlet water temperature
B10
Dual setpoint from external contact
Digital outputs
NO1
Unit operating mode: Chiller - Heat pump /
Circuit 1 cycle reversal valve (units with freon-
side reversal only)
NO2
Circuit 2 cycle reversal valve (units with freon-
side reversal only)
NO3
Solenoid valve 1
NO4
Solenoid valve 2
NO5
Pump 1
NO6
Pump 2
NO7
Compressor 1
NO8
Compressor 2
NO9
NO10
NO11
NO12
Evaporator antifreeze heating element
NO13
General alarms cumulative
NO14
Compressor 3
NO15
Compressor 4
NO16
NO17
NO18
Analogue outputs
Y1
Condensation adjustment
Y2
Y3
Y4
Y5
Y6