WATER-WATER UNIT “B”
Digital inputs
ID1
Circuit 1 high pressure switch
ID2
Circuit 2 high pressure switch
ID3
Remote on/off
ID4
Chiller/Heat pump from external contact
ID5
Evaporator flow switch
ID6
Circuit 1 low pressure switch
ID7
Circuit 2 low pressure switch
ID8
Compressor 1 thermal protection
ID9
Compressor 2 thermal protection
ID10
Pump 1 thermal protection
ID11
Condenser flow switch (units with freon-side
reversal only)
ID12
Phase sequence
ID13
System pressure control
ID14
Pump 2 thermal switch
ID15
Demand limit
Analogue inputs
B1
Circuit 1 high pressure transducer
B2
Circuit 2 high pressure transducer
B3
Evaporator inlet water temperature
B4
Evaporator outlet 1 water temperature
B5
Evaporator outlet 2 water temperature
B6
Condenser outlet water temperature
B7
Outlet 2 water temp. / cond. inlet
B8
Setpoint var. from ext. signal output 4-20 mA
Digital outputs
NO1
Evaporator antifreeze heating element
NO2
Unit operating mode: Chiller - Heat pump /
Circuit 1 cycle reversal valve (units with freon-
side reversal only)
NO3
Circuit 2 cycle reversal valve (units with freon-
side reversal only)
NO4
NO5
Pump 1
NO6
Compressor 1
NO7
Compressor 2
NO8
General alarms cumulative
NO9
Pump 2 / Condenser pump (units with freon-side
reversal only)
NO10
NO11
NO12
Analogue outputs
Y1
Condensation adjustment (PWM)
Y2