System information

C0240111-06-07-GB
96
10 Terminal configuration
The first thing to do when connecting the boards of several units in a network in order to have a remote
keypad or replace a board, is to configure the terminals.
This cannot be achieved with the basic W3000 keypad
. In this case, configure the terminals using the
W3000 or W3000 compact keypad and afterwards reconnect the W3000 basic display.
Before starting, it is advisable to check that each board and each terminal has been identified with the
correct address established when the network was designed. It is important to remember that as the set
address is only read by the boards during start-up, it is best to perform a global reset of all the devices if
a mistake is made when configuring the addresses (more than one board with the same address). Reset
the network by disconnecting all the devices from the power supply .
The configuration procedure can be activated from any terminal (keyboard), which may also be
connected temporarily only to perform configuration operations and removed upon completion. The
operations to perform are described in the following paragraphs.
10.1 Setting the keypad address
After connecting the keypad to the device, perform the following procedure:
1)
Press [UP], [DOWN] and [ENTER] together and hold down until the
mask shown to the side appears.
Display address
Setting..........:00
I/O Board address:
2) Press [ENTER] to move the cursor to “Display address setting”. Press
[UP] and [DOWN] to set the required keypad address (e.g.: 21).
Display address
Setting..........:21
I/O Board address:--
3) This mask means that the address of the keyboard has been set.
Display address
changed
4) If an empty mask or a mask showing “NO LINK” appears after
pressing [ESC], it means that the keypad is not communicating with
any board. Either the board must be addressed or the plan network
must be configured.
NO LINK
N.B.: This is a timed procedure; if the parameters are not set within a few seconds, the display turns off.