System information

C0240111-06-07-GB
98
10.3 Plan network configuration
10.3.1 Plan network connection (local)
For each unit with an on-board keyboard, perform the following procedure to create a “local” plan
network:
0 Make sure the board has been addressed (as described in the
previous paragraph).
pLan address: 1
UP: increase
DOWN: decrease
ENTER: save & exit
1 Press [UP], [DOWN] and [ENTER] together and hold down until the
mask shown to the side appears.
Display address
Setting..........:00
I/O Board address:
2 Set the required address for the keyboard (e.g.: 21 )
Display address
Setting..........:21
I/O Board address:--
3 Press [ENTER] to display the address of the boards in pLan (in this
case 1 ).
N.B.: If there is more than one board, press [UP] or [DOWN] to
choose which board to configure.
Display address
Setting..........:21
I/O Board address:01
4 Press [ENTER] to configure the terminals of the selected board; press
[ENTER] to confirm
Terminal config
Press ENTER
To continue
5 In this mask, the [ENTER] key moves the cursor from one field to
another and the [UP] or [DOWN] keys change the values.
P:01 means that the board with address 1 is being configured.
P:01 Adr Priv/Shared
Trm1 None --
Trm2 None --
Trm3 None -- Ok?No
6 Configure keyboard 21 (previously set) as Pr=private (usually the one
on the unit). (Sp=printer, or Sh=shared)
P:01 Adr Priv/Shared
Trm1 21 Pr
Trm2 None --
Trm3 None -- Ok?No
7 The remote keyboard must also be configured. Simply define the
keyboard addressed with 32 (even if not present) as Sh.
P:01 Adr Priv/Shared
Trm1 21 Pr
Trm2 32 Sh
Trm3 None -- Ok?No
8 To save the settings and exit the configuration procedure, move the
cursor to “No”, change it to “Yes” and press [ENTER]. To exit without
saving the settings, wait 30 seconds without touching the keyboard.
P:01 Adr Priv/Shared
Trm1 21 Pr
Trm2 32 Sh
Trm3 None -- Ok?Yes
9 The following mask may appear. If no expansions are connected,
simply press [ESC] to show the main display menu.
####################
...expansion
link...
####################
To connect several units together and remote control them, thereby forming a plan network (global), a
remote keypad controlling all the units is required.
The remote keypad cannot be a W3000 base keypad. If a W3000 basic keypad is installed on the
machine, replace it with a 3000 compact.