- CTC-1052-QT-DT35A will match the numbers starting from the last digit, and verify 10 digits at
the most.
For example, if a number string 321 is programmed, CTC-1052-QT-DT35A will instantly pick
up any call that has 321 as the last 3 digits. If a number string 17605851848 is programmed,
CTC-1052-QT-DT35A will instantly pick up any call that has 7605851848 as the last 10 digits.
The first digit "1" of the Caller ID will be ignored.
Click “Write” when you have completed all settings.
4.4.1.7 Temperature
The Temperature tab allows user to program the High/Low Temperature Alarm thresholds.
When temperature reaches/rises above High Temperature threshold or drops below Low
Temperature threshold, alarm will be activated.
55# High Temperature Reporting:
- Set the High Temperature Reporting threshold in degrees Fahrenheit. (32°F ~ 212 °F)
- Factory Default is 95°F.
56# Low Temperature Reporting:
- Set the Low Temperature Reporting threshold in degrees Fahrenheit. (32°F ~ 212 °F)
- Factory Default is 47°F.
4.4.1.8 CO2
The CO2 tab allows user to program the CO2 Alarm Reporting threshold. When CO2
concentration value reaches or exceeds the Alarm Reporting threshold, CTC-1052-QT-
DT35A will report CO2 Alarm to CMS.