5.4. Timer
Supervision Check: Select to enable or disable system supervision function. When
ON is selected, the Control Panel will monitor the accessory devices according to the
supervision signal received.
Supervision Timer: The Control Panel monitors accessory devices according to the
supervision signal transmitted regularly from the device. User this option to set a time
period for receiving supervision signals. If the Control Panel fails to receive supervision
signal from a device within this duration, it will consider the device out of order and
report the event accordingly. NOTE: This must be set to 2 hours or less to meet the
requirementes of EN Grade 2.
Cross Zone Timer: When a Sensor configured for Cross Zone Monitoring is tripped,
this timer begins to count down. If a different zone is tripped in this time period the
control panel will report a Burglar Alarm, otherwise the panel will report a Cross Zone
Trouble event. Repeatedly tripping the zone configured for cross zone monitoring will
reset the Cross Zone Timer.
Fire Verification Timer: When a Smoke Detector set to Fire Verification attribute is
triggered, the panel begins to sound alarm, counts down Fire Verification Timer and
reports a Near Alarm event (CID 118). Triggering a regular Smoke Detector with Smoke
attribute during the Fire Verification Timer will prompt panel to report Smoke Alarm
event (CID 111), the timer will not be reset. When the Fire Verification Timer expires,
the panel reports Fire Verification Timeout event (CID 695).
5.5. Trouble Condition Setting
The Trouble Condition Setting determines panel report time when AC failure or RF jamming is
detected.
AC Fail Report Timer: Set the waiting time before Control Panel report to Monitoring
Station when AC failure is detected.
Jamming Report Timer: Set the waiting time before the panel report to Monitoring
Station when radio inteference is detected.