10.3. Cross Zone Verification
Cross Zone Verification is use to setup cross verification for intrusion sensors.
To use Cross Zone Verification, the following sensor and panel setting must be adjusted:
1 At least 1 intrusion sensor must be set to Cross Zone attribute.
2 The Cross Zone Timer option under Panel Setting webpage must be enabled.
Cross Zone Verification Rule
Cross Zone function does not activate under Exit and Entry Time.
When a sensor set to Cross Zone attribute is triggered, the panel begins to sound alarm,
counts down Cross Zone Timer and reports a Cross Zone First Trip event (CID 693).
If the Cross Zone Timer expires without any other sensor trigger, the panel reports
Cross Zone Trouble event (CID 378) when the timer expires.
If the same sensor is triggered again during Cross Zone Timers, the Cross Zone Timer
is reset and extended.
If another sensor is triggered during the timer:
The Panel report Burglar (CID 130) for both sensors.
If the newly triggered sensor is set to Cross Zone attribute, the Panel also report
Burglar Verified (CID 139) for this sensor.
The Cross Zone Timer is reset and extended.
When the Cross Zone Timer expires, the panel reports Cross Zone Timeout (CID
694).