10.4. Fire Verification
Fire Verification is use to setup verification for Smoke Detector.
To use Fire Verification, the following sensor and panel setting must be adjusted:
1 At least 1 Smoke Detector must be set to 24 HR Fire with Verification attribute.
2 The Fire Verification Timer option under Panel Setting webpage must be enabled.
Fire Verification Rule
When a Smoke Detector set to Fire Verification attribute is triggered, the panel begins to
sound alarm, counts down Fire Verification Timer and reports a Near Alarm event (CID 118).
Triggering any Smoke Detector with Fire Verification attribute (including the original
Some Detector) during Fire Verification Timer will prompt panel to report Smoke Alarm
event (CID 111), the timer will be reset and extended.
Triggering a regular Smoke Detector with Smoke attribute during the Fire Verification
Timer will prompt panel to report Smoke Alarm event (CID 111), the timer will not be
reset..
When the Fire Verification Timer expires, the panel reports Fire Verification Timeout
event (CID 695).