Zone Wiring (Zone 1 -16)
The 16 zones can be wired by supervising NC (normally close) or NO (normally open)
devices, e.g. PIR sensor, door contact, smoke detector, water sensor, fire sensor, CO
sensor, gas detector, heat detector, and glass break detector, etc.
Wire gauge: Minimum 20 AWG, maximum 18 AWG. Do not use shielded wire.
The hardwired zones support Single-End-of-Line (SEOL) or Double-End-of-Line (DEOL)
loop configuration, with a value from 1K, 2.2K, 3.74K, 4.7K, 5.6K, 6.8K, 8.2K, 10K ohms.
Please install the resistor(s) at the end of each zone loop far away from the Control Panel.
The Panel will detect if the circuit is secure, open, or short.
For an NC loop, please have an EOL resistor in series with the loop.
For an NO loop, please have an EOL resister in parallel (across) the loop. Please refer to
the following diagrams for wiring examples.
There is no EOL resistor in loop 1 and loop 2.
NO/NC Wiring
1.
2.
Single-End-of-Line Resistor Wiring
3.
4.
15