Owner's Manual

pol~caseJ
Installation Instructions
for
Electrical Enclosure,
UL-
SOSA
Listed, Category
NITW
- Industrial Control
Panel Enclosure
File # E352997
Types
1,
2, 3, 3X, 3R, 3RX, 3S, 3SX, 4, 4X,
5,
6/6P, 12, 13
For Type 6/6P enclosure ratings, all 4 screws must
be
used to secure the cover
with
or
without the hinge
Components and Assembly
ZH Series units with Cover Latches include (1) or (2) S.S. cover latches to
secure the cover. Number
of
latches depends on enclosure size. The enclosure
also consists of a base, gasketed cover, mounting feet or flanges, & (4) #10-32
S.S. screws to install the mounting feeUflanges. The latches are installed
by
sliding
the latch over the latch keeper feature on the side
of
the enclosure base. For
enclosures 12"x10"
x6
" and larger, two latches are required. For 10"x8"x6" and
smaller, one latch is required.
ZH Series units with Cover Screws includes (4) #10-32 S.S. cover screws to
secure the cover. Recommended torque
for
cover screws is 12 in-pounds. The
enclosure also consists
of
a base, gasketed cover, mounting feet
or
flanges, & (4)
#10-32 S.S. screws to install the mounting feeUflanges.
ZQ Series units with Cover Screws includes (4) #10-32 S.S. cover screws to
secure the cover. Recommended torque
for
cover screws is 12 in-pounds. The
enclosure also consists
of
a base, gasketed cover, mounting feet
or
flanges, & (4)
#10-32 S.S. screws to install the mounting feeUflanges.
Foot/Flange mounting: The mounting feet/flanges are fastened to the base using
#10-32 S.S. screws provided with the enclosure. Suggested torque is 15-20 in-
pounds. The cover screws & fooUflange screws are identical.
Modifications
If this enclosure has been provided with customer-specified modifications, any
openings must be filled with UL Listed components or fittings with environmental
ratings equal to the enclosure's environmental rating to preserve the desired
rating. Any modification must be made to the components manufacturer's
specifications.
Type 2, 3R, &/or 3RX enclosures require a drainage opening in the enclosure.
Drainage openings shall not be less than 3.2
mm
(1
/8") in diameter or more than
6.4
mm
(1/4") in diameter. The hole
must
be located in the lowest part
of
the
bottom wall to maintain Type 2, 3R,
3RX
ratings.
Installation
of
Conduits and Grounding
Conduit holes can be made in the enclosure in any location
per
applicable codes
and standards. Rigid, metallic and non-metallic conduit and fittings can be used,
as well
as
appropriate liquid-tight flexible conduit systems Ho
le
saws, speed
bores,
or
hydraulic punches can be used.
In
order to maintain required
environmental ratings, only the use
of
UL
Listed metallic conduit hubs with
environmental ratings appropriate for the end use are required.
Metallic conduits must be grounded. Bonding between conduit connection is not
automatic and must be provided as a part
of
the installation.
In order to prevent enclosure damage and to maintain enclosure requirements,
conduits should
be
aligned to prevent unnecessary stress on enclosure walls.
Misc. Notes
1. Ok to use a compatible PVC cement to connect fittings to the enclosure.
2. Internal mounting bosses have #10-32 thread. The non-inserted mounting
bosses accept a #10 x 3/8" self-tapping screw.
Rev. -

Summary of content (3 pages)