Installation manual
I/O Control Parameters
S1A53838 09/2011 93
27 [RV, PS3]
Combination of reverse 
run command and preset 
speed 3 command
OFF: Motor ramps down to a stop 
ON: Motor runs in reverse, at speed set by Sr3, preset speed 3
30 [FW-RMP2-SP1]
Combination of forward 
run command, preset 
speed 1 command, and 
acceleration/deceleration 
pattern 2 selection
OFF: Motor stops, ramping down per ACC/dEC pattern 2 
ON: Motor runs forward, at speed set by Sr1, preset speed 1, 
ramping up per ACC/dEC pattern 2
31 [Rev-RMP2-SP1]
Combination of reverse 
run command, preset 
speed 1 command, and 
acceleration/deceleration 
pattern 2 selection
OFF: Motor stops, ramping down per ACC/dEC pattern 2 
ON: Motor runs in reverse, at speed set by Sr1, preset speed 1, 
ramping up per ACC/dEC pattern 2
32 [FW-RMP2-SP2]
Combination of forward 
run command, preset 
speed 2 command, and 
acceleration/deceleration 
pattern 2 selection
OFF: Motor stops, ramping down per ACC/dEC pattern 2 
ON: Motor runs forward, at speed set by Sr2, preset speed 2, 
ramping up per ACC/dEC pattern 2
33 [Rev-RMP2-SP2]
Combination of reverse 
run command, preset 
speed 2 command, and 
acceleration/deceleration 
pattern 2 selection
OFF: Motor stops, ramping down per ACC/dEC pattern 2 
ON: Motor runs in reverse, at speed set by Sr2, preset speed 2, 
ramping up per ACC/dEC pattern 2
34 [FW-RMP2-SP3]
Combination of forward 
run command, preset 
speed 3 command, and 
acceleration/deceleration 
pattern 2 selection
OFF: Motor stops, ramping down per ACC/dEC pattern 2 
ON: Motor runs forward, at speed set by Sr3, preset speed 3, 
ramping up per ACC/dEC pattern 2
35 [Rev-RMP2-SP3]
Combination of reverse 
run command, preset 
speed 3 command, and 
acceleration/deceleration 
pattern 2 selection
OFF: Motor stops, ramping down per ACC/dEC pattern 2 
ON: Motor runs in reverse, at speed set by Sr3, preset speed 3, 
ramping up per ACC/dEC pattern 2
38 [Frequency source]
Frequency reference 
source switching
OFF: drive follows speed reference set by parameter [Frequency mode sel] (FMOd)
ON: drive follows speed reference set by parameter [Remote spd ref 2] (F207) >
(if [Auto/man speed ref] (F200) = 1)
39 [Motor switch]
CAUTION
RISK OF DAMAGE TO THE MOTOR
z The motor switching function disables motor thermal protection.
z The use of external overload protection is required when using motor switching.
Failure to follow these instructions can result in death, serious injury, or equip-
ment damage.
OFF: 1
st
 motor V/Hz parameter set active: 
([Mot cont. mode sel.] (Pt), [Motor rated freq.] (uL), [Motor rated voltage] (uLu), [Mot 
Voltage Boost] (ub), [Motor thermal prot.] (tHr)) 
ON: 2
nd
 motor V/Hz parameter set active: 
(Pt = 0, F170, F171, F172, F173)
Function Action
No. Description