The program enables storing the read data for further analysis. Press the    button to save the data in 
.csv or .dat format, allowing reloading and displaying data in a chart window. 
 The information about the type of power supply, its  position in the manager list and  the communication 
address can be obtained by pressing the   button. This information is particularly useful when importing a file 
from another PSU. 
5.3.2 Reading the history of events of the power supply with LCD display. 
To read the history of events of the power supply with LCD display press the   button. The reading starts 
from the most recent entries. The reading can be stopped at any time by pressing the   button. 
Fig. 19. The „History” tab. 
The table of the history of events of the power supply includes information about: 
  Time and date – date and time of the event 
  Event description – event code and its description. Appendixes A, B and C at the end of the manual 
summarize all the failure and event codes that may occur during the power supply operation. The individual 
codes are accompanied by appropriate optical indication on the panel, acoustic indication and activation of 
the dedicated technical output. 
  AC – AC 230V power indication: 
ON = AC power on 
OFF = AC power off 
  LB – battery charging indication 
 ON = battery charging  
OFF = no charging, battery fully charged 
  EXTi – external failure input 
ON = failure 
OFF = normal status 
  EPS – technical output indicating AC power loss 
Open = AC power loss 
closed = AC power - OK. 
  PSU – technical output indicating PSU failure 
open = failure 
closed = PSU operation - OK 
  APS – technical output indicating battery failure 
open = battery failure 
closed = battery OK 
  EXTo – controlled relay output 
open = output on 
closed = output off 
  ALARM – technical output of collective failure 
 Open = AC power loss 
 closed = AC power - OK. 