Technical data

Auxiliary Output Parameters List • 15
Fnd Fan delay after defrost: (0 to 255 min) The time interval between the defrost end and evaporator fans start.
FCt
Temperature differential avoiding short cycles of fans (0.0°C to 50.0°C; 0°F to 90°F) If the difference of
temperature between the evaporator and the room probes is more than the value of the Fct parameter, the fans
are switched on.
FSt
Fan stop temperature: (-50 to 110°C; -58 to 230°F) setting of temperature, detected by evaporator probe,
above which the fan is always OFF.
FHy
Differential to restart fan: (0.1°C to 25.5°C) (1°F to 45°F) when stopped, fan restarts when fan probe reaches
FSt-FHy temperature.
Fod Fan activation time after defrost: (0 to 255 min.) it forces fan activation for indicated time.
Fon
Fan ON time: (0 to 15 min) with Fnc = C_n or C_y, (fan activated in parallel with compressor). Sets the
evaporator fan ON cycling time when the compressor is off. With Fon =0 and FoF ? 0 the fan are always off,
with Fon=0 and FoF =0 the fan are always off.
FoF
Fan OFF time: (0 to 15 min) with Fnc = C_n or C_y, (fan activated in parallel with compressor). Sets the
evaporator fan off cycling time when the compressor is off. With Fon =0 and FoF =0 the fans are always off,
with Fon=0 and FoF =0 the fans are always off.
MODULATING OUTPUT (AnOUT) If Present
trA
Kind of regulation with PWM output: (UAL - rEG - AC) it selects the functioning for the PWM output if
CoM is not equal to OA7. UAL= the output is at FSA value; rEG= the output is regulated with fan algorithm
described in fan section; AC= anti-sweat heaters control (require the XWEB5000 system).
SOA Fixed value for analog output: (0 to 100%) value for the output if trA = UAL.
SdP
Default value for Dew point: (-55.0 to 50.0°C; -67 to 122°F) default value of dew point used when there is
no supervising system (XWEB5000). Used only when trA=AC.
ASr
Dew-point offset (trA=AC) / Differential for modulating fan regulation (trA=rEG): (-25.5°C to 25.5°C) (-
45°F to 45°F).
PbA Differential for anti-sweat heaters: (0.1°C to 25.5°C) (1°F to 45°F)
AMi Minimum value for analog output: (0 to AMA)
AMA Maximum value for analog output: (Ami to 100)
AMt
Anti-sweat heaters cycle period (trA=AC)/ Time with fan at maximum speed (trA=rEG): (0 to 255 s) when
the fan starts, during this time the fan is at maximum speed.
ALARMS
rAL
Probe for temperature alarm: (nP - P1 - P2 - P3 - P4 - P5 - tEr) Selects the probe used to signal alarm
temperature
ALC
Temperature alarm configuration: rE = High and Low alarms related to Setpoint; Ab = High and low alarms
related to the absolute temperature.
ALU
High temperature alarm setting: (ALC= rE, 0 to 50°C or 90°F / ALC= Ab, ALL to 150°C or 302°F) when
this temperature is reached and after the ALd delay time the HA alarm is enabled.
ALL
Low temperature alarm setting: (ALC = rE, 0 to 50 °C or 90°F / ALC = Ab, - 55°C or - 67°F to ALU) when
this temperature is reached and after the ALd delay time, the LA alarm is enabled.
AHy
Differential for temperature alarm: (0.1°C to 25.5°C / 1°F to 45°F) Intervention differential for recovery of
temperature alarm.
Table 9-1 - XM670K to XM679K Parameters List