Technical data

38 • XM670K-XM679K I&O Manual 026-1218 Rev 0 19-DEC-2012
3. In the Num Network Ctrls: NetSetup screen, under
the ECT tab, enter the number of devices in the
Quantity field. (Max shows the maximum number
of devices allowed on the network.)
4. Press
to return to the Network Setup menu,
then select
- Network Summary.
5. Locate the units you added to the network list (press
and to scroll through the list). If desired, en-
ter a new name for each device in the Name field.
6. By default, each device in the network list has a
board number of 0. To set the address and begin
communication, choose the device and press .
In the list of MODBUS devices, choose the address
number corresponding to the XR670K - XR679K
address set up through the front display, and press
to select it. A window will open where you
can specify the address of the controller. If a net-
work ID has already been selected, its name will be
shown next to the network ID in this list. If the net-
work ID you are trying to assign has already been
used, you must set the address on this device to a
different number that is not being used.
7. Repeat Steps 5 and 6 until each device has a name
and address.
8. When finished, press
to return to the Network
Setup menu, then press
- Network Summary
(Figure 22-7). Locate the devices you set up, and
look at each device’s status in the Status field. You
will see one of the following messages:
Online - The device is communicating normally.
Offline - The device is not communicating, has not
been commissioned, is not functional, or is not pow-
ered up. Verify the device is powered up, wired cor-
rectly, and has the proper network address, baud
rate, and parity.
Unknown - The device is not communicating or has
not been commissioned. Verify the device is pow-
ered up, wired correctly, and has the proper network
address, baud rate, and parity.
No Port - No port is set up in the E2 Serial Config-
uration Manager to be a MODBUS port.
Wrong FW Rev - This message is likely caused by
the device having a firmware version older than the
minimum revision required by E2 for communica-
tion. Replace the device with a new one or a device
Figure 22-6 - Num Network Ctrls: NetSetup Screen
Figure 22-7 - Network Summary Screen
Figure 22-8 - List of MODBUS Devices