Specifications

LWLCWH COLUMBIA BOILER COMPANY REV. 13106
25
Monthly Boiler Check & Maintenance List
1. Test all fan interlocks.
2. Check main burner safety shut off valve(s) for operational closure.
3. Oil fired; check fuel pressure interlocks when provided.
4. Gas fired; check high and low fuel pressure switches.
5. Flue or stack dampers; make visual inspection for proper operation.
6. Inspect heating surfaces for cleanness.
Semiannual Boiler Check & Maintenance List
1. Inspect burner components; Refer to burner manufacturers instructions.
2. Check the flame failure system components; Refer to the burner section of this manual.
3. Check piping and wiring of all interlocks and shut off valves.
4. Internal boiler plate inspection. Remove hand-hole assemblies; use new gaskets when
replacing covers.
Annual Boiler Check & Maintenance List
1. Check operating Pressure Control Controller or Aquastat Controller.
2. Check high limit Pressure Control Controller or Aquastat Controller.
3. Test safety valves.
4. Remove the Low Water Cut Off and clean inside casting.
5. Oil fired - clean/replace oil filters or strainers if equipped
6. Oil fired - replace ignition electrodes if equipped.
7. Gas pilots - conduct pilot turndown test.
8. Gas fired - replace ignition and flame rods.
9. Gas fired - check drip leg/strainer.
10. Oil fired - check for refractory hold in.
11. Check Automatic Change Over Control if equipped.
12 Gas fired - perform valve leakage test.
Gauge Glass - Not required on hot water boilers only.
The water gauge glass must be kept clean. Dirt on, or in, the glass may be mistaken for the water
level. Do not allow steam or water to leak from the water glass, as this may effect the accuracy of
the level indication. Leaking of the gauge glass will also reduce the wall thickness of the glass to the
point where it may explode.
WARNING: DO NOT OPERATE THE BOILER WITHOUT THE GAUGE GLASS PROTECTOR
INSTALLED. NEVER ATTEMPT TO WORK ON THE GAUGE GLASS WHILE THE
BOILER IS UNDER PRESSURE. ALWAYS CLOSE GAUGE VALVES PRIOR TO
TIGHTENING GASKETS ON WATER LEVEL GAUGE GLASS. SERIOUS INJURY
COULD RESULT.