Install Instructions

Installation Manual - A-VMH18DU,28TU,36QU-1
6
WARNING
Appliance shall be installed, operated and stored in a room with a oor area larger than X m²
(Please see the following form ). The appliance shall not be installed in an unventilated space, if
that space is smaller than X m² (Please see the following form ).
Appliance shall be stored in a well-ventilated area where the room size corresponds to the room
area as specied for operation.
The appliance disconnection must be incorporated with an all-pole disconnection device using
hard wiring in accordance with electrical codes.
Any person who is involved with working on or breaking into a refrigerant circuit should hold a
current valid certificate from an industry-accredited assessment authority, which authorizes their
competence to handle refrigerants safely in accordance with an industry recognized assessment
specification.
Amount of refrigerant
to be charged (kg)
maximum installation
height (m)
Minimum room
area (m²)
2.048 2.2m 4
2.048 1.8m 4
2.048 0.6m 35
2.048-3.0 2.2m 4
2.048-3.0 1.8m 8
2.048-3.0 0.6m 80
>3.0 2.2m 5
>3.0 1.8m 9
>3.0
Model
(Btu/h)
30000
30000
30000
30000-48000
30000-48000
30000-48000
>48000
>48000
>48000 0.6m 80
The appliance shall be stored in a room without continuously operating ignition sources
(for example: open ames, an operating gas appliance or an operating electric heater).
Do not pierce or burn.
Be aware that the refrigerants may not contain an odour.
Compliance with national gas regulations shall be observed.
Servicing shall only be performed as recommended by the equipment manufacturer.
Maintenance and repair requiring the assistance of other skilled personnel shall be carried out
under the supervision of the person competent in the use of refrigerants.
The appliance shall be stored so as to prevent mechanical damage from occurring.
Keep ventilation openings clear of obstruction.
NOTE:
The following informations are required for the units adopt R32/R290 Refrigerant.