Brochure

3
Electrical Data
Model No. Nom.Tons Nom. CFM HP Volts/Ph. FLA MCA MOCP
AHG24 1.5-2.0 800 1/4 115-1-60 3.2 4.0 10.0
AHG30 2.5 1000 1/3 115-1-60 6.2 7.8 15.0
AHG36 3.0-3.5 1330 1/3 115-1-60 6.2 7.8 15.0
AHG48 3.0-4.0 1740 3/4 115-1-60 9.5 11.8 20.0
AHG60 5.0 2000 3/4 115-1-60 9.5 11.8 20.0
Hot Water Heating Capacity
Model
Number
Nom. CFM
Fan Speed
HeatingCapacity
GPM WPD APD
120
o
F 140
o
F 160
o
F 180
o
F
AHG24 715-M 12,820 18,310 23,940 29,700 4.0 2.5 0.14
AHG30 950-H 20,740 29,630 38,760 48,090 4.0 2.3 0.23
AHG36 1290-H 27,140 38,730 50,610 62,730 4.0 2.4 0.23
AHG48 1720-H 36,290 51,740 67,570 83,720 4.0 2.4 0.52
AHG60 1950-H 46,370 65,940 85,900 106,180 7.0 2.9 0.64
OperationofAHGAirHandlerwithhotwaterheat—
air handler blower is energized by a conventional
heating thermostat. Field installed pump (not included)
circulates water from the water heater to the heating
coil in the air handler, and the blower circulates warm
air through the duct system.
NOTE:Airhandlersarecapableofusinghotwater
from other sources such as boilers as long as the
watertemperaturedoesnotexceed180
o
F.
Dimensions (in.)
Model No. A B C D E F G
AHG24,30 17
1
/2 21 15 17
1
/2 16 12
5
/8 39
3
/4
AHG36,48,60 21
1
/2 25 19
1
/4 22
1
/4 19
5
/8 17
1
/4 49
3
/4