9. Installation is designed for new or existing ceilings. However, anchoring/mounting to wood, steel, and
concrete must follow all local/national building codes.
10. Mounting hardware for suspension in ceiling must be acquired locally. M10 or 3/8” diameter threaded
rods and nuts are the recommended to ensure a proper fit with the mounting flanges of the unit.
Location Considerations:
The location must take into consideration the size of the indoor unit, ceiling opening, and where the threaded
rods must be located to suspend the unit:
Model
Capacity
Ceiling Opening Dimensions Unit Dimensions Threaded Rod Dimensions
A x A in(mm) B x B in(mm) C1 x C2 in(mm)
12/18K
22.4(570) x 22.4 (570)
15.8(400) x 23.8(604)
24K 35.0(890) x 35.0(890) 33.1(840) x 33.1(840) 26.8(680) x 30.7(780)
12/18K Model Dimensions: 24K Model Dimensions:
Additional considerations:
Allow at least 6.3in (160mm) clearance from the top of the installation flange of the unit and the top of
the ceiling cassette panel.
The drop ceiling tile should overlap the edge of the ceiling cassette panel by at least 0.8in (20mm).
4
A
B
C1
AC2B
A
C2
B
A
B
C1
0.8in.(20mm)
6.3 in.
(160mm)