User Manual

Re-installing the right side cable access panel
IP-RN 8000 Installation & Commissioning Guide 207
Re-installing the right side cable access panel
This procedure explains how to re-install the right side cable access panel.
Required tools and materials:
5/32 inch tamper-resistant hex drive screw driver
5/8 inch open ended wrench
11/16 open ended wrench
Torque wrench with a 5/32 inch tamper-resistant hex drive bit
Thread tapping set with bit for 1/4-20 threads at 3/4 inch depth
To reinstall the right-side cable-access panel:
1. Locate the right-side access panel.
2. Retrieve the 12 tamper-resistant screws and rubber washers that you set aside when removing the panel.
3. Examine the inside edge of the access panel to ensure the access panel is undamaged:
The gasket on the inside edge must be intact to ensure a proper seal.
4. Slide the access panel into place along the grounding wires.
If the access panel does not slide towards the cabinet along the grounding wires, loosen the nuts
securing the access panel to each grounding wire.
NOTE
Conduit and cables may already be installed into the access
panel.
Right access panel