User Manual

Appendix A IP-RN 8000 Specifications
192 Release 2.0, 910056 Rev01d
Table 27 IP-RN 8000 physical and environmental specifications
Specification Description
Weight
Fully populated approximately 630 lbs (286 kg)
Dimensions
Height 59.5 inches (1511.3 mm)
Width 30.5 inches (774.7 mm)
Depth 39 inches (990.5 mm)
Operating temperature range
With heater
-40
°C to 46°C
Without heater
-10°C to 46°C
Startup and operation is possible at temperatures as low
as -40
°C, but the IP-RN 8000 may not satisfy all
specifications below -10°C.
Rate of temperature change
Not to exceed a change of more than 15
°C per hour.
Non-operating (storage) ranges
Temperature
-40°C to 70° C
Humidity 0 to 95% noncondensing
Loading Wind 150 miles per hour. Exp. D (241 kilometers per hour)
Snow 60 pounds per square foot (may be higher depending on
installation) (27.2 kilograms per square
Seismic Bellcore Zone 4 (GRE-CORE)
Ratings
UL UL 1950 (UL60950)
Construction Aluminum structure and body
Lifting eyes
1/2 inch diameter
Heat exchanger Closed loop design for use outdoors
Standard alarms
High temperature
Set-point 70°C
Low temperature
Set-point 14
°C
Intrusion On front door (pull the tech-on-site switch to override
the door alarm)
Altitude
Maximum 3000 meters