Installing CAP Ms
Determine the Power Consumption of the CAP M
Use the power consumption matrix in Table 6 to calculate power consumption for a CAP M, where
the consumption
numbers are at the CAP M power inputs and do not account for feed losses
the
maximum consumption numbers in Table 6 do not include the power consumed by any attached
auxiliary devices. Both CAP M power consumption and auxiliary device
power must be included when
calculating feed losses.
Table 6. CAP M Power Consumption
CAP M Model
Configuration
Voltage Range
(V
)
Typical Power
(W)
1 2
Maximum Power
(W)
1 2
Part Number Model Name
7781125-000x CAP M 9/18/21/26
AC 90 to 264 Vac 140 150
DC -36 to -60 Vdc 140 150
7820478-000x CAP M 7E/80-85/17E/19
AC 90 to 264 Vac 160 170
DC -36 to -60 Vdc 160 170
7820689-000x CAP M 23/23/25/25
AC 90 to 264 Vac 160 170
DC -36 to -60 Vdc 160 170
7835269-000x CAP M 6/6/7E/7E
AC 90 to 264 Vac 160 170
DC -36 to -60 Vdc 160 170
1 Does not include SFP+ Module consumption. Can support up t
o 3W (more with engineering consultation) maximum
total SFP+ Module consumption. Typical installation (sufficient for SM up to 10km or MM) would be 0.8W typical, 1.0W
max for each SFP+ Module.
2 Does not include power drawn by an external PoE device connected to the RJ45 Auxiliary port (Port A); in this
configuration, the CAP M will draw an additional 20W.
Mains power must be interruptible with an external delay-actions mains breaker. For the Mains breaker,
observe the following recommendations.
For the AC power supply, 120 Volt / 20 Amp maximum or 240 Volt
/ 16 Amp, single-phase, 50 / 60 Hz
AC service is needed. That is, the external AC breaker should be 20 Amps maximum for 120-Volt
service, or 13 to 16 Amps for 240-Volt service.
For the DC power supply, observe the local
regulations of the DC service provider.