Data Sheet

FEATURES
Transmits up to eight independent supervised or
unsupervised dry switch or relay contacts over one optical
fiber, or via a 2-wire RS-485 point-to-point copper circuit
Microprocessor-based logic and latching relays in the
receiver unit eliminate random contact closure states in the
event of a loss of the link, or a loss of prime operating power
Tested and certified by an independent laboratory for full
compliance with the environmental requirements (ambient
operating temperature, mechanical shock, vibration, humidity
with condensation, high-line/low-line voltage conditions and
transient voltage protection) of NEMA TS-1/TS-2 and the
Caltrans Specification for Traffic Signal Control Equipment
Indicating LEDs for monitoring power, contact closure status,
and summary fault
› Automatic resettable solid-state current limiters
Hot-swappable rack modules
Interchangeable between stand-alone or rack mount use –
ComFit
› Lifetime Warranty
APPLICATIONS
› Alarm Event Triggering
› Fire Alarm & Intrusion Detection Systems
› Lane/Gate Control
› PIR Signal Transmission
› Building Automation and Environmental Control Systems
The ComNet
FDC80 Series contact closure transmitter and receiver units provide
transmission of up to eight independent supervised or unsupervised dry switch or
relay contact closures over a single optical fiber, or any two-wire RS-485 copper circuit.
Microprocessor-based logic transmits the contact closure information in packets that
are ordered and encoded, ensuring extremely robust and reliable transmission. Packets
that are garbled, or packets out of sequence with transmission bit errors will not cause
random changes of state in the FDC80R receiver unit relays. The supervising function
in the FDC80T transmitter allows for the detection of short and open circuit conditions,
and normally open or normally closed contact inputs are supported. System faults
are displayed via LED status indicators, and user-programmable summary fault alarm
contacts are triggered in the FDC80R receiver unit. The FDC80R receiver is offered in
both latching and non-latching relay configurations. External series and shunt resistors are
included for each of the 8 contact input channels, for contact supervision.
FDC80 Series
8-Channel Supervised Contact Closure
Transmitter and Receiver
8
HARDENEDINCLUDED
LIFETIME WARRANTY WWW.COMNET.NET TECH SUPPORT: 1.888.678.9427

Summary of content (2 pages)