Cyclon Series User Manual – Commissioning
No. Action Reason Display
14. Press
PLUS
or
MINUS
To adjust the displayed value 1500
or go to step 16 if no adjustment
required. (pulsing display)
15. Press
STOP
To program the new value 1500
into the controller memory
(steady display)
16. Press
VIEW
To step to the next option
17. Indicator L4 will light and the 5.0
display will show the solenoid
valve 'open' time setting.
18. Press
PLUS
or
MINUS
To adjust the displayed value 2.0
or go to step 20 if no adjustment
required. (pulsing display)
19. Press
STOP
To program the new value 2.0
into the controller memory
(steady display)
20. Press
VIEW
To step to the next option
21. Indicator L5 will light and the display 7.0 bar
will show the lower pressure set
point P2.
22. Press
PLUS
or
MINUS
To adjust the displayed value 6.5 bar
or go to step 16 if no adjustment
required. (pulsing display)
23. Press
STOP
To program the new value 6.5 bar
in to the controller memory
(steady display)
24. Press
VIEW
To step to the next option
25. Indicator L6 will light and the display C215
will show the compressor model
26. Press
PLUS
or
MINUS
To adjust the displayed value C330
until the displayed model
matches the model number (pulsing display)
shown on the compressor
data plate.
27. Press
STOP
To program the new value C330
in to the controller memory
(steady display)