User manual
CompAir BroomWade Limited
page 30
No. Action Reason Display
28. Press
VIEW
To step to the next option
29. Indicator L7 will light and the display 0 secs
will show the Auto restart delay time.
30. If the auto restart facility is
required press
PLUS
or
MINUS
. To adjust the displayed value 60 secs
If the facility is not required set
the display to 0 seconds, this (pulsing display)
will disable the facility.
31. Press
STOP
To program the new value 60 secs
in to the controller memory
(steady display)
32. Press
VIEW
To step to the next option
33. Indicator L8 will light and the display 3 mins
will show the Run-on time.
34. Press
PLUS
or
MINUS
To adjust the displayed value 5 mins
or go to step 28 if no adjustment
required. (pulsing display)
35. Press
STOP
To program the new value 5 mins
in to the controller memory
(steady display)
36. Press
RESET
To exit Program mode. 0.0 Bar
1.4 Final Checks
No. Action Reason Display
1. Switch power ‘ON’ at the isolator 0.0 bar
and allow the controller to initialise.
2. Press
START
To start the compressor 0.0 Bar
and check direction of rotation
CAUTION: Do not repeatedly start May cause motor overheating,
and stop the compressor. contactor damage or air-end
seizure.
Note: The motor may appear to turn
slowly for the first few revolutions before
beginning to run up to speed. This is
normal and should not be considered
a fault condition.